WEG SSW7000 User manual

Category
Networking
Type
User manual
Motors | Automation | Energy | Transmission & Distribution | Coatings
Anybus-CC
SSW7000
User’s Manual
Anybus-CC User’s Manual
Series: SSW7000
Language: English
Document no: 10001038457 / 01
Publication date: 01/2011
Preface
Dear Customer,
The SSW7000 soft-starter is a product developed with quality and efficiency levels that assure excellent
performance.
This product must be properly identified and handled, because its characteristics require certain attention, as for
storage, installation and maintenance.
If doubts persist, we ask you to contact WEG.
Keep this manual always close to the product, so that it can be consulted whenever necessary.
ATTENTION!
1. It is necessary to follow the procedures contained in this manual, so that the warranty is valid.
2. The product installation, operation and maintenance procedures must be performed by qualified
personnel.
NOTE!
SSW7000| 3
1.
The total or partial reproduction of the information of this manual is allowed, as long as the source is
mentioned;
2. Should this manual be lost, the electronic file in PDF format is available on the
www.weg.net web site, or
another hard copy may be requested.
WEG EQUIPAMENTOS ELÉTRICOS S.A.
Revision Index
SSW7000| 4
Revision Description Chapter
01 First edition -
Contents
SSW7000| 5
CONTENTS
1 INTRODUCTION TO THE FIELDBUS...................................................................8
2 ACCESSORY KITS (ACTIVE MODULES) .............................................................9
2.1 DEVICENET ................................................................................................................................. 9
2.1.1 DEVICENET-05 KIT.....................................................................................................................9
2.1.2 CONNECTOR PINOUT.....................................................................................................................9
2.1.3 INDICATIONS.................................................................................................................................9
2.1.4 CONNECTION TO THE NETWORK .....................................................................................................9
2.1.5 MODULE CONFIGURATION............................................................................................................10
2.1.6 ACCESS TO THE PARAMETERS ......................................................................................................10
2.2 PROFIBUS DP-V1 .......................................................................................................................10
2.2.1 PROFIBUS-05 KIT ....................................................................................................................10
2.2.2 CONNECTOR PINOUT...................................................................................................................11
2.2.3 INDICATIONS...............................................................................................................................11
2.2.4 CONNECTION TO THE NETWORK ...................................................................................................11
2.2.5 MODULE CONFIGURATION............................................................................................................11
2.2.6 ACCESS TO THE PARAMETERS ......................................................................................................12
2.3 ETHERNET/IP.............................................................................................................................12
2.3.1 KIT ETHERNETIP-05.................................................................................................................12
2.3.2 CONNECTOR ..............................................................................................................................12
2.3.3 INDICATIONS...............................................................................................................................12
2.3.4 CONNECTION TO THE NETWORK ...................................................................................................13
2.3.5 MODULE CONFIGURATION............................................................................................................13
2.3.6 BAUD RATE................................................................................................................................14
2.3.7 ACCESS TO THE PARAMETERS VIA WEB ........................................................................................15
3 ACCESSORY KITS (PASSIVE MODULES) .........................................................17
3.1 RS232 .....................................................................................................................................17
3.2 RS232-05 KIT...........................................................................................................................17
3.3 CONNECTOR PINOUT ...................................................................................................................17
3.3.1 INDICATIONS...............................................................................................................................17
3.3.2 CONNECTION TO THE NETWORK ...................................................................................................18
3.4 RS485/422 ..............................................................................................................................18
3.4.1 RS485-05 KIT...........................................................................................................................18
3.4.2 CONNECTOR PINOUT...................................................................................................................18
3.4.3 INDICATIONS...............................................................................................................................18
3.4.4 CONNECTION TO THE NETWORK ...................................................................................................18
4 SSW PARAMETER SETTINGS..........................................................................19
4.1 SYMBOLS FOR PROPERTIES DESCRIPTION ........................................................................................19
P0220 LOCAL/REMOTE MODE SELECTION..........................................................................................19
P0229 LOCAL COMMAND SELECTION ..................................................................................................19
P0230 REMOTE COMMAND SELECTION................................................................................................19
P0313 COMMUNICATION ERROR ACTION................................................................................................19
P0680 SSW STATUS WORD................................................................................................................20
P0686 ANYBUS-CC CONTROL WORD ...................................................................................................21
P0692 CONFIURATION MODE STATUS....................................................................................................22
P0693 CONFIGURATION MODE COMMANDS ............................................................................................23
P0695 VALUE FOR THE DIGITAL OUTPUTS...............................................................................................24
P0696 VALUE 1 FOR ANALOG OUTPUTS .................................................................................................24
P0697 VALUE 2 FOR ANALOG OUTPUTS .................................................................................................24
P0723 ANYBUS IDENTIFICATION............................................................................................................25
Contents
SSW7000| 6
P0724 ANYBUS COMMUNICATION STATUS..............................................................................................26
P0725 ANYBUS ADDRESS ...................................................................................................................26
P0726 ANYBUS BAUD RATE ................................................................................................................26
4.2 NUMBER OF EXCHANGED WORDS ....................................................................................................27
P0728 ANYBUS READING # 2...............................................................................................................28
P0729 ANYBUS READING # 3...............................................................................................................28
P0730 ANYBUS READING # 4...............................................................................................................28
P0731 ANYBUS READING # 5...............................................................................................................28
P0732 ANYBUS READING # 6...............................................................................................................28
P0733 ANYBUS READING # 7...............................................................................................................28
P0734 ANYBUS READING # 8...............................................................................................................28
P0735 ANYBUS READING # 9...............................................................................................................28
P0736 ANYBUS READING # 10.............................................................................................................28
P0737 ANYBUS READING # 11.............................................................................................................28
P0738 ANYBUS READING # 12.............................................................................................................28
P0739 ANYBUS READING # 13.............................................................................................................28
P0740 ANYBUS READING # 14.............................................................................................................28
P0741 ANYBUS READING # 15.............................................................................................................28
P0742 ANYBUS READING # 16.............................................................................................................28
P0743 ANYBUS READING # 17.............................................................................................................28
P0744 ANYBUS READING # 18.............................................................................................................28
P0745 ANYBUS READING # 19.............................................................................................................28
P0746 ANYBUS READING # 20.............................................................................................................28
P0747 ANYBUS READING # 21.............................................................................................................28
P0748 ANYBUS READING # 22.............................................................................................................28
P0749 ANYBUS READING # 23.............................................................................................................28
P0750 ANYBUS READING # 24.............................................................................................................28
P0751 ANYBUS WRITING # 2 ...............................................................................................................29
P0752 ANYBUS WRITING # 3 ...............................................................................................................29
P0753 ANYBUS WRITING # 4 ...............................................................................................................29
P0754 ANYBUS WRITING # 5 ...............................................................................................................29
P0755 ANYBUS WRITING # 6 ...............................................................................................................29
5 DEVICENET PROTOCOL..................................................................................30
5.1 INTRODUCTION ...........................................................................................................................30
5.2 PHYSICAL LAYER.........................................................................................................................30
5.3 DATA LINK LAYER .......................................................................................................................31
5.4 NETWORK AND TRANSPORT LAYER .................................................................................................31
5.5 APPLICATION LAYER CIP PROTOCOL ............................................................................................31
5.6 CONFIGURATION FILE ...................................................................................................................32
5.7 COMMUNICATION MODES ..............................................................................................................32
5.8 PREDEFINED MASTER/SLAVE CONNECTIONS SET ...............................................................................33
5.9 DEVICENET MODULE STATUS ........................................................................................................33
5.10 DEVICENET NETWORK STATUS ...................................................................................................33
6 PROFIBUS DP-V1 PROTOCOL.........................................................................35
6.1 INTRODUCTION ...........................................................................................................................35
6.2 BASIC CHARACTERISTICS..............................................................................................................35
6.3 PROTOCOL ARCHITECTURE ...........................................................................................................35
6.4 TRANSMISSION MEDIUM ...............................................................................................................36
6.5 BAUD RATE AND CONNECTORS......................................................................................................37
6.6 CONFIGURATION FILE ...................................................................................................................37
6.7 COMMUNICATION MODULE STATUS ................................................................................................37
6.8 OPERATION MODE STATUS ............................................................................................................38
7 ETHERNET/IP PROTOCOL...............................................................................39
7.1 INTRODUCTION ...........................................................................................................................39
Contents
SSW7000| 7
7.2 PHYSICAL LAYER.........................................................................................................................39
7.3 DATA LINK LAYER .......................................................................................................................40
7.4 NETWORK AND TRANSPORT LAYER..................................................................................................40
7.5 CONFIGURATION FILE ...................................................................................................................41
7.6 ETHERNET/IP MODULE STATUS .....................................................................................................41
7.7 ETHERNET/IP NETWORK STATUS ...................................................................................................41
7.8 LINK/CONNECTION STATUS...........................................................................................................41
8 FAULTS AND ALARMS RELATED TO THE ANYBUS-CC COMMUNICATION ......42
A129/F229 OFFLINE ANYBUS-CC MODULE............................................................................................42
A130/F230 ANYBUS-CC MODULE ACCESS ERROR .................................................................................42
Introduction to the Fieldbus
1 INTRODUCTION TO THE FIELDBUS
The Fieldbus is a digital communication system used in the industry to connect primary automation elements,
such as PLCs, drives, valves, sensors, actuators etc., as illustrated in the
Figure 1.1 below.
Figure 1.1: Illustration of a Fieldbus network
The concept that was born at the end of the 1980s, it appeared as an alternative to the limited analogue
systems (4-20mA and +/-10V). In the analog control, the installation of long wires and cables from each device
to the central controller was frequent. This led to high cabling costs, difficult maintenance and also
compromised the system expansion.
The first industrial digital networks that appeared used proprietary solutions created by big manufactures. There
was no concern with interaction or standardization. The customer options regarding suppliers were restricted.
However, the crescent demand for process improvements turned this situation around. Several technologies
appeared. Standardization became important because of the involved costs. Organizations responsible for the
promotion and update of networks and protocols, many of them open, were created. User groups with the
purpose of mutual help also appeared.
Nowadays, there is a great variety of protocols in the market, each one with its advantages and disadvantages.
It is up to the user/project designer to evaluate what the necessary requirements for the application are, and
choose among the available options.
Regardless of the choice, the main advantages of the industrial networks are:
Significant reduction in cable and installation costs;
Reduction of the start-up time;
More reliability and efficiency;
Addition, removal and replacement of equipment with the network under load (supply);
Integration of several suppliers (standardization);
Effective process monitoring;
Device configuration through the network.
The SSW supports, by means of the Anybus-CC communication module, three protocols widely spread in the
industry: DeviceNet, Profibus DP-V1 and EtherNet/IP.
The characteristics of the Anybus-CC modules available for the SSW, as well as the protocols used by these
modules, will be presented next.
SSW7000| 8
Accessory Kits (active modules)
2 ACCESSORY KITS (ACTIVE MODULES)
In order to make available a DeviceNet, Profibus DP-V1 or EtherNet/IP interface for the SSW, it is necessary to
use one of the communication kits described next. Information on the installation of these kits can be obtained
in the guide that comes with them.
2.1 DEVICENET
2.1.1 DEVICENET-05 Kit
WEG part number: 10413655.
It is composed by the Anybus ABCC-DEV communication
module, mounting instructions and a torx screwdriver for fixing
the module.
ODVA certified interface.
It allows the programming of the drive via network
configuration software.
2.1.2 Connector Pinout
The DeviceNet communication module presents a male plug-in connector with the following pinout:
Table 2.1: DeviceNet plug-in connector pinout
Pin Name Function
1
V-
Power supply negative pole
2
CAN_L
CAN_L signal
3
Shield
Cable shield
4
CAN_H
CAN_H signal
5 V+ Power supply positive pole
2.1.3 Indications
MS LED: bicolor LED (green/red). It indicates the communication module status.
NS LED: bicolor LED (green/red). It indicates the DeviceNet network status.
For a better interpretation of the indications above, refer to the sections
5.9 and 5.10.
2.1.4 Connection to the Network
For the connection of the using the active DeviceNet interface, the following points must be observed:
It is recommended to use cables specific for CAN/DeviceNet networks.
Grounding of the cable shield at only one point, thus avoiding current loops. This point is normally the
network own power supply. If there is more than one power supply, they must be referenced to the same
point.
Termination resistors must be installed only at the extremes of the main bus, even if there are derivations.
The network power supply must be able to supply the current for all the equipment transceivers. The SSW
DeviceNet module consumes approximately 50 mA.
SSW7000| 9
Accessory Kits (active modules)
2.1.5 Module Configuration
In order to configure the DeviceNet module, follow the steps indicated below:
With the SSW switched off, install the module on the XC44 connector. Make sure it is fitted in correctly and
secured by the screws.
Apply power to the SSW.
Observe the content of the parameter P0723. Verify whether the module has been recognized. The
detection occurs automatically and does not require any user intervention. The module MS LED must be on
in solid green. During the module acknowledgement phase a warning message will be showed on the
product HMI.
Set the SSW network address through the parameter P0725.
- Valid values: 0 to 63.
Adjust the baud rate at P0726:
- 0 = 125 kbps;
- 1 = 250 kbps;
- 2 = 500 kbps;
- 3 = Autobaud.
The number of words to be exchanged with the network master is defined automatically (refer to the section
4.2). The default is 1 input and 1 output word. The same number of words must be adjusted at the
DeviceNet Master.
Cycle the SSW auxiliary power supply, so that the changes become effective.
Connect the network cable to the module.
Register the configuration file (EDS file) in the network configuration software
1.
Add the SSW to the scan list of the master.
Choose a method for data exchange with the master in the network configuration software, i.e., polled,
change of state, cyclic or bit-strobe. The SSW DeviceNet module supports all those types of I/O data,
besides of the explicit (acyclic data).
If everything is configured correctly, the NS LED will go on in solid green. It is in that condition that the cyclic
data exchange between the SSW and the network master effectively occurs.
For more information regarding the mentioned parameters, refer to the section
3.
2.1.6 Access to the Parameters
After the EDS file registration in the network configuration software, the user will get access to the equipment
complete parameter list, which can be accessed via explicit messages.
For details on the use of this resource, refer to the PLC programming software documentation.
2.2 PROFIBUS DP-V1
2.2.1 PROFIBUS-05 Kit
WEG part number: 10413654.
It is composed by the Anybus ABCC-DPV1 communication
module, mounting instructions and a torx screwdriver for fixing
the modu
le.
Interface certified by Profibus International.
It supports DP-V1 functions (acyclic messages).
1
The SSW7000 DeviceNet communication module will be recognized by the network configuration software as Anybus- CC DeviceNet.
SSW7000| 10
Accessory Kits (active modules)
2.2.2 Connector Pinout
The Profibus DP-V1 communication module has a female DB9 connector with the following pinout:
Table 2.2: Profibus
2
female DB9 connector pinout
Pin Name Function
1 - -
2 - -
3 B-Line (+) RxD/TxD positive
4 RTS Request To Send
5 GND Ground (isolated from the RS485 circuit)
6 +5 V
+5V for active termination (isolated from the
RS485 circuit)
7 - -
8 A-Line (-) RxD/TxD negative
9 - -
2.2.3 Indications
ST LED: bicolor LED (green/red). It indicates the communication module status.
OP LED: bicolor LED (green/red). It indicates the operation mode status.
For a better interpretation of the indications above, refer to the sections
6.7 and 6.8.
2.2.4 Connection to the Network
For the SSW connection using the Profibus active interface, the following points must be observed:
It is recommended to use a shielded cable with a twisted pair of wires, preferable one specific for Profibus.
The connector must also be compatible with the Profibus specification.
The cable must be laid separately (and far away if possible) from the power cables.
All the network devices must be properly grounded, if possible at the same point. The cable shield must
also be connected to the protective ground. The Profibus connector normally has a point for connecting the
cable shield.
Termination resistors must be installed only at the extremes of the main bus, even if there are derivations.
Switches for enabling those resistors are normally present at the Profibus connector.
2.2.5 Module Configuration
In order to configure the Profibus DP-V1 module follow the steps indicated below:
With the SSW switched off, install the module on the XC44 connector. Make sure it is fitted in correctly and
secured by the screws.
Apply power to the SSW.
Observe the content of the parameter P0723. Verify if the module was recognized. The detection occurs
automatically and does not require any intervention from the user. The ST LED from the module must be on
in solid green. During the module acknowledgement phase a warning message will be showed on the
product HMI.
Set the SSW network address by means of the parameter P0725.
- Valid values: 1 to 126.
It is not necessary to set the module baud rate. Profibus uses autobaud; therefore, this configuration is
done by means of the network master.
2
The SSW7000 requires the use of a 180 º connector.
SSW7000| 11
Accessory Kits (active modules)
The number of words to be exchanged with the network master is defined automatically (refer to the section
4.2). The default is 1 input and 1 output word. The same number of words must be adjusted at the Profibus
Master.
Cycle the SSW auxiliary power supply, so that the changes become effective.
Register the configuration file (GSD file) in the network configuration software
3
.
Add the SSW to the device list of the master, setting the number of words according to the programmed in
the SSW.
Connect the network cable. If everything is configured correctly, the module OP LED will go on in solid
green. It is in that condition that the cyclic data exchange between the SSW and the network master
effectively occurs.
For more information regarding the mentioned parameters, refer to the section
3.
2.2.6 Access to the Parameters
The PROFIBUS-05 communication kit allows parameter reading/writing services by means of DP-V1 acyclic
functions. The parameter mapping is done based on the slot and index addressing, as showed in the equations
below:
Slot: (parameter number - 1) / 255
Index: (parameter number - 1) MOD 255
NOTE: MOD represents the remainder of the division.
2.3 ETHERNET/IP
2.3.1 Kit ETHERNETIP-05
WEG part number: 10509967.
It is composed by the Anybus ABCC-EIP communication
module, mounting instructions and a torx screwdriver for fixing
the module.
Standard RJ45 connector.
ODVA certified interface.
It allows access (reading/writing) to certain parameters via WEB.
2.3.2 Connector
The EtherNet/IP communication module has a common female RJ45 connector. The same mounting standard
(T-568A or T-568B) used in cables for office networks can also be adopted for the industrial environment.
However, the drive installation site must be verified. Cables and connectors normally used in office networks use
to be fragile. They cannot withstand high temperatures, high mechanic stress, excessive vibration and do not
have a high protection degree. The responsible for the plant installation must evaluate those factors and suggest
adaptations according to the needs.
2.3.3 Indications
MS LED: bicolor LED (green/red). It indicates the communication module status.
NS LED: bicolor LED (green/red). It indicates the EtherNet/IP network status.
LINK LED: green LED. It indicates connection (link) and also activity in the network.
For a better interpretation of the indications above, refer to the sections
7.6, 7.7 and 7.8.
3
The SSW7000 with Profibus DP-V1 communication module will be recognized by the network configuration software as Anybus-CC
Profibus DP-V1.
SSW7000| 12
Accessory Kits (active modules)
2.3.4 Connection to the Network
For the connection of the SSW using the active EtherNet/IP interface, the following points must be observed:
The SSW must be connected to an EtherNet/IP network preferably by means of switches. Hubs are not
recommended because they do not use the channel in an efficient way (great number of collisions).
The most common topology is in star, exactly the way it is done with computer networks.
It is recommended to use equipment (cables, switches) prepared for industrial environment.
Each cable segment (switch SSW) with a maximum length of 90 m.
2.3.5 Module Configuration
In order to configure the EtherNet/IP module follow the steps indicated below:
With the SSW switched off, install the module on the XC44 connector. Make sure it is fitted in correctly and
secured by the screws.
Apply power to the SSW.
Observe the content of the parameter P0723. Verify whether the module has been recognized. The
detection occurs automatically and does not require any user intervention.
The MS and NS LEDs from the
module must be flashing in green
4
.
Connect a network cable to the module. The other extreme of the cable must be connected to a hub/switch
or, occasionally a PC (for the PC SSW connection use a cross-over cable). If the network cable is
installed correctly, the LINK LED will go on in solid green indicating that a successful connection occurred. If
this does not occur, make sure the cable is in good conditions and the hub/switch is on.
With the aid of a PC connected to the same network where the SSW with the EtherNet/IP is present,
execute the HMS AnyBus IPconfig
5
program. This software will scan the network for the module. In the
example below a module with the IP 192.168.0.4 was found.
In order to change those configurations, double-click the module IP address. The window below will be
displayed. Set those parameters according to the network where the SSW will be installed. Remember that
the IP address is unique, i.e., each equipment in the network has its own address. The IP duplicity is a
critical fault and causes serious communication problems among the devices.
4
The SSW7000 with EtherNet/IP communication module will be recognized by the network configuration software as Anybus-CC
EtherNet/IP.
5
It is available on the CD-ROM that comes with the SSW.
SSW7000| 13
Accessory Kits (active modules)
The number of words to be exchanged with the network master is defined automatically (refer to the section
4.2). The default is 1 input and 1 output word. The same number of words must be adjusted at the
EtherNet/IP Master.
Connect the network cable to the module.
Register the configuration file (EDS file) in the network configuration software.
If everything is configured correctly, the NS LED will go on in solid green and the LINK LED will start blinking
indicating normal network activity.
For more information regarding the mentioned parameters, refer to the section
3.
2.3.6 Baud Rate
The SSW with EtherNet/IP kit works in networks with 10 Mbps or 100 Mps rates, in half-duplex or full-duplex
mode. When working at 100 Mbps full-duplex, the effective baud rate doubles, changing to 200 Mbps. The
baud rate setting is done only via software, as illustrated below:
In order to perform such setting, it is necessary to have a PC with an Internet browser connected to the
same network (same IP addressing range) of the SSW.
Open the browser and type the hostname or the IP address of the SSW. In the example below, we use the
IP 192.168.0.4.
Click on ‘Network interface’. A window with information about the communication module will be displayed.
SSW7000| 14
Accessory Kits (active modules)
Next, click on ‘Network Configuration’. In order to set the baud rate select the option ‘Comm Settings’.
Save the modifications clicking on the ‘Store Settings’ button.
2.3.7 Access to the Parameters via WEB
The SSW allows access for reading and writing via web certain parameters previously programmed by the user
(refer to the section
7). This function allows the operator to monitor the SSW status, being necessary only a
computer with access to the industrial plant network.
In order to use this function follow the steps indicated below:
Make sure the SSW is online. Verify the Anybus communication status via the parameter P0724.
Again, it is necessary to have a PC with an Internet Browser connected to the same network (same IP
addressing range) of the SSW.
Open the browser and type the hostname or the IP address of the SSW. In this example, the SSW has the
IP 192.168.0.4. The window showed in the figure 2.1 will be displayed.
Click on ‘Parameter data’. Another window containing the reading and writing parameters will be showed.
In this case, one reading parameter (SSW Status Word) and one writing parameter (Anybus-CC Control
Word) are showed. This window will show all the parameters programmed by the user.
SSW7000| 15
Important: The parameter writing via WEB (acyclic) is performed in a way similar to the I/O data (cyclic). Thus, if
a specific variable is accessible via cyclic as well as acyclic connections, one will be overwritten by the other. In
the case above, writing in the ‘Anybus-CC Control Word” will be almost immediately overwritten by the value
sent via the I/O cyclic connection. The same happens with the next word. In this case one gets the wrong
impression that the command had not been executed.
SSW7000| 16
Accessory Kits (passive modules)
3 ACCESSORY KITS (PASSIVE MODULES)
In order to make available a RS232 or a RS485/422 interface at the SSW, one of the communication kits
described next can be used. The operation of those modules follows the same principle of the serial interface.
For this reason it is not possible to use them simultaneously with the RS485-01, RS232-01 and CAN/RS485-01
communication kits. If this occurs, the A130 alarm message will be showed on the HMI to indicate hardware
incompatibility.
Those passive devices work only as physical layer converters, not performing any processing over the data flow.
This means that any serial protocol programmed in P0312 (Modbus-RTU, TP) can be used with those
interfaces.
For more information on the operation of those passive modules, refer to the SSW7000 Modbus-RTU User’s
Manual. Instructions on the installation of those modules can be obtained in the guide that comes with the kit.
3.1 RS232
3.2 RS232-05 KIT
WEG part number: 10413656.
It is composed by the Anybus ABCC-RS232 communication
module (drawing at the left), mounting instructions and a torx
screwdriver for fixing the module
It allows baud rates up to 115.2 kbps.
3.3 CONNECTOR PINOUT
The RS232 communication module presents a male DB9 connector (XC8) with the following pinout:
Table 3.1: RS232 DB9 male connector pinout
Pin Name Function
1 - -
2 RxD RS232 data reception
3 TxD RS232 data transmission
4 - -
5 GND Ground
6 - -
7 RTS Request To Send
8 - -
9 - -
3.3.1 Indications
PWR LED: Green LED. When on, it indicates that the module is powered.
SSW7000| 17
Accessory Kits (passive modules)
3.3.2 Connection to the Network
For the connection of the SSW using the passive RS232 interface, the following points must be observed:
Use good quality cables, preferably shielded.
Keep the cable length within the limits stipulated by the standard, normally about 10 m.
Avoid passing the cables close to output and input power cables.
3.4 RS485/422
3.4.1 RS485-05 Kit
WEG part number: 10413657.
It is composed by the Anybus ABCC-RS485 communication
module (drawing at the left), mounting instructions and a torx
screwdriver for fixing the module
It allows baud rates up to 115.2 kbps.
3.4.2 Connector Pinout
The RS485/422 interface module presents a female DB9 connector with the following pinout:
Table 3.2: RS485/422 female DB9 connector pinout
Pin RS422 mode RS485 mode Function
1 Term Pwr Term Pwr +5 V for active termination (isolated)
2 - - -
3 - - -
4 Mode Select Mode Select Not connected in RS485 mode; Ground in RS422 mode
5 GND GND Isolated ground
6 RxD -
7 RxD (inverted) -
Data reception line in RS422 mode
Not connected in RS485 mode
8 TxD RxD/TxD
9 TxD (inverted) RxD/TxD (inverted)
Data transmission line in RS422 mode
Bidirectional data line in RS485 mode
3.4.3 Indications
PWR LED: Green LED. When on, it indicates that the module is powered.
3.4.4 Connection to the Network
For the connection of the SSW using the passive RS485 interface, the following points must be observed:
Use good quality shielded cables.
Keep the cable length within the limits stipulated by the standard, normally about 1000 m.
Even being the RS485 more robust than the RS232 because of its cables using signals in differential mode
(balanced signals), avoid passing them close to power cables.
Put termination resistors between the data signal wires (RxD/TxD and TxD/RxD) at the network extreme
nodes. This will avoid reflections in the line.
SSW7000| 18
SSW Parameter Settings
4 SSW PARAMETER SETTINGS
Next, only the SSW parameters related to the Anybus-CC communication will be presented.
4.1 SYMBOLS FOR PROPERTIES DESCRIPTION
RO
Read-only parameter.
CFG
Parameter that can be changed only with a stopped motor.
Net
Parameter visible on the HMI if the SSW has a network interface installed – RS232,
RS485, CAN, Anybus-CC, Profibus – or if the USB interface is connected.
Serial
Serial Parameters visible on the HMI if the SSW has the RS232 or the RS485 interface
installed.
USB
Parameters visible on the HMI if the SSW USB interface is connected.
Anybus
Parameters visible on the HMI if the Anybus-CC module is connected.
P0220 – LOCAL/REMOTE Mode Selection
P0229 – LOCAL Command Selection
P0230 – REMOTE Command Selection
These parameters are used for the configuration of the SSW local and remote mode command sources. In
order that the SSW is controlled through the Anybus-CC interface, one of the ‘Anybus-CC’ options available in
the parameters must be selected.
The detailed description of these parameters is found in the Soft-Starter SSW7000 Programming Manual.
P0313 – Communication Error Action
Adjustable 0 = Off Factory setting: 0
Range: 1 = Ramp Stop
2 = General Disable
3 = Goes to Local
4 = Off
5 = Causes Fault
Properties: CFG, Net
Access groups via HMI: 01 PARAMETER GROUPS...
33 Communication... ... ... . ..
131 RS232/485 Serial... ... ...
Description:
It allows programming the action the SSW must take if a communication error is detected.
Table 4.1: Parameter P0313 options
Options Description
0 = Off No action is taken and the SSW remains in the existing
status.
1 Ramp Stop A stop command with deceleration ramp is executed and
the motor stops according to the programmed deceleration
ramp.
2 = General Disable The SSW is General Disabled and the motor coasts to stop.
3 = Goes to Local The SSW is commanded to the local mode.
0 = Off No action is taken and the SSW remains in the existing
status.
5 = Causes Fault Instead of an alarm, a communication error causes a SSW
fault, and it is necessary to perform a fault reset in order to
restore the normal operation.
SSW7000| 19
SSW Parameter Settings
For the Anybus-CC interface, the events of Anybus-CC module offline (A129 alarm/F229 fault) and Anybus-CC
module access error (A130 alarm/F230 fault) are considered communication errors.
The actions described in this parameter are executed by means of the automatic writing of the respective bits in
the Anybus-CC control word – P0686. In order to be effective, it is necessary that the SSW be programmed to
be controlled via Anybus. This programming is done by means of the parameters P0220, P0229 and P0230.
P0680 – SSW Status Word
Adjustable 0000h – FFFFh Factory setting: -
Range:
Properties: RO
Access groups via HMI: 01 PARAMETER GROUPS...
33 Communication... ... ... ...
130 Status/Commands... ...
Description:
It allows the user to identify the status of the SSW.
Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Function
Fault
Power Section
Supply
Configuration Mode
By-pass
Reverse Rotation
Rotation Reversion
Braking
Remote
Deceleration Ramp
Alarm
Full Voltage
P0831 Time
Acceleration Ramp
JOG
General Enabled
Running
SSW7000| 20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43

WEG SSW7000 User manual

Category
Networking
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI