GSA
Gas-Fired Steam Boilers ā Boiler Manual
2
Part Number 550-110-738/1012
This manual must only be used by a qualiļ¬ed
heating installer/service technician. Read
theseīinstructionsīcompletelyībeforeībeginningītheī
installation.īFailureītoīfollowītheseīinstructionsīcanī
cause severe personal injury, death or substantial
property damage.
Improperī ī installation,ī ī adjustment,ī ī alteration,ī ī serviceī orī
maintenance can cause property damage, personal injury,
exposureītoīhazardousīmaterials,īorīlossīofīlife.īīReferītoītheī
UserāsīInformationīManualīprovidedīwithīthisīboiler.īīInstallationī
andīserviceīmustībeīperformedībyīaīqualiī¬edīinstaller,īserviceī
agencyīīorīītheīīgasīīsupplierīīwhoīīmustīīreadīīandīīfollowīītheī
suppliedīinstructionsībeforeīinstalling,īservicingīorīremovingīthisī
boiler. This boiler contains materials that have been identiļ¬ed
as carcinogenic, or possibly carcinogenic, to humans.
Failure to adhere to the guidelines below
can result in severe personal injury, death or
substantial property damage.
The boiler contains ceramic ļ¬ber and ļ¬berglass
materials.īīīīUseīīcareīīwhenīīīhandlingīītheseīī
materialsī perī instructionsī onī pageī 25ī ofī thisī
manual. Failure to comply could result in severe
personal injury.
When servicing boiler ā
1.ī Toīavoidīelectricīshock,īdisconnectīelectricalīsupplyībeforeī
performingīmaintenance.
2.ī Toīavoidīsevereīburns,īallowīboilerītoīcoolībeforeīperformingī
maintenance.
Boiler operation ā
3.ī Doīnotīblockīīowīofīcombustionīorīventilationīairītoīboiler.
4.ī Shouldīoverheatingīoccur,īturnīoffīorīdisconnectīelectricalī
supplyītoīboilerīandīshutīoffītheīgasīsupplyīatīaīlocationī
externalītoītheīappliance,īifīpossible.
5.ī Doīnotīīuseīthisīboilerīifīanyīpartīhasībeenīunderīwater.ī
Immediatelyīcallīaīqualiī¬edīserviceītechnicianītoīinspectītheī
boilerīandītoīreplaceīanyīpartīofītheīcontrolīsystemīandīanyī
gas control that has been under water.
Boiler water ā
6. DO NOT use petroleum-based cleaning or sealing
compounds in boiler system. Water seal deterioration will
occur,īcausingīleakageībetweenīboilerīsections,īcirculatorī
īanges,īdiaphragmītanksīorīotherīsystemīcomponents.īThisī
can result in substantial property damage.
7.ī DOīīīNOTīīīuseīīāīhomemadeīīcuresīāīīorīīāīboilerīīpatentīī
medicinesā. Serious damage to boiler, personnel and/or
property may result.
8.ī Continualīfreshīmakeupīwaterīwillīreduceīboilerīlife.īMineralī
buildupīinīsectionsīreducesīheatītransfer,īoverheatsīcastī
iron,ī andī causesī sectionī failure.ī Additionī ofī oxygenīandī
otherīgasesīcanīcauseīinternalīcorrosion.īLeaksīinīboilerīorī
pipingīmustībeīrepairedīatīonceītoīpreventīmakeupīwater.
9.ī Doīnotīaddīcoldīwaterītoīhotīboiler.īThermalīshockīcanīcauseī
sectionsītoīcrack.
1 Prepare boiler location
Codes & Checklist
Installations must follow these codes:
ā¢ī Local,īstate,īprovincial,īandīnationalīcodes,īlaws,īregulationsī
and ordinances.
ā¢ī NationalīFuelīGasīCode,īANSIīZ223.1ālatestīedition.
ā¢ī StandardīforīControlsīandīSafetyīDevicesīforīAutomaticallyī
FiredīBoilers,īANSI/ASMEīCSDā1,īwhenīrequired.
ā¢ī NationalīElectricalīCode.
ā¢ī ForīCanadaīonly:īB149.1īorīB149.2īInstallationīCode,īCSAī
C22.1īCanadianīElectricalīCodeīPartī1īandīanyīlocalīcodes.
Certiļ¬cation
ī TheīGSAīboilerīgasīmanifoldīandīcontrolsīmetīsafeī
Lightingīandīotherīperformanceīcriteriaīwhenīboilerī
underwentī testsī speciī¬edī inī ANSIī Z21.13ālatestī
edition.
Before locating the boiler:
oī Checkīforīnearbyīconnectionīto:
ā¢ī Ventingīconnections
ā¢ī Gasīsupplyīpiping
ā¢ī Electricalīpower
oī Checkīareaīaroundīboiler.īRemoveīanyīcombustibleīmaterials,ī
gasolineīandīotherīīammableīliquids.
ī Failureītoīkeepīboilerīareaīclearīandīfreeīofīcom-
bustibleī materials,ī gasolineī andī otherī īammableī
liquidsī andī vaporsī canī resultī inī severeī personalī
injury, death or substantial property damage.
o Boiler must be installed so that gas control system components
areīprotectedīfromīdrippingīorīsprayingīwaterīorīrainīduringī
operation or service.
oī Ifīnewīboilerīwillīreplaceīexistingīboiler,īcheckīforīandīcorrectī
system problems, such as:
ā¢ī Systemīleaksīcausingīoxygenīcorrosionīorīsectionīcracksī
fromīhardīwaterīdeposits.
Read this ļ¬rst!