Century Air Handler HWCGxxT0A Operating instructions

Category
Heat pumps
Type
Operating instructions
1
`
INSTALLATION GUIDE
HWCGxxT0A Series - Multi-Position
Air Handler (Hydronic Heat)
1. Safety Instruction
!
WARNING
Potential safety hazards are alerted using the following symbols. The symbol is used in conjunction with terms
that indicate the intensity of the hazard.
This symbol indicates a potentially hazardous situation, which if not avoided,
could result in serious injury, property damage, product damage or death.
This symbol indicates a potentially hazardous situation, which if not avoided,
may result in moderate injury or property damage.
CAUTION
!
2. Ensure These Steps are Completed to Reduce
Chances of a Frozen Hydronic Coil
Ensure the air handler motor and control board are receiving
proper power input per the wiring diagram.
Ensure the hydronic coil has access to a constant water supply as
loss of water movement can lead to a frozen coil.
Prime the water circulator pump using the purge valve per the
“Start-Up” section of this installation guide.
Run the pump for ve minutes after priming to ensure no air is in
the system.
If any interruption to the water supply occurs, prime the water
circulator pump again.
Insulate the water piping in unconditioned spaces or within
structures that may be unoccupied during freezing conditions.
If the air handler does not have an internal pump and/or relies on
an external boiler system for hot water, the installer may need to
rewire the system to ensure that it maintains access to a constant
water supply.
Only factory authorized kits and acces-
sories should be used when installing or
modifying this unit unless it is so noted in
these instructions. Some localities may require a licensed
installer/service personnel.
CAUTION
!
Certied technicians or those individuals
meeting the requirements specied by
NATE may use this information. Property
and product damage or personal injury hazard may occur
without such background.
!
WARNING
All power sources should be disconnect-
ed prior to servicing. Failure to do so may
cause personal injury or property dam-
age.
!
WARNING
Product designed and manufactured to
permit installation in accordance with lo-
cal and national building codes. It is the
installers responsibility to ensure that product is installed
in strict compliance with national and local codes. Manufac-
turer takes no responsibility for damage (personal, product
or property) caused due to installations violating regula-
tions. In absence of local/state codes, refer to National Elec-
tric Code: NFPA 90A & 90B Uniform Mechanical Code.
!
WARNING
When this unit is installed in an enclosed
area, such as a garage or utility room with
any Carbon Monoxide producing devices
(i.e. automobile, space heater, water heater etc.) ensure that
the enclosed area is properly ventilated.
!
WARNING
The unit is designed for operation with
ply. HCI will not be responsible for
damages caused due to modification of the unit to
operate with alternative power sources.
!
WARNING
108/120V
, single phase, 60 Hz power sup-
Unit is not approved for outdoor installa-
tions.
!
WARNING
2
4. Installation Preparation
4A. Clearances
4B. Installation Options
4C. Condensate Drain Preparation
4D. Condensate Drain
4E. Ductwork
Read all the instructions in this guideline carefully while paying spe-
cial attention to the WARNING and CAUTION alerts. If any of the
instructions are unclear; clarify with certied technicians. Gather all
the tools needed for successful installation of the unit prior to begin-
ning the installation.
This unit is designed for zero clearance installation on three sides
and adequate clearance to provide access for service in the front.
A minimum of 2.5 – 3.5 feet clearance is recommended on the front
end (Fig 4A-1).
If the unit is to be installed in garages, warehouses or other areas
where they may be subjected to physical damage, adequate protec-
tive barriers must be installed. Unit MUST be installed 18” away from
source of ignition.
If the unit is located in high humidity areas like attics or uncondi-
tioned garage; the air handler casing might experience nuisance
sweating. In such installation scenarios, wrapping the casing with a
2” berglass insulation with vapor barrier SHOULD be used.
The drain lines must be installed with ¼” per foot pitch to provide free
drainage. A condensate trap MUST be installed on the primary drain
line to ensure proper drainage of the condensate. The trap must be
installed in the drain line below the bottom of the drain pan (Fig.
4D-1)
Since coil is upstream of the blower, all drains MUST be
trapped or sealed. Failure to do so will re-
sult in condensate overow from the drain
pan. HCI will NOT be responsible for any
damages resulting from failure to follow these instructions.
CAUTION
!
Ductwork for air conditioning systems should be installed in accor-
dance with standards of the National Fire Protection Association
Pamphlet No. 90A or 90B, and also be sized in accordance with
National Environmental System Contractors Association Manual K,
whichever is applicable.
On any job, non-ammable exible collars should be used for the
return air and discharge connections to prevent transmission of vi-
bration. Although these units have been specially designed for quiet
vibration-free operation, air ducts can act as soundboards, and if
poorly installed, amplify the slightest vibration to the annoyance level.
All main supply and return air drops should be properly size as deter-
mined by the designer of the duct system and should not necessarily
be the size of the duct ange openings of the unit.
The drain pan has primary (white) and secondary (red) drain connec-
tions. If a secondary drain line is required, it should be run separately
from the primary and should terminate in a highly visible location.
Condensate disposal through the secondary drain line indicates that
the primary drain line is plugged and needs cleaning. If a second-
ary drain line will not be provided, plug the secondary drain. Drain
plugs are NOT to be reused without plumbers tape or putty. Drain
line connection should be nger tightened, then turned no more than
one complete turn as needed to ensure a rm connection. DO NOT
overtighten connection or damage may occur.
Fig 4A-1. Minimum Clearance for Air Handler
Fig 4D-1. Condensate Drain Trap
3. Inspection
ü On receiving the product, visually inspect it for any major shipping
related damages. Shipping damages are the carrier’s responsibility.
Inspect the product labels to verify the model number and options
are in accordance with your order. Manufacturer will not accept dam-
age claims for incorrectly shipped product.
Drain lines from the auxiliary drain pan
should NOT be connected to the primary
drain line of the coil.
CAUTION
!
ü An auxiliary drain pan must be provided by the installer and placed
under the entire unit with a separate drain line that is properly sloped
and terminated in an area visible to the home owner. The auxiliary
pans provide extra protection to the area under the unit should the
primary and secondary drain plug up and overflow. As expressed
in our product warranty; HCI WILL NOT BE BILLED FOR ANY
STRUCTURAL DAMAGES CAUSE BY FAILURE TO FOLLOW
If the drain pan is constructed of nylon
or plastic; use Teon tape to connect the
drain lines to the threads in the drain pan.
DO NOT USE SOLVENT BASED PIPE DOPE. THIS WILL RE-
DUCE THE LIFE OF THE PAN.
CAUTION
!
THIS INSTALLATION REQUIREMENT. The drains from the auxil-
iary drain pan must be installed according to the local building codes.
3
5. Installation
Ensure that the unit is adequately sized.
The tonnage of the outdoor unit should
never exceed the tonnage of this unit.
CAUTION
!
Only lead free solder should be used to
connect water (hydronic) coil to the hot
water source.
CAUTION
!
The coil was manufactured with a dry ni-
trogen pre-charge. Release the pressure
through the Schrader valve test port prior
to installation. If holding pressure is not present, return coil
to distributor for exchange.
!
WARNING
Prior to connecting the water (hydronic)
coil, make sure that the hot water supply
is turned off. Water from the heater could
be extremely hot and might result in burns and other person-
al injury along with equipment damage. Ensure that proper
safety gear is being used prior to making connections.
!
WARNING
Some HCI coils may include a Schrader
valve on the suction manifold. Ensure that
the Schrader valve and valve core (where
present) are protected from heat during brazing and instal-
lation to prevent leakage. Use a core removal tool to tempo-
rarily remove the core when brazing. Replace the core once
brazing is completed.
CAUTION
!
5. Air Handler Orientation
This unit can be installed in vertical or right horizontal position with-
out modications. In case of a counterow application, the horizontal
drain pan MUST be removed. Fig. 6-1 shows the various orientations
this air handler can be installed in.
When the unit is used in a horizontal orienta-
tion, an auxiliary drain pan MUST be provided
by the installer and placed under the entire
unit with a separate drain line that is properly sloped and ter-
minated in an area visible to the home owner. The auxiliary pan
provides extra protection to the area under the unit should the
primary and secondary drains become plugged and overow. As
expressed in our product warranty, failure to follow this instal-
lation requirement will void the product warranty. The drain
from the auxiliary drain pan must be installed according to the
local building codes.
CAUTION
!
Fig 6-1
1. With Air Handler in vertical position remove all access panels.
2. Remove horizontal drain pan from
right hand side of coil.
6A. Horizontal Left-hand Installation
4. “P” traps must be installed on pri-
mary and secondary drains of the
horizontal drain pan.
3. Relocate the removed horizontal
drain pan to the left side of the coil.
ü Clean coil ns with degreasing agent or mild detergent and rinse
ns clean prior to installation.
ü The refrigerant line sizes should be selected according to the rec-
ommendations of the outdoor unit manufacturer.
ü Care must be taken to ensure all connection joints are burr-free
and clean. Failure to do so may increase chances of a leak. It is
recommended to use a pipe cutter to remove the spun closed end of
the suction line.
ü To reduce air leakage, rubber gommets may be present where the
lines pass through the coil case. To avoid damage, remove grom-
mets prior to brazing by sliding over the lines. Use a quenching cloth
or allow the lines to cool before reinstalling the grommets.
ü Use of wet rags/quenching cloth is highly recommended to prevent
weld-related damages to the casing and Schrader valve (if present).
When installing a central air return grille in or near the living space,
it is advisable to design the ductwork so that the grille is not in direct
line with the opening in the unit. The use of one or two elbows and
acoustical duct liner will also ensure quieter system operation.
It is recommended that wherever supply and return air sheet metal
duct pass through unconditioned areas, they be insulated to pre-
vent excessive heat loss during heating operation. When applied in
conjunction with summer air conditioning, sheet metal duct routed
through unconditioned areas should be insulated and have an out-
side vapor barrier to prevent formation of condensation.
4
6B. Counter/Downow Installation
Fig 6A-1 - Air ow direction in Horizontal Left application
5. Reinstall all access panels to the
unit.
A downow kit (DFK) is required for counter/downow air handler
installation
1. Remove the bottom access panel (1), top access panel (2), lter
cover (4), and air lter (5.) Remove the A-coil assembly (6) with side
drain pan (3) as shown in gure below.
2. Rotate the unit 180° as shown in the
gure. Discard existing bottom access
panel (1), top access panel (2) and side
drain pan (3.)
180° Rotation
3. For STYLE 1 downow kit ,rotate the lter rails 180° and re-in-
stalled the lter rails. After fastening lter rails, slide the air lter back
as shown below (A).
For STYLE 2,Fasten the Filter Rails D and E to the wrapper and slide
the air lter back as shown below (B).
A: Style 1
B: Style 2
4. Add Block Off Plate C
on the both side of coil as
shown.
5
7. Connecting Ducting
1. Secure supply air ducting to the top of the air handler. Canvas connectors are recommended for reducing potential noise transmission.
2. Secure the return air ducting to the air handler cabinet.
8. Metering Devices/Liquid Line Connection
HCI coils are available with two kinds of metering devices a) flowrator or b) TXV. The following instructions are separated into
sections by metering device.
5. Re-install and fasten the coil deck. After installing coil deck prop-
erly, slide the coil assembly back as shown below.
6. Install and fasten the lter cover rst,then the blower and control
access panel B and last will be coil access panel A to the unit as
shown below
The process of re-installing downow application conguration for
Style 1 and Style 2 respectively:
Re-installing Downow Conguration Style-1
Re-installing Downow Conguration Style-2
6
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
Use Piston sizes recommended by the
outdoor unit manufacturer whenever pos-
sible. The piston should be sized accord-
ing to the capacity of the outdoor unit.
CAUTION
!
Fig 8A-1. Flowrator assembly components
Failure to install the proper piston can
lead to poor system performance and
possible compressor damage.
!
WARNING
I. Installation
I-1. Disassemble owrator body
using two wrenches and un-
screwing with a counterclockwise
motion.
8A. Flowrator Coils
I-4. Braze the stub-out portion to the liquid line and let cool.
I-3. Slide the attachment nut onto
the liquid line stub out.
I-6. Tighten the nut to a torque of approximately 10-30 ft-lbs. Do NOT
overtighten the nut. Overtightening will impede the piston movement
during operation.
I-5. Taking care that the white
Teon seal is still in place inside
the owrater body, rmly seat the
stub and screw the attachment
nut to owrater body.
O-ring
Be aware of the Teon O-ring. Be sure to
replace the O-ring to attain a proper
seal. (The Teon O-ring is located between
the two halves of the owrator)
CAUTION
!
I-2. Replace the Teon O-ring
(located between the halves).
Discard Schrader if present.
O-ring
During some installations, a piston change may
be required. If so, the installer MUST change the
piston. Use piston sizes recommended by the
outdoor unit manufacturer. If a sizing chart is not
available, use the piston size chart provided be-
low to size the required piston. The size of the
piston is stamped on the piston body (Fig 8A-2).
II. Piston Replacement
Fig 8A-2
Use the chart below when matching coil with an outdoor unit with a
different nominal capacity than the coil.
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
II-4. Slide the 13/16” nut over
the lineset and separate the two
halves of the owrator.
II-1. Evacuate the system as per manufacturer guidelines and rec-
ommendations
II-2. Turn the 13/16” nut once to release any residual pressure in the
coil.
II-3. After ensuring that the coil
is free of any residual pressure,
disassemble the owrator body
completely using two wrenches.
Take great care not to distort the
feeder tubes. The wrench used
to clasp the nut should be turned
in counter-clockwise direction to
unscrew the nut.
7
Be aware of the Teon O-ring. Be sure to
replace the O-ring to attain a proper
seal. (The Teon O-ring is located between
the two halves of the owrator)
CAUTION
!
Pay close attention to the piston orienta-
tion. The pointed end of the piston MUST
go into the distributor body, towards the
coil. Failure to ensure this orientation will cause the piston
to be bypassed during operation which might damage the
outdoor unit.
CAUTION
!
II-6. Replace the piston with one
of the correct size. Do not force
the new piston into the body.
Make sure the piston moves
freely in body.
II-7. Assemble the two halves correctly and ensure that the white
Teon O-ring is present between the two halves (See I-5). Slide the
13/16” nut onto the distributor body.
II-8. Tighten the nut to a torque of approximately 10-30 ft-lbs. Do NOT
overtighten the nut. Overtightening will impede the piston movement
during operation.
II-9. If present, slide the rubber grommet back to position to prevent
air leakage.
7B. TXV Coils
Ensure that the TXV selected is compat-
ible with the refrigerant used in the out-
door system (R22 or R410A). TXV caps are
painted green for R22 or pink for R410A. In absence of col-
or, the caps will be marked with the compatible refrigerant.
CAUTION
!
The sensing bulb and TXV body MUST be
protected from overheating during braz-
ing. The sensing bulb and TXV body must
be covered using a quench cloth or wet cloth when brazing.
Pointing the brazing ame away from the valve and sensing
bulb provide partial protection only.
!
WARNING
Fig 8B-1. Components of a typical TXV assembly
The valves should be sized according to
the capacity of the outdoor unit. Failure to
install the right valve can lead to poor per-
formance and possible compressor damage.
CAUTION
!
Ensure that the TXV bulb is in direct con-
tact with the suction/vapor line. Gap be-
tween the bulb and tube should be avoid-
ed. Failure to do so will impair the proper functioning of the
TXV valve.
CAUTION
!
I. TXV Bulb Horizontal Mounting
The orientation and location of the TXV bulb has a major inuence
on the system performance.
II-5. Pull the piston out using a
small wire or pick. Verify the pis-
ton size (size is typically stamped
on the body of the piston - Fig
8A-2). If a different piston size
is required by the outdoor unit
manufacturer, replace the piston
using the small wire provided with
the piston kit.
It is recommended that the TXV bulb be installed parallel to the
ground (on a horizontal plane). The bulb position should be at
2 o’clock or 10 o’clock. Fig. 7B-2 shows the recommended position
for the TXV bulb installation in the horizontal plane.
The TXV sensing bulb SHOULD be mounted on the suction line ap-
proximately 6” from the TXV or coil housing using the metal clamp
provided. In order to obtain a good temperature reading and correct
superheat control, the TXV sensing bulb must conform to ALL of the
following criteria:
1. The sensing bulb MUST be in direct and continuous
contact with the suction line.
2. The sensing bulb should be mounted horizontally on
the suction line.
3. The sensing bulb MUST be mounted at the 2 o’clock or
10 o’clock position on the circumference of the suction line.
4. The sensing bulb MUST be insulated from outside air.
A properly mounted sensing bulb will prevent false readings caused
by liquid refrigerant that may have formed inside the suction/vapor
line. Insulation will protect the sensing bulb from false readings due
to contact with warm air.
Fig 7B-2. Recommended location for horizontal TXV bulb mount
Bulb position at
2 o’clock or
10 o’clock
8
If the TXV sensing bulb is mounted verti-
cally, the capillary MUST be directed up-
wards. The bulb must be mounted on the
wall opposite to that being directly hit by the refrigerant and
oil leaving the distributor tubes.
CAUTION
!
II. TXV Bulb Vertical Mounting
Fig 8B-3. Recommended location
for vertical TXV bulb mount
As recommended in Section
8B-I, the TXV sensing bulb
should be mounted in a hori-
zontal plane in relation to the
suction/vapor line. However,
some installation congura-
tions may require that the
sensing bulb be mounted ver-
tically. In this instance, place
the bulb opposite the piping
wall being hit by refrigerant
and oil leaving the distributor
tubes, and with capillary tubes
directed upwards as shown in
Fig. 8B-3.
III-3. Replace the Teon O-ring
seal in place (located between
the halves).
O-ring
III-2. Remove the existing ow-
rator piston using a small wire
or pick.
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
III. Field-Installed TXV Retrot
When installing an expansion valve, it is not necessary to slide the
coil out of the housing.
III-1. Disassemble the owrator
body using two wrenches. Un-
screw the body with a counter-
clockwise motion.
III-4. Inspect the TXV box to conrm that the valve is compatible
with the refrigerant in the system.
Male
(Inlet)
Female
(Outlet)
III-5. Remove the valve from
the box and note the loca-
tion of the inlet side (threaded
male port) and the outlet side
(female swivel nut port).
III-8. Braze the stub-out portion to the liquid line and let cool.
III-7. Slide attachment the nut onto the liquid line stub out
(See 8A, I-3)
Do not attempt to touch brazed joints
while hot. Severe burns may result.
!
WARNING
O-ring
III-6. After ensuring that the
Teon O-ring seal is still in place
inside the owrator body, screw
the female swivel nut onto the
owrator body.
O-ring
III-9. Remove the additional Tef-
lon O-ring seal from the box and
place on the shoulder just inside
the TXV inlet port. Screw the nut
attached to the stub-out portion of
the owrator body onto the inlet
port of the TXV.
A. Remove the valve stem from
the Schrader port mounted on the
suction line.
III-10. Tighten all connections taking care to use proper back up.
III-11. Remove the valve identification sticker from the valve and place it
adjacent to the HCI model number on unit name plate.
III-12a. Some HCI coils come with a Schrader valve on the suc-tion line.
If a Schrader port is present:
9
B. Screw are nut on TXV equal-
ization tube on to the Schrader
valve stem.
III-12b. In some cases, a suction line schrader port may not be
present. If a Schrader port is NOT present:
When handling or manipulating the equal-
izer tube, take great care not to kink or
make extreme bends in the tubing.
CAUTION
!
A. Install a eld-supplied braze-on schrader
valve like that shown on the suction line near the
intended sensing bulb mounting location. Fol-
low valve manufacturer instructions and recom-
mendations for installation.
B. Attach equalizer tube to valve as described in
section III-12a above.
III-13. Mount the sensing bulb as described in section 8B-I or 8B-II.
9. Connecting Refrigerant Lines
11. Electrical Installation
1. Release nitrogen hold-
ing charge by depressing the
Shrader Valve at the liquid line
connection on the air handler.
If no gas releases from the air
handler, contact distributor re-
garding potential leak.
2. Cut off Shrader Valve tting at
the liquid line connection. Use a
tubing cutter for this step. Clean
the burr from the cut tubing to
reduce the chance of future
leaks. Connect the liquid line to
the tubing at the indoor unit.
3. Use a tubing cutter to remove
the spun end from the suction
line connection at the air han-
dler. Clean the burr from the cut
tubing to reduce the chance of
future leaks.
4. To avoid heat damage to grommets where present, remove these
prior to brazing by sliding them over the refrigerant lines and out of
the way.
5. Check to determine if the
evaporator coil has a Shrader
tting on the suction manifold.
If yes, remove the valve core
to prevent heat damage during
brazing. Replace the valve core
once the piping has cooled.
6. If the air handler has a TXV metering device, remove the sensing
bulb from the suction line prior to brazing to prevent heat damage
from occurring. Replace the sensing bulb once the piping has cooled.
7. Flow nitrogen through the piping when brazing.
8. Braze both refrigerant line connections using proper brazing pro-
cedures.
9. When all line connections are brazed, perform a proper system
evacuation procedure per the outdoor unit manufacturer instructions.
10. Seal the penetration openings where the lineset piping enters the
air handler cabinet.
1. Following outdoor unit manufacturer instructions and recommen-
dations, charge the system with dry nitrogen to a maximum pressure
of 150 PSIG.
3. If any leaks are discovered, relieve system pressure and repair
leaks. Repeat steps 1-3.
4. With no leaks or weak connections present, evacuate the system
and charge as per the outdoor unit manufacturer instructions and
specications.
10. Leak Check
2. Check all brazed and screw-
on line connections by applying a
soap solution to the joint. A leak
will produce bubbles in the soap
solution.
These units are designed for a single phase 120 volts, 60 Hz power
supply. Wire selection and wiring must be in accordance with the Na-
tional Electric Code and/or local codes. Unit terminals are designed
to accommodate copper or aluminum wiring. If aluminum wiring is
used; please observe special precautions relative to sizing, wire con-
nections and corrosion protection.
Fig.11-1 shows the typical electrical connections required for A/C
only and heat pump applications.
Fig 11-1.
10
Line voltage wiring should be
routed through the access holes
at the top of the air handler.
Proper electrical conduit con-
nection ttings should be used.
Connect the power wiring to the
line side connections on the air
handler. The electrical ground
wire should be connected to the
grounding lug. Ensure both the
eld supplied ground wire and air
handler GREEN ground wire are
both secured to the grounding
lug of the air handler (Fig 11-2).
The aquastat (AQ) jumper must be in the
OFF position at all times, except for when
an aquastat is used. If the jumper is moved
to the ON position without installing an aquastat, the blower
will not be energized.
CAUTION
!
The unit ships with a micro-processor based board which controls
the electrical functioning of the unit. An inspection of the controls is
recommended prior to startup.
Fig.11-B2 provides a schematic of the control board present in the
unit. The unit ships from the factory with the aquastat jumper in the
OFF position (right two pins) and the heating selector in the HW
position (right two pins). If an aquastat is used in the application; the
jumper should be changed to the ON position (left two pins).
Note: Terminals T and N located on the top right side of the board are
not intended for eld use and should be left disconnected.
Fig 11A-2.
Fig 11-2.
Fig 11B-2.
11B. Jumper Placement
11C. Pump/Valve/Boiler Wiring
Operating CFM based upon each speed tap number is shown on
the electrical wiring diagram of the unit. Final air volume adjustments
should be made by referencing total external static pressure (Table
11A-1).
Table 11A-1.
11A. Single Stage Cooling
On units shipped from the factory with a pump installed (Fig 11C-3),
the pump will be energized on a call for heat.
Fig 11C-3.
During cooling mode operation, indoor blower wire “G” will energize
a time delay relay located on the control board inside the air han-
dler. After a short time delay period, the time delay relay will apply
120VAC to the motor via the “MTR“ terminal. (See Schematic Fig
22-1.) Fan time delay periods are 30 seconds ON delay and 120
seconds OFF delay.
The Y wire from the thermostat is not connected at the air handler.
This wire goes directly to the outdoor unit 24 volt wiring to turn on
the outdoor condensing unit when a call for cooling takes place. The
24 volt common for the outdoor unit circuitry is connected at the air
handler brown wire. (See Fig11-1.)
The hydronic heater low voltage wiring terminal “W” is wired directly
from the thermostat to the air handler. The indoor blower, on a call for
heat, will ON delay for a period of 5 seconds. When the call for heat
has been satised, the indoor blower will have an OFF delay time
period of 60 seconds.
On units that were shipped without factory installed pumps, two
black wires should be connected to the terminals marked “BOILER”
T T (see Fig 11B-2). In applications where a boiler provides the hot
water supply, these wires should be connected to the boiler control
wiring. Terminals “BOILER” T T are normally open dry contacts.
23/24
35/36
47/48/60
11
The freeze protection sensor is connected to the “FP” and “R“ ter-
minals. This sensor is normally open and will close when the sensor
detects a temperature of less than 40ºF. The pump will operate and
stay ON for a minimum of 30 seconds.
The board has a built-in timer which circulates hot water 6 times a
day for 60 seconds to prevent the hydronic coil from freezing.
12. Condensate Drain
1. Select desired condensate drain openings according to air han-
dler orientation. Both Primary and Secondary outlets can be used.
2. Pipe condensate system using proper PVC ttings.
3. Ensure a minimum 2” trap
is installed in the condensate
drain. Locate the trap near to
the connection opening on the
air handler. See illustration.
Air volume needs to be set to the level recommended by the outdoor
unit equipment manufacturer. Most systems will require around 400
CFM of indoor air for every 1 ton of system cooling capacity. The air
volume must be set prior to attempting system charge.
This air handler uses a PSC type motor. The speed of this motor
is set by placing the appropriate winding lead wire on the “MTR”
terminal of the control board. Unused motor winding leads are to
be placed on the “BLANK” terminals on the control board. The air
volume level produced by the air handlers at varying external static
pressure levels is shown in Table 13-1.
Use a Magnehelic Gauge with a 1” scale and two static pressure
tips to measure the static pressure during the air volume adjustment
procedure (Fig. 13-1). The high port static pressure tip should be
placed in the supply duct near the outlet of the air handler. The low
port static pressure tip should be placed in the return air duct near
the entrance to the air handler. The factory provided air lter should
be in place inside of the air handler.
13. Air Volume Adjustment
Table 13-1.
Fig. 13-1
1. Select a speed tap from the CFM table and connect appropriate
motor lead wire to the “MTR“ terminal on the control board.
2. Call for fan only operation at the thermostat.
3. Read the external static pressure level on the Magnehelic gauge.
4. Make speed tap selection change to get the air volume as close
as possible to the required level.
11D. Freeze Protection Sensor Wiring
In applications where a valve or pump is used to regulate the hot
water supply, the two black wires located on the “BOILER” T T ter-
minals should be removed and placed on the two terminals marked
“VALVE”. These wires should be connected to a 24V valve or pump
relay according to local requirements and instructions of the valve or
relay manufacturer.
On a call for heat, 24V will be sent to the eld-installed valve or pump
relay, the valve will open or pump relay will close contacts allowing
the pump to run. Water will circulate through the water (hydronic) coil
for 60 seconds prior to energizing the blower. After the thermostat is
satised, the blower will continue to stay energized for a minimum of
30 seconds. The additional blower run time helps maximize heating
efciency.
5. If the static pressure is above .5” wc, excessive turbu-
lence or duct friction needs to be reduced. (Obstructions in
the duct system can also cause excessive static pressure.)
6. When proper air volume is established, move on to the charging
procedure.
1. Bring airow up to the maximum CFM possible according to Table
12-1.
2. Evacuate refrigeration system to micron level required by outdoor
unit manufacturer.
3. Release system charge from outdoor unit and call for cooling.
4. Use outdoor unit equipment manufacturer specific charging charts
if available and make proper charge adjustment based upon outdoor
unit instructions.
5. If outdoor unit instructions and charts are not available, use HCI
provided charts. Make certain indoor air temperature is near comfort
level setpoint of 75°F prior to establishing superheat and subcooling
levels.
14. System Charging
An improperly charged system may cause
degradation in system performance and
damage the compressor. After installation
of the coil, refer to the outdoor unit manufacturer for charging
techniques and amount of charge. If outdoor unit manufacturers
charging instructions are unavailable, then refer to instructions
below to charge the system.
CAUTION
!
23/24
35/36
47/48/60
12
16. Start-Up
The hot water (hydronic) coil and all wa-
ter lines MUST be purged of air prior to
starting the pump. Failure to do so could
result in pump damage. HCI will not be
responsible for any property or personnel damage caused
by failure to fol-low this instruction.
!
WARNING
After all connections are made, start-up and checkout must be per-
formed before proper evaluation of the entire system can be made.
Make sure that heat anticipator is properly set as noted on thermo-
stat instructions. Load requirements can vary in each residence and
it may be necessary for the installer or homeowner to make slight ad-
justments to the heat anticipator setting for longer or shorter cycles.
It is recommended to change the setting no more than plus or minus
0.05 amps at a time. Greater changes can cause the unit to rapid
cycle or remain on excessively.
15. Adjustment Of Heat Anticipator
Hot water owing to the coil should be in
the range of 120º - 180º F. Water at these
temperatures can cause rst-degree
burns. Use of proper safety gear while installing or servicing
the equipment is strongly recommended as is installation
of a water-tempering valve (for water temperatures of above
140ºF) to supply lower temperature water to xtures in the
house. N170L series or equivalent should be used.
!
WARNING
Connect the hydronic coil to the water heater system as shown in Fig
16-1 and 16-2. Use exible piping and insulate all pipes. Plumbing
must be in compliance with state or local codes (Code CMR248 in
Massachusetts). The units for hydronic heat have different top and
heater box congurations. This conguration is not suitable for elec-
tric heat. DO NOT try to install hydronic heater in a unit not equipped
for it. Verify connections: hot water to “in” and cold water to “out”. 7/8”
OD stubs are provided for plumbing connections. Bleed the air ow
system through the bleeder port or optional valve.
Fig 16-1.
Fig 16-2.
Purging The System
1. Open air vent and allow water heater to ll with water. Close air
vent when water heater is full and all air has been purged.
2. Ignite water heater. Set thermostat on water heater to 140 de-
grees.
3. Close the valve on the hot water supply from the water heater (“A”)
and open the valve on the cold water return to the water heater (“B”).
Then open the air vent in the fan coil. Use bucket or hose to discard
water during purging process at air bleed valve. Purge air completely
from line.
4. Once air is purged, close return valve (“B”) and open supply valve
(“A”). Purge the coil and lines of air completely.
5. After air is purged from the system and lled with water, open the
return valve (“B”). Then close the air vent in the fan coil.
6. Apply power to the fan coil and set the room thermostat on heat.
Raise the temperature setting to activate the circulating pump
7. Check the pump to ensure proper operation. The water inlet of the
unit should be hot if the water temperature in the water heater has
reached the set point. If water is not being circulated through the coil
but the pump is running, then open the air bleed valve in the unit and
purge any air left in the system.
Add refrigerant until the superheat measured at the outdoor unit suc-
tion/vapor line matches the superheat from the chart below.
15A . Flowrator Coils
Add refrigerant until the subcooling measured at the outdoor unit
liquid line matches the subcooling recommendation of the outdoor
manufacturer. If chart is unavailable charge the unit to a subcooling
value of 8ºF +/- 1ºF.
Table 15B-1.
15B . Expansion Valve Coils
Outdoor
Temp
Superheat
°F D.B. Min Nom Max
65 30 35 40
70 26 30 34
75 21 25 29
80 17 20 23
85 12 15 18
90 8 10 12
95
4 5 7
100
Installer MUST open water lines and run
system to a.) ensure pump is primed and
waterow is constant and b.) ensure there
are no leaks in the coils, connections, and/or water piping.
Failure to do so could result in water leaks and property dam-
age. HCI will not be responsible for any damage caused
by failure to follow this instruction.
!
WARNING
13
Turn on power supply. Set thermostat fan switch to on. Set the cool-
ing indicator to maximum, heating to minimum. System switch may
be on heat or cool. Check slope gauge measurement against appro-
priate air ow chart. Make damper, register and motor speed adjust-
ments to obtain required airow.
Set thermostat fan switch to auto, system to heat and thermostat
heating indicator to maximum heat. Blower should start and all heat
be energized.
Check air ow using temperature rise method.
17. Checking Air Flow/Temperature Rise Method
Table 16-1. - CFM Delivered at Various External Statics
CFM
OUTPUT BTUH
TEMP RISE
=
()
..108
Note: BTUH output should be computed by 500 x Gallons Per Min-
utes x System Temperature Change = BTUH OUTPUT.
8. Adjust the water heater thermostat so that the water temperature
entering the hot water coils is 120 – 180ºF depending on the amount
of heat required by the structure. This is done with the unit energized
and operating long enough for all temperatures to stabilize.
After all connections are made, start-up and check-out must be per-
formed before proper evaluation of the entire system can be made.
Make sure that heat anticipator is properly set as noted on thermo-
stat instructions.
Load requirements can vary in each residence and it may be neces-
sary for the installer or homeowner to make slight adjustments to the
heat anticipator setting for longer or shorter cycles. It is recommend-
ed to change the setting no more than plus or minus 0.05 amps at
a time. Greater changes can cause the unit to rapid cycle or remain
on excessively. To properly check the unit’s operation, the installer
should have an electrical current measuring device (0-10 amp Am-
probe, Fluke), air pressure measuring device (0-1.0 in slope gauge),
and a temperature-measuring device (0-200ºF thermometer).
Install the Amprobe to measure blower current, the slope gauge to
measure static air pressure at the units and the temperature device
to measure unit supply and return air temperature. Before taking
measurements, be sure that all registers, grilles and dampers are
open or are set to their proper positions. Be sure that clean lters are
in place. Temperature measuring device must be installed to obtain
average temperature at both inlet and outlet. For outlet, measure
temperature of each main trunk at a location far enough away to
avoid heater radiation and read the average temperatures. Table
16-1 below shows the CFM that should be achieved at various exter-
nal static pressures.
Below are brief descriptions of the key components of the unit and in-
stallation. This manual only provides general idea of the components
and recommended practices. The installer should use best judge-
ment to ensure safe installation and operation of the unit.
1. Room Thermostat- This is the device that controls that operation
of your heating and/or cooling unit. It senses the indoor temperature
and signals the equipment to start or stop maintaining the tempera-
ture you have selected for your comfort. The room thermostat should
be in a central, draft free inside wall location for best operation. Do
not place any heat producing apparatus such as lights, radio, etc.,
near the thermostat as this will cause erratic operation of the comfort
system. The thermostat can accumulate dust or lint which can affect
its accuracy. It should be cleaned annually.
2. Air Filter(s) - All central air moving comfort systems must include
air lter(s). These lters will be located either in the equipment or in
the return air duct system upstream of the equipment. The lter(s)
removes dust and debris from the air thus helping to keep your air-
conditioned space clean. More important, the lter keeps dust and
debris from collecting on the heat transfer surfaces thus maintaining
optimum equipment efciency and performance. Inspect and clean
or replace lters every month. This routine maintenance procedure
will pay big dividends in reduced operating cost and reduced service
expense. Never operate comfort equipment without lter(s).
3. Fuses and/or Circuit Breakers- This comfort equipment should be
connected to the building electric service in accordance with local
and National Electric codes. This electrical connection will include
over-current protection in the form of circuit breakers. Have your
contractor identify the circuits and the location of over-current protec-
tion so that you will be in a position to make inspections or replace-
ments in the event the equipment fails to operate.
18. Operation and Maintenance
5. Periodic Checkup and Service- This product is designed to pro-
vide many years of dependable, trouble-free comfort when properly
maintained. Proper maintenance will consist of annual check-ups
and cleaning of the internal electrical and heat transfer components
by a qualied service technician. Failure to provide periodic checkup
and cleaning can result in excessive operating cost and/or equip-
ment malfunction.
6. Lubrication- Direct drive blower motors are equipped with perma-
nently lubricated bearings and do not require further lubrication.
7. Air lter replacement: An air lter can restrict the airow of air to
the fan coil if it is not cleaned or replaced periodically. When replac-
ing the air lter, always replace with the same type and size as origi-
nally furnished with the unit.
4. a) Do not store combustible materials
or use gasoline or other ammable liquids
or vapors in the vicinity of this appliance.
b) Do not operate the comfort equipment with panels re-
moved.
c) Have your contractor point out and identify the various
cut-off devices, switches, etc., that serve your comfort
equipment. There is a main switch that will cut off energy to
your heating system. Know where they are so that you may
cut off the ow of energy in the event of overheating.
!
WARNING
23/24
35/36
47/48/60
14
1. Equipment Sizing Select an air handler with a heating output
that exceeds the space heating loss of the structure and that has a
cooling coil sized to match the outdoor condensing unit. Note: The
heating output of the air handler or hot water coil will not be greater
than the output of the selected hot water heater. Therefore, if the
water heater is undersized the heating BTUH of the air handler will
be LESS than its rated output.
2. Water Heater Selection
The following sizing information should only be used as a basic
guide to adequate water heater sizing because of variations in each
family’s domestic hot water requirements. For additional assistance
in water heater sizing contact a professional engineer. Proper water
heater sizing should consider both the gallon capacity AND the BTU
input of the water heater.
a. To determine water heater GALLON CAPACITY: A minimum
40-gallon high recovery and/or high efciency gas or oil-red
water heater is recommended. The following volume-sizing
guide is satisfactory in most areas of the country (Table 19-1).
19.
HWCGxxT0A Hydronic Related General Information
b. To determine water heater BTU INPUT (assumes a water
heater recovery efciency of 76%): For mild climates: BTU
INPUT=structure’s heat loss x 1.51. For colder climates: BTU
INPUT=structure’s heat loss x 1.58.
3. Pump Replacement
a. Disconnect electrical power to the unit before servicing.
b. Remove access door to reveal pump. Close supply valve (“A”)
and return valve (“B”). Open the air bleed valve to de-pressur-
ize the system and drain water.
c. Remove the metal pump housing by loosening the four screws
on the pump. DO NOT UN-SOLDER PUMP.
d. Replace the new pump housing assembly and reconnect com-
ponents to the pump. Before assembling, make sure that the
runner on the o-ring is in place on the pump housing.
e. Purge the system of the air as described earlier and re-connect
the electrical power.
Table 19-1.
4. Little or no heat from water coil.
a. Purge the system.
b. The inlet connections may be reversed at the fan coil.
c. Water heater thermostat is not set at proper temp.
d. Water heater thermostat is not calibrated.
e. Dip tube in the water heater may not be installed correctly or
could be restricted.
f. Look for restrictions in heating system from water heater to fan
coil. Some water heaters are supplier with check valves, re-
move any extra check valves except for the one supplied with
the fan coil.
g. The air handler is undersized for space being heated.
h. Water heater is undersized.
Note: All units installed in Massachusetts are required to be in com-
pliance with CMR 248 Massachusetts State Plumbing Code and/or
Massachusetts Fuel Gas Code.
These codes require the use of an optional pump timer to circulate
the hydronic loop independent of the thermostat.
1. Noisy Pump
System may not be totally purged of air. Purge the system again as
described in the start up section above.
2. T&P valve on water heater weeps This normally occurs when a
backow preventer has been installed in the cold water supply line
to the water heater. An expansion tank may be necessary to correct
this problem. Please contact a qualied plumbing professional for
assistance.
3. Hot water is circulating through the water coil during cooling cycle
The check valve may be stuck open and allowing hot water to circu-
late through the coil.
20. Common Problems and Solutions
21. Final System Checkout
1. Make certain all cabinet openings are properly sealed and any
grommets moved during installation are moved into proper place.
2. With cooling system operating, check for condensate leakage.
3. Perform leak detection inspection of refrigerant circuit and con-
necting piping.
4. Secure all cabinet doors
15
22. Wiring
diagram for HWCGxxT0A models
HIGH VOLTAGE disconnect all power sources prior to servicing. Failure might lead to safety hazard
Fig 21-1.
16
23. Massachusetts Applicable Installation Diagram
08/2019
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17

Century Air Handler HWCGxxT0A Operating instructions

Category
Heat pumps
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI