Cooper Lighting SP Splitter Installation guide

Type
Installation guide
Risk of Fire and Electrical Shock- MWS must
be installed by qualified personnel. If not
qualified, consult an electrician.
Risk of Electric Shock- Disconnect power at
fuse or circuit breaker before installing or
servicing.
Ensure both latches are securely fastened-
Unlatched connections can separate causing
arcing and overheating of the connectors.
WARNING
IMPORTANT: Read, understand and follow all MWS
safety and installation instructions. Retain for future
reference.
NOTICE: Installation must comply with all applicable
national and local codes. Manufactured wiring systems
covered by Article 604 of the National Electrical Code.
NOTICE: Do not use any MWS component for other
than it’s intended purpose.
NOTICE: Do not tamper with the internal wiring of any
MWS component or physically modify in any way.
NOTICE: Starter fitting/starter fixture cable is
the starting point of the MWS system. All MWS
components attached to the system will be energized.
Cap all unused connector openings.
Installation Instructions – MWS
Instructions d’installation – MWS
Instrucciones de instalacn del sistema de cableado modular
IMPORTANT: Save installation instructions for future changes.
ADM140814
MWS
Failure to comply with these instructions may result in death, serious bodily injury and property damage.
DISCLAIMER OF LIABILITY: Eaton assumes no liability for damages or losses of any kind that may arise from the
improper, careless, or negligent installation, handling or use of this product.
INSTALLATION
1. Standard carton size 14”W x 14”L x 12”H
Half carton size 14”W x 14”L x 6”H.
2. Each carton label list component cat. no. quantity,
length voltage with photograph.
3. Standard pallet size: 32”W x 46”L x 42”H
Max. 18 cartons per pallet. Pallets are shrink
wrapped by Cooper.
120V/277V/347V
Blue/Hot 3
Red/Hot 2
Black/Hot 1
White/Neutral
Green
10/2G
12/2G
10/3G
12/3G
208V/240V/480V
Blue/Hot 3
Red/Hot 2
Black/Hot 1
Blank
Green
10/2G
12/2G
10/3G
12/3G
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
ote:N 12/4G, 10/4G Available (4 Hots) Yellow Conductor
in Pin #2.
MWS Standard Contact Configuration
2
MWS Components
Fixture Cable
Starter Fitting/Starter Cable
Starter Fitting
Starter Cable
3/4 (19mm)
4-3/8”(112mm)
12 ST
12/2G
XX
12 120V
27 277V
34 347V
20 208V
24 240V
48 480V
12/2G
12/3G
12/4G
10/2G
10/3G
10/4G
For Starter Cable
add Length
Starter Fixture Cable
Extender Cables
Switch Drops
Splitters
CT Fitting
Tee Cord Drops TS
Drop Cord “DS”
Tee Cable Drop
4-3/8”(112mm)
4-3/8”(112mm)
3/4”(19mm)
1-7/8”
(47mm)
5/8”
(16mm)
12 FC 12/2G XX
Length
07
09
11
13
15
17
3/4 (19mm)
4-3/8”(112mm)
5/8”(16mm)
1-7/8”
(47mm)
4-3/8”(112mm)
3/4”(19mm)
12 SF 12/2G 09
1 2
27
34
09
15
2-1/4”(57mm)
5-5/16”(136mm)
2-1/4”(57mm)
1-13/16”(45mm)
12 SD SL XX
All Switch Drops #12
Conductors
2-1/4”(57mm)
1-13/16”(45mm)
5-5/16”(136mm)
2-1/4”(57mm)
12 SP 12/4
12/4
10/4
5-5/16”(136mm)
2-1/4”(57mm)
2-1/4”(57mm)
1-13/16”(45mm)
4-3/8”(112mm)
5/8”
(16mm)
1-7/8”
(47mm)
2-1/4”
(57mm)
5-5/16”(136mm)
4-3/8’’(112mm)
4-3/8”(112mm)
09 - 9ft
15 - 15ft
21 - 21ft
2-1/4”
(57mm)
EATON ADM140814 Installation instructions - MWS
Installation Instructions – MWS
3
Starter Fittings “ST”
Fixture Cable “FC”
Poke Home Connectors standard on all fixture cables – Starter Fixture Cables –
Fixture Fitting Maximum 3 leads per poke Home Connector.
Red
Black
White
Blue
Green
Green/Yelllow
120V/277V/347V
From Panel
Install in 1/2" KO
12/2G-10/2G
GRN-WH-BK
12/3G-10/3G
GRN-WH-BK-RD
12/4G-10/4G
GRN-WH-BK-RD-BU
Red
Black
Blue
Green
Yelllow
208V/240V/480V
From Panel
12/2G-10/2G
GRN-BK-RD
12/3G-10/3G
GRN-BK-RD-BU
12/4G-10/4G
GRN-BK-RD-BU-YW
Starter Cable “ST”
Lengths 9’ – 15’ – 21’
wire per Starter Fitting detail
(Starter Fitting)
Wiring to Starter Fittings or
cables to be 90°
Starter (ST)
Fixture Cable (FC)
Fixture Cable (FC)
Dust Cover
Fixture
Wiring
Quick
Connect
Wiring from
Panel or
Switch Box
T SO Cord Drop “TS”
All Extender Cable between fixtures must be supported first 12” and every 4-1/2’ thereafter.
Starter (ST)
Wiring from Lighting
Panel or Lighting
Controller
Drop SO Cord “DS”
Extender Cable (EC)
Extender Cable (EC) Extender Cable (EC)
T SO Cord (TS)
Ensure both Latches
are Securely Fastened.
T SO Cord (TS)
T SO Cord (TS)
Extender Cable (EC)
Extender Cable (EC)
Drop SO Cord (DS)
Circuit T (CT)
EATON ADM140814 Installation instructions - MWS
Installation Instructions – MWS
4
Starter Fixture Cable “SF”
SL - Single Level, DL - Dual Level, SE - Single Level w/EM
Wire fixture before placing in ceiling Grid.
T Cable “TC
Fixture Fitting “FF”
Drop Cable “DC”
Alternative - Fixture Fitting “FF”
Switch Drop “SD”
With Fitting
Run 15' “SD”
from SW box to
first fixture.
With fixture cables
run switch drop from
switch box to above
ceiling
ot
e:
N Fixt
ure Cables, Fixture Fittings, Tee Cord Drops and Drop Cords may be
ordered factory attached by Cooper Lighting.
Starter Fixture Cable (SF)
Wire Leads Per
Starter Cable may
run down wall to
Switch Box
#12 Loads
Fixture Cable or
Extender to next Figure
Fixture Wiring
Starter (ST)
Extender Cable (EC)
Fixture Fitting (FF)
Fixture Wiring
Extender Cable (EC)
Switch Drop (SD)
Extender Cable (EC)
Fixture Cable (FC)
Fixture Cable (FC)
Single Level
Dual Level
Extender Cable (EC)
Switch Drop (SD)
Fixture Fitting (FF)
Extender Cable (EC)
Extender Cable (EC)
Run switch Drop to first Fixture Fitting
120V/ 277V/ 347V
120V/ 277V/ 347V – 2 Circuit, 2 Neutral
208V/ 240V/ 480V
Ground
Neutral/WH
Hot 1/BK
Hot 2/RD
Hot 3/BU or ORG
Hot 3/BU or ORG
Hot 2/RD
Hot 1/BK
Neutral/WH
Ground
16/2G
16/3G
16/4G
Ground
Neutral 1/NB
Hot 1/BK
Hot 2/RD
Neutral 2/ORG
Ground
Neutral 1/NB
Hot 1/BK
Hot 2/RD
Neutral 2/ORG
16/4G 2N
Ground
Hot 1/BK
Hot 2/RD
Hot 3/BU or ORG
Hot 4/YW or WH
16/2G 16/3G
16/4G
Ground
Hot 4/YW or WH
Hot 1/BK
Hot 2/RD
Hot 3/BU or ORG
EATON ADM140814 Installation instructions - MWS
Installation Instructions – MWS
Eaton
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.eaton.com/lighting
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2019 Eaton
All Rights Reserved
Printed in USA
Imprimé aux États-Unis
Impreso en los EE. UU.
Publication No. ADM140814
August 13, 2019
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton est une marque de commerce
déposée. Toutes les autres marques
de commerce sont la propriété de leur
propriétaire respectif.
Eaton es una marca comercial
registrada. Todas las marcas
comerciales son propiedad de sus
respectivos propietarios.
Product availability, specifications,
and compliances are subject to
change without notice
La disponibilité du produit, les
spécifications et les conformités
peuvent être modifiées sans préavis
La disponibilidad de productos, las
especificaciones y los cumplimientos
están sujetos a cambio sin previo aviso
Warranties and Limitation of Liability
Please refer to www.eaton.com/LightingWarrantyTerms for our terms and conditions.
Garanties et limitation de responsabilité
Veuillez consulter le site www.eaton.com/LightingWarrantyTerms pour obtenir les conditions générales.
Garantías y Limitación de Responsabilidad
Visite www.eaton.com/LightingWarrantyTerms para conocer nuestros términos y condiciones.
FCC Statement
Note: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
Declaración de la FCC
Nota: Este equipo ha sido probado y cumple con los límites para un
dispositivo digital de Clase A, de conformidad con la parte 15 de las
Normas de la FCC. Estos límites están diseñados para proporcionar
una protección razonable contra interferencias perjudiciales cuando el
equipo se opera en un entorno comercial. Este equipo genera, utiliza y
puede emitir energía de radiofrecuencia y, si no se instala y utiliza de
acuerdo con el manual de instrucciones, puede causar interferencias
perjudiciales en las comunicaciones de radio. El funcionamiento
de este equipo en un área residencial puede causar interferencias
perjudiciales, en cuyo caso el usuario deberá corregir las interferencias
por su cuenta.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Cooper Lighting SP Splitter Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI