EDWARDS 106DEXSTC-FJ Series Installation guide

Type
Installation guide

EDWARDS 106DEXSTC-FJ Series is a strobe light intended for indoor use in fire alarm systems and other applications requiring electrical supervision of signaling circuit field wiring. When assembled, the device is UL listed for use in various hazardous locations.

The strobe light has a clear lens, flashes at a rate of approximately 65 times per minute, and has a rated light output of 55 cd ceiling and 35 cd in other directions. It can operate within a voltage range of 20-30V DC and has special application voltage range of 20-30V DC. The strobe light requires supply wire temperature ratings of 75°C when the ambient temperature is 40°C, 90°C when the ambient temperature is 55°C, and 105°C when the ambient temperature is 65°C.

EDWARDS 106DEXSTC-FJ Series is a strobe light intended for indoor use in fire alarm systems and other applications requiring electrical supervision of signaling circuit field wiring. When assembled, the device is UL listed for use in various hazardous locations.

The strobe light has a clear lens, flashes at a rate of approximately 65 times per minute, and has a rated light output of 55 cd ceiling and 35 cd in other directions. It can operate within a voltage range of 20-30V DC and has special application voltage range of 20-30V DC. The strobe light requires supply wire temperature ratings of 75°C when the ambient temperature is 40°C, 90°C when the ambient temperature is 55°C, and 105°C when the ambient temperature is 65°C.

P/N 3100101 ISSUE 6 © 2003
CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH. SERV.)
Installation Instructions for 106DEXST-FJ AdaptaBeacon
®
Strobe Lights for Use in Hazardous Locations
DescriptionDescription
DescriptionDescription
Description
The 106DEXSTC-FJ (clear lens only) AdaptaBeacons are in-
rush current limited strobe lights that are UL1971 listed as
Special Application 20-30V DC Signaling Appliances for
the Hearing Impaired, with CSFM Listing as well. They
are intended for indoor use in UL listed compatible fire
alarm systems and other applications requiring electrical
supervision of signaling circuit field wiring. The strobe
flashes a 360-degree beam of light approximately 65 times
per minute with a 55 cd ceiling light output (35 cd other)
per Figure 5.
When assembled in accordance with these instructions,
these 106DEX Series visual strobe signals are UL listed for
use in Class I, Division 1, Group C and D, Class I, Division 2,
Group A, B, C and D, Class II, Division 1, Group E, F and G,
Class II, Division 2, Group F and G, and Class III Division 1
and 2 hazardous locations with Operating Temperature
Codes per the following chart.
Figure 1. Detail of Pendant Mounting
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, do not apply power to the unit
until installation has been completed and unit is
tightly assembled and secured.
InstallationInstallation
InstallationInstallation
Installation
Install this unit in accordance with the applicable require-
ments in the latest edition of the National Electrical Code.
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.
box (not supplied). Secure 3/4" (19 mm) NPT
threaded conduit (not supplied) to the box. Install
the hood on the conduit. Proceed to step 2.
b. Ceiling Mount Models (Figures 2 and 4):
Unscrew the globe assembly from the ceiling
mount box. Mount the ceiling box using
appropriate hardware (not supplied) suitable for
the mounting surface. Proceed to step 2.
c. Bracket Mount Models (Figures 3 and 4):
Unscrew the globe assembly from the wall bracket.
Install the mounting bracket using appropriate
hardware (not supplied) for the mounting surface.
Pull the field wiring through the mounting
bracket. Proceed to step 2.
2. Extend the required power source wiring down
through the mounting hood. See Table 4 for required
supply wire temperature ratings.
3. A ground screw is provided in the wiring compartment
for attachment of field earth ground wire.
4. Connect the two red positive (+) and two black
negative (-) wire leads to the supervised circuit in
accordance with Figure 4.
5. Install the fixture on the mounting hood, bracket or
box as applicable.
Operating Temperature Codes
Class II, Div. 2,
Class I, Div. 2, Groups F, G;
Groups C and D Class III, Div. 2
Class II, Div. 1,
Ambient Class I, Div. 2 Class I, Div. 1 Groups E, F, G;
Temp. Groups A and B Groups C and D Class III, Div. 1
40°C 260°C (T2B) 85°C (T6) 120°C (T4A)
55°C 280°C (T2A) 100°C (T5) 135°C (T4)
65°C 280°C (T2A) 120°C (T4A) 160°C (T3C)
NOTE: This unit must be mounted vertically with the
globe assembly vertically facing down in
Hearing Impaired Applications.
1. Mount using the following applicable method.
a. Pendant Mount Models (Figures 1 and 4):
Unscrew the globe assembly from the mounting
hood and set aside. Install explosion-proof hanger
4.50"
(114.3mm)
13.15"
(334.01mm)
13.53"
(343.66mm)
7.80"
(198.12mm)
6. Apply power to the unit and ensure proper function.
P/N 3100101 ISSUE 6
Figure 2. Detail of Ceiling Mounting Figure 3. Detail of Bracket Mounting
Figure 4. Wiring Diagram
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device.
Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
From Power Source
or
Previous Signaling Device
End-of-Line Resistor,
when required with
supervised system
KEY:
Light symbol -
Wire nut symbol -
(+)
Red
(+)
Red
(+)
Red
(+)
Red
Black
(-)
Black
(-)
Black
(-)
Black
(-)
Series
106DEX
Series
106DEX
(+)
(-)
NOTE: For non-fire alarm use without field wire supervision installer can tie the two red leads together and
tie the two black leads together.
For strobe tube replacement, disconnect from the supply
circuit and allow five (5) minutes for stored energy to dis-
sipate before starting work or disassembly (Figure 6).
1. Loosen the (3) guard screws and remove the guard.
2. Loosen the globe and ring assembly set screw. Insert
a suitable tool into the notches in the globe and ring
assembly and loosen the assembly by prying in a
counterclockwise direction. Remove the ring and
globe assembly.
MaintenanceMaintenance
MaintenanceMaintenance
Maintenance
CAUTION
When replacing the strobe tube, do not handle the
tube. Hold the strobe tube only by its base to pre-
vent damage to the tube.
3. Refer to Table 2 for the correct replacement catalog
number and replace the necessary part.
4. To replace, simply screw the unit on until it seats firmly
onto its gasket. Tighten the unit another 1/8 to 1/4
turn. Tighten the setscrew.
5. Reinstall the guard, where applicable, and secure using
the three supplied screws.
6. After the unit is assembled, apply power and make
sure the unit functions properly.
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.
To reduce the risk of ignition of hazardous atmo-
spheres and shock, disconnect from the supply and
circuit and allow five (5) minutes for stored energy to
dissipate before disassembling the unit.
13.88"
(352.6 mm)
12.38"
(314.45mm)
13.75"
(349.25mm)
7.80"
(198.12mm)
4.93"
(125.2mm)
5.95"
(151.13mm)
13.0"
(330.2mm)
13.38"
(339.85mm)
7.80"
(198.12mm)
P/N 3100101 ISSUE 6
Table 3. 106DEX AdaptaBeacon Strobe Light Replacement Parts
Mounting Replacement
Cat. No. Method Strobe
106DEXPSTC-FJ Pendant Cat. No.
Figure 1 92-ST
106DEXCSTC-FJ Ceiling
Figure 2
106DEXBSTC-FJ Bracket
Figure 3
Table 1. 106DEX AdaptaBeacon Strobe Light Electrical Specifications
Operating Current* Initial Surge Inrush Current Repetitive Surge Current
Voltage** RMS Current (A) Mean Current (A) Current (A) Time (mS) Current (A) Time (mS)
20V DC 1.08 0.84 2.70 1.10 2.24 450
24V DC 0.95 0.69 2.97 1.13 2.21 400
28V DC 0.85 0.66 3.06 1.24 2.16 381
30V DC 0.83 0.64 3.14 1.27 2.14 360
*Use the operating current to establish the wire gauge and standby power requirements. Consult the control unit manufacturer to
determine surge and peak current effects and maximum number of strobes on the system.
**CAUTION: To prevent damage to the visual signal's internal circuit and to assure its continued proper functioning, DO
NOT operate the unit outside of the Special Application Voltage range of 20-30V DC.
Table 2. 106DEX AdaptaBeacon Strobe Light Specifications
Mounting Conduit Flash Rated Light
Cat. No. Method Size Rate Output
106DEXPSTC-FJ Pendant 3/4" 360° beam 55 cd/35 cd
Figure 1 NPT of light at per
106DEXCSTC-FJ Ceiling ~65 fpm Figure 5
Figure 2
106DEXBSTC-FJ Bracket
Figure 3
Table 4. Supply Wire Temperature Markings
Ambient Supply Wire
Temperature Temperature Marking
40°C 75°C
55°C 90°C
65°C 105°C
P/N 3100101 ISSUE 6
WALL
BRACKET
MOUNTING
A
NGLE
(DEGREES)
VERTICAL
PLANE
HORIZONTAL
PLANE
zero 100% 100%
5 90% 90%
10 90% 90%
15 90% 90%
20 90% 90%
25 90% 90%
30 90% 75%
35 65% 75%
40 46% 75%
45 34% 75%
50 27% 55%
55 22% 45%
60 18% 40%
65 16% 35%
70 15% 35%
75 13% 30%
80 12% 30%
85 12% 25%
90 12% 25%
Compound
45
24%
UL1971 REQUIRED
DISPERSION AS % OF CD
RATING
0
10
20
30
40
50
60
70
80
90
100
-90
-85
-80
-75
-70
-65
-60
-55
-50
-45
-40
-35
-30
-25
-20
-15
-10
-5
0 degrees
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
TYPICAL CD
UL REQUIRED CD
FOR 35 RATING
0
10
20
30
40
50
60
70
80
90
100
180
175
170
165
160
155
150
145
140
135
130
125
120
115
110
105
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
degrees 0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
155
160
165
170
TYPICAL CD
UL REQUIRED CD
F
O
R
55
RATIN
G
CEILING
MOUNTING
ANGLE
(DEGREES)
0 100%
5 90%
10 90%
15 90%
20 90%
25 90%
30 75%
35 75%
40 75%
45 75%
50 55%
55 45%
60 40%
65 35%
70 35%
75 30%
80 30%
85 25%
90 25%
Com
p
ound 45 24%
UL1971
REQUIRED
X & Y PLANE
DISPERSION
AS % OF CD
RATING
Figure 5. Light Output Patterns for 105DHISTC-FJ (Unit with clear lens only)
Effective Candela Light Output for Wall Bracket Mount
Vertical Plane
(Zero degree angle at side of globe)
Effective Candela Light Output for Ceiling Mount
X & Y Planes
(Zero degree angle at bottom of of globe)
UL 1971 Hearing Impaired: 35 cd wall
UL 1638 General Utility: 35 cd at 0
o
axis
UL 1971 Hearing Impaired: 55 cd ceiling
UL 1638 General Utility: 94 cd at 0
o
axis
P/N 3100101 ISSUE 6
Figure 6. Disassembly of the 106DEX Series AdaptaBeacons
Mounting
Hood
Strobe Tube
Globe & Ring
Assembly
Guard
(optional)
Contacting Edwards:
Phone: (203) 699-3000
Website: http://www.edwards-signals.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

EDWARDS 106DEXSTC-FJ Series Installation guide

Type
Installation guide

EDWARDS 106DEXSTC-FJ Series is a strobe light intended for indoor use in fire alarm systems and other applications requiring electrical supervision of signaling circuit field wiring. When assembled, the device is UL listed for use in various hazardous locations.

The strobe light has a clear lens, flashes at a rate of approximately 65 times per minute, and has a rated light output of 55 cd ceiling and 35 cd in other directions. It can operate within a voltage range of 20-30V DC and has special application voltage range of 20-30V DC. The strobe light requires supply wire temperature ratings of 75°C when the ambient temperature is 40°C, 90°C when the ambient temperature is 55°C, and 105°C when the ambient temperature is 65°C.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI