Lennox Q90-100 Series IV Installation Instructions Manual

Category
Water heaters & boilers
Type
Installation Instructions Manual

This manual is also suitable for

INSTALLATION MANUAL
An ISO 9001-2000 Certied Company
MEMBER: The Hydronics Institute
P/N# 14683301, Rev. A [08/08]
GAS-FIRED, DIRECT VENT,
CONDENSING, HOT WATER BOILER
DUNKIRK BOILERS
85 Middle Rd.
Dunkirk, NY 14048
www.dunkirk.com
2

󰮐






Improper installation, adjustment, alteration, service,
or maintenance can cause injury or property damage.
Refer to this manual. For assistance or additional in-
formation consult a qualied installer, service agency,
or the gas supplier.
Read all instructions carefully before starting the
installation.
Save this manual for reference.
WARNING
!
CAUTION
!
3




 
 
A. Codes ..............................................................................................................................................................................................10
B. Boiler Sizing .................................................................................................................................................................................. 11
C. Considerations For Boiler Location ...........................................................................................................................................11
D. Locating e Boiler ......................................................................................................................................................................12
E. Combustion Air And Vent Pipe Requirements ........................................................................................................................12
F. Condensate Drain Requirements ................................................................................................................................................ 13
G. Foundation Requirements ........................................................................................................................................................... 14
H. Removal Of Existing Boiler From Common Vent System .....................................................................................................14
 
 
A. Supply And Return Lines ............................................................................................................................................................ 15
B. Pressure Relief Valve ....................................................................................................................................................................19
C. Expansion Tank And Make-Up Water ....................................................................................................................................... 19
D. Condensate Drain Piping ............................................................................................................................................................ 22
E. Filling Condensate Trap With Water ......................................................................................................................................... 23
F. Chilled Water Piping .....................................................................................................................................................................23
 
A. Connections And Termination ................................................................................................................................................... 23
B. Installation .....................................................................................................................................................................................29
 
A. Check Gas Supply .........................................................................................................................................................................29
B. Connecting e Gas Piping .........................................................................................................................................................30
C. Checking e Gas Piping ............................................................................................................................................................30
 
A. Electric Power Supply .................................................................................................................................................................31
B. Install Your ermostat ................................................................................................................................................................32
C. Connect Circulator Pump Wiring .............................................................................................................................................. 32
 
A. Integrated Boiler Control (IBC) ................................................................................................................................................36
B. Gas Control Valve ........................................................................................................................................................................36
C. Hot Surface Igniter ......................................................................................................................................................................36
D. High Limit Aquastat Control .....................................................................................................................................................36
E. Dra Inducer Temperature Safety Switch ................................................................................................................................. 36
F. Casting Temperature Safety Switch .............................................................................................................................................36
4

G. Dierential Pressure Air Proving Switch/Blocked Vent Safety Shuto ................................................................................. 36
H. Dra Inducer ................................................................................................................................................................................37
I. Circulator Pump ............................................................................................................................................................................ 37
J. Drain Valve ..................................................................................................................................................................................... 37
K. A.S.M.E. Rated Pressure Relief Valve ........................................................................................................................................ 37
L. Blocked Vent Safety Shuto ........................................................................................................................................................ 37
M. External Condensate Pump (Optional) ................................................................................................................................... 37
 
Piping Recommendations ................................................................................................................................................................ 38
Water Chemistry ................................................................................................................................................................................ 38
Cleaning the Hydronic System ........................................................................................................................................................ 39
Freeze Protection ............................................................................................................................................................................... 39
 
A – Filling Boiler With Water And Purging Air For Systems With Diaphragm Type Expansion Tanks ..............................40
B – Purging Air For Systems With Conventional Closed Type Expansion Tanks: ................................................................... 40
C - Placing Boiler In Operation ....................................................................................................................................................... 41
 
A. Verify Proper Sequence Of Operation ...................................................................................................................................... 42
B. Inspect Venting And Air Intake System ..................................................................................................................................... 43
C. Inspect Condensate Drain ........................................................................................................................................................... 43
D. Inspect System Piping .................................................................................................................................................................. 43
E. Test Ignition System Safety Shuto Device ................................................................................................................................43
F. Test High Limit Control And Adjust .......................................................................................................................................... 44
G. Test Other Safety Controls .......................................................................................................................................................... 44
H. Set ermostat Heat Anticipator (If Used) And Verify ermostat Operation ..................................................................44
I. Measure e Natural Gas Input Rate .......................................................................................................................................... 44
J. Set ermostat To Desired Room Temperature .........................................................................................................................45
K. Review All Instructions ............................................................................................................................................................... 45
 
Beginning Of Each Heating Season ................................................................................................................................................48
Daily During Heating Season .......................................................................................................................................................... 48
Monthly During Heating Season .....................................................................................................................................................49
Periodically During Heating Season ...............................................................................................................................................49
End Of Each Heating Season - Annual Shutdown Procedure ..................................................................................................... 49
Annual Examination And Cleaning Of Boiler Components.......................................................................................................49
 
 
󰮏 
 
5
is appliance is a gas-red direct vent hot water boiler with
cast aluminum boiler sections. A revolutionary cast aluminum
heat exchanger means better heat transfer and thermal storage
than similarly sized cast iron boilers, which results in higher
eciency. e heating system water absorbs large amounts of
heat from the cast aluminum heat exchanger, cooling the ue
gases and causing condensation. Sealed combustion, premix
gas burner, and low ame temperature means drastically
reduced CO and NOx emissions, which contribute to a cleaner
and healthier environment.
is appliance, unlike normal residential atmospheric and
induced dra units, takes its combustion air directly from
the outdoors (sealed combustion) and does not compete with
building occupants for fresh air. Sealed combustion (also
known as “direct vent”) is the safest and best way to obtain
plenty of clean combustion air. e induced dra fan draws
in the outside combustion air, then takes the cooler ue gases
from the boiler unit and provides a positive removal of the ue
gases from the building through inexpensive and readily avail-
able PVC and CPVC pipes.


6
TABLE #1 – SEA LEVEL RATINGS – NATURAL AND PROPANE GASES
Model
Input
*(MBH)
++ Heating Capacity
*(MBH)
Net I=B=R Rating
*(MBH)
Shipping
Weight (lbs.)
Flue Dia.
90-50 50 45 39 220 2” CPVC & PVC
90-75 75 68 59 220 2” CPVC & PVC
90-100 100 90 78 220 2” CPVC & PVC
* 1 MBH = 1,000 Btuh Btuh = British ermal Units Per Hour
ese low pressure gas-red hot water boilers are design certi-
ed by CSA International for use with natural and propane
gases. e boilers are constructed and hydrostatically tested for
a maximum working pressure of 50 psig (pounds per square
inch gage) in accordance with A.S.M.E. (American Society of
Mechanical Engineers) Boiler and Pressure Vessel Code Sec-
tion IV Standards for heating boilers.
++ AFUE (Annual Fuel Utilization Eciency) and Heating
Capacity is based on the D.O.E. (Department of Energy) test
procedure.
e Boilers are certied in accordance with ANSI (American
National Standards Institute) Z21.13 standards as gas-red,
direct vent, condensing, hot water boilers.
e Heating Capacity indicates the amount of heat available
aer subtracting the losses up the stack. Most of this heat is
available to heat water. A small portion is heat from the jacket
and surfaces of the boiler, and it is assumed that this heat stays
in the structure. e Net I=B=R Rating represents the portion
of the remaining heat that can be applied to heat the radiation
or terminal units (i.e. nned tube baseboard, cast iron radia-
tors, radiant oor, etc.). e dierence between the Heating
Capacity and the Net I=B=R Rating, called the piping and
pickup allowance, establishes a reserve for heating the volume
of water in the system and osetting heat losses from the pip-
ing.
e Net I=B R Ratings shown are based on a piping and pickup
factor of 1.15 in accordance with the I=B=R Standard as pub-
lished by the Hydronics Institute. e Net I=B=R Rating of the
boiler selected should be greater than or equal to the calculated
peak heating load (heat loss) for the building or area(s) served
by the boiler and associated hot water heating systems. e
manufacturer should be consulted before selecting a boiler for
installations having unusual piping and pickup requirements.
e boilers are factory equipped for operation at altitudes
ranging from 0-2,000 feet above sea level. For use of these boil-
ers at altitudes above 2,000 feet above sea level, the gas input
ratings (MBH) automatically reduced.

7
e boilers (with the exception of the 90-75 LP product)
are factory equipped for operation at altitudes ranging from
0-10,000 feet above sea level. No changes to the factory settings
are required for installations from 0-5,000 feet above sea level.
For altitudes from 5,000-10,000 feet above sea level the gas
manifold pressure will need to be adjusted based upon caloric
(Btu) value of supply gas (contact local gas utility or distributor
for this value). For specic settings refer to Table #1 for natural
gas applications and Table #2 for LP gas applications. Instruc-
tions on how to adjust the gas manifold pressure settings are
shown in
Figures #17 & #18
.
Note that 90-75 LP applications for 5,000 - 10,000 feet above
sea level will require an orice change as well as a gas manifold
pressure adjustment based upon caloric (Btu) value of supply
gas. Refer to Table #2 for altitude orice kit part number. For
replacing the orice refer to specic instructions included with
the kit.
TABLE #1: SERIES 90 NATURAL GAS
SERIES 90-50
Stock Factory Btu Value of Natural Gas++
Settings 750 850 950 1000 1050
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 50
Manifold Pressure In W.C. 2.5 4 4 3.5 2.5 2.5
Orice 43331094 43331094
SERIES 90-75
Stock Factory Btu Value of Natural Gas++
Settings 750 850 950 1000 1050
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 75
Manifold Pressure In W.C. 2.5 3.5 3.5 2.5 2.5 2.5
Orice 43331092 43331092
SERIES 90-100
Stock Factory Btu Value of Natural Gas++
Settings 750 850 950 1000 1050
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 100
Manifold Pressure In W.C. 2.5 3.5 3.5 2.5 2.5 2.5
Orice 43331090 43331090
++Contact local gas utility or distributor for Btu value of gas.

8
NOTE: For model 90-75 LP units only at altitudes above 5,000 ., install 90-75 High Altitude Orice Kit
#550001810*. For all other altitudes use factory installed orice.
TABLE #2: SERIES 90 PROPANE GAS
SERIES 90-50
Stock Factory Btu Value of LP Gas++
Settings 2300 2350 2400 2450 2500
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 50
Manifold Pressure In W.C. 2.5 3 3 2.5 2.5 2.5
Orice 43331095 43331095
SERIES 90-75*
Stock Factory Btu Value of LP Gas++
Settings 2300 2350 2400 2450 2500
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 75
Manifold Pressure In W.C. 2.5 3.5 3.5 3.5 3 3
Orice 43331093
43331096*
* For model 90-75 LP units only at altitudes above 5,000 ft., install 90-75 High Altitude Orice Kit #550001810. For all other alti-
tudes use factory installed orice.
SERIES 90-100
Stock Factory Btu Value of LP Gas++
Settings 2300 2350 2400 2450 2500
Altitude in Ft. 0-5,000 5,000-10,000
Normal Input (MBH) 100
Manifold Pressure In W.C. 2.5 3 3 3 2.5 2.5
Orice 43331091 43331091
++Contact local gas utility or distributor for Btu value of gas.

9
is boiler has been equipped for residential installations.
If used for commercial applications, any additional code
requirements must be adhered to for installation. is may
require additional controls including but not limited to a
low water cut o, a manual reset high temperature limit, and
wiring and/or piping modications. e manufacturer is
not responsible for any eld installation changes made to a
boiler installation which are not described or acknowledged
in this manual.
Complete all of the following prior to installing the boiler.

is boiler product is a gas-red, direct vent, condensing boiler
and must be installed in accordance with all applicable federal,
state and local building codes including, but not limited to the
following:
United States - Installation shall conform with National Fuel
Gas Code (NFPA-54/ANSI Z223.1-latest edition)
Canada - Installation shall be in accordance with CSA B 149.1
and .2. installation codes.
Where required by the authority having jurisdiction, the instal-
lation must conform to the American Society of Mechanical
Engineers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers, No.CSD-1.


WARNING
!
Important - In the state of Massachusetts this product
must be installed by a licensed plumber or gas tter and the
installation must be in accordance with 248 CMR.
e installation must conform to the requirements of the author-
ity having jurisdiction or, in the absence of such requirements, to
the National Fuel Gas Code, ANSI Z223.1 - latest revision.
Installers - Follow local regulations with respect to installation
of CO (Carbon Monoxide) Detectors. Follow maintenance
recommendations in this manual.
Installation Requirements Specic To e State Of
Massachusetts
For Direct Vent, Mechanical Vent, And
Domestic Hot Water Appliances
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the commonwealth and where the
side wall exhaust vent termination is less than seven (7)
Read the entire installation manual before beginning the
1.
installation. Failure to follow these rules for safe instal-
lation and operation and these instructions could cause
a malfunction of the boiler and result in death, serious
bodily injury, and/or property damage.
Check all applicable state and local building codes and
2.
utility company requirements before installation. e
installation must conform with these requirements in their
entirety. In the absence of these codes, use NFPA Installa-
tion Codes and good industry practice.
Before servicing the boiler - allow the boiler to cool. Al-
3.
ways shut o any electricity and gas supply connected to
the boiler prior to servicing.
Inspect gas line for leaks.
4.
Be certain gas input rate is correct. Over ring may result
5.
in early failure of the boiler sections. is may cause
dangerous operation. Under ring may result in too much
air for the pre-mix burner causing poor or loss of combus-
tion.
Never vent the products of combustion from this boiler
6.
to an enclosed space. Always vent to the outdoors. Never
vent to another room or to inside a building.
Be sure there is adequate outdoor air supply to boiler for
7.
complete combustion.
Follow a regular service and maintenance schedule for ef-
8.
cient and safe operation.
Keep boiler area clean of debris and free of combustible
9.
and ammable materials.
Proper through the wall or through the roof combustion
10.
venting shall be in accordance with the materials and
methods described in this manual. Installation must com-
ply with local codes.
is boiler and related hot water heating systems are not
11.
do it yourself items. ey must be installed and serviced by
qualied professionals.
10

feet above nished grade in the area of the venting, includ-
ing but not limited to decks and porches, the following
requirements shall be satised:
Installation of carbon monoxide detectors: at the time of
1.
installation of the side wall horizontal vented gas fu-
eled equipment, the installing plumber or gastter shall
observe that a hard wired carbon monoxide detector with
an alarm and battery back-up is installed on the oor level
where the gas equipment is to be installed. In addition, the
installing plumber or gastter shall observe that a battery
operated or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling,
building or structure served by the side wall horizontal
vented gas fueled equipment. It shall be the responsibility
of the property owner to secure the services of qualied
licensed professionals for the installation of hard wired
carbon monoxide detectors.
In the event that the side wall horizontally vented gas A.
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
oor level.
In the event that the requirements of this subdivision can B.
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that
during said thirty (30) day period, a battery operated car-
bon monoxide detector with an alarm shall be installed.
Approved carbon monoxide detectors: each carbon mon-
2.
oxide detector as required in accordance with the above
provisions shall comply with nfpa 720 and be ansi/ul 2034
listed and ias certied.
Signage: a metal or plastic identication plate shall be
3.
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in
line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. e
sign shall read, in print size no less than one-half (1/2)
inch in size, “gas vent directly below. Keep clear of all
obstructions”.
Inspection: the state or local gas inspector of the side wall
4.
horizontally vented gas fueled equipment shall not ap-
prove the installation unless, upon inspection, the inspec-
tor observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 cmr
5.08(2)(A)1 through 4.
Product-approved vent/air-intake: a product-approved
5.
vent terminal must be used and, if applicable, a product-
approved air intake must be used. Installation shall be in
strict compliance with the manufacturer’s instructions.
Installation instructions: a copy of all installation instruc-
6.
tions for all product approved side wall horizontally vent-
ed gas fueled equipment, all venting instructions, all parts
lists for venting instructions, and/or all venting design
instructions shall remain with the appliance or equipment
at the completion of the installation.

Check to be sure you have selected the boiler with the proper
capacity before starting the installation. e I=B=R Rating of
the boiler selected should be greater than or equal to the cal-
culated peak heating load (heat loss) for the building or area(s)
served by the boiler and associated hot water heating systems.
See the table “BOILER RATINGS AND CAPACITIES.
Heat loss calculations should be based on approved industry
methods.

Before selecting a location for the boiler, the following should
be considered. Each boiler considered.
Supplied with the correct type of gas (natural gas or pro-•
pane).
Connected to a suitable combustion air intake piping sys-•
tem to supply the correct amounts of fresh (outdoor) air
for combustion, refer to Combustion Air And Vent Pipe
section (near center of this manual) for details.
Connected to a suitable venting system to remove the haz-•
ardous products of gas combustion, refer to Combustion
Air And Vent Pipe section (near center of this manual) for
details.
Connected to a suitable hot water heating system.•
Supplied with a suitable electrical supply for all boiler mo-•
tors and controls.
Connected to a properly located thermostat or operating •
control. (not included with boiler)
Placed on level surface (must NOT be installed on carpet-•
ing)
Condensate drain line must be pitched down to oor drain •
or external condensate pump with reservoir at ¼” per foot
(wood frame or blocks may be used to raise boiler).
11
TABLE #2 -
BOILER CLEARANCES
Unit
Combustible Clearance
Inch (mm)
Accessibility, Cleaning, and Servicing
Inch (mm)
Top 1 (25.4) 8 (203.2)
Left Side 1 (25.4) 24 (609.6)
Right Side 8 (203.2) -
Base 1 (25.4) -
Front 0 (0) 24 (609.6)
Back 1 (25.4) -
Intake/Vent Piping 0 (0) -
Near Boiler Hot Water Piping 1 (25.4) -
All distances measured from the cabinet of the boiler.


Select a location which is level, central to the piping sys-
7.
tems served and as close to the vent and air intake termi-
nals as possible.
Accessibility clearances, if more stringent (i.e. larger clear-
8.
ances) than required re protection clearances, must be
used for the boiler installation. Accessibility clearances
may be achieved with the use of removable walls or parti-
tions.
e boiler is approved for installation in closets and on
9.
combustible oors. is boiler shall NOT be installed on
carpeting.
e clearances shown in Table #2 indicate required clear-
10.
ances per IAS listing. A minimum 1” clearance must be
maintained between combustible construction and each
of the le, top and back surfaces of the boiler. A minimum
8” clearance is required on the right side, to allow room
for the inlet air pipe. An 18” clearance must be maintained
at a side where passage is required to access another side
for cleaning or servicing, inspection or replacement of
any parts that normally may require such attention. Allow
at least 24” at the front and le side and 8” at the top for
servicing. No clearances are required to venting or com-
bustion air intake piping.
Equipment shall be installed in a location which facilitates
11.
the operation of venting and combustion air intake piping
systems as described in this manual.
Advise owner of boiler to keep venting and combustion
12.
air intake passages free of obstructions. both the venting
and combustion air intake piping systems connected to
the outdoors must permit ow through the piping systems
without restrictions for the boiler to operate.
e boiler shall be installed such that the automatic gas ig-
13.
nition system components are protected from water (drip-
ping, spraying, rain, etc.) during operation and service
(circulator replacement, control replacement, etc.).

is boiler requires a dedicated direct vent system. In a direct
vent system, all air for combustion is taken directly from
outside atmosphere, and all ue products are discharged to
outside atmosphere.
Combustion air and vent pipe connections must terminate to-
gether in the same atmospheric pressure zone, either through
the roof or sidewall (roof termination preferred). See
Figures
#9 & #10
(in Combustion Air And Vent Pipe section near
center of this manual) for required clearances.
12
When vent pipe is exposed to temperatures below freezing,
such as when it passes through an unheated space or when
a chimney is used as a raceway, vent pipe must be insulated
with 1/2” Armaex or equivalent. In extreme cold climate
areas, use ¾” Armaex or equivalent.
Combustion air must be clean outdoor air. Combustion
air must not be taken from inside structure because that
air frequently is contaminated by halogens, which include
uorides, chlorides, phosphates, bromides and iodides.
ese elements are found in aerosols, detergents, bleaches,
cleaning solvents, salts, air fresheners, paints, adhesives and
other household products.
Locate combustion air inlet as far away as possible from
swimming pool and swimming pool pump house.
All combustion air and vent pipes must be airtight and
watertight. Combustion air and vent piping must also ter-
minate exactly as shown in Figure #9 or 10 (in Combustion
Air And Vent Pipe section near center of this manual).
Vent connections serving appliances vented by natural dra
shall not be connected into any portion of mechanical dra
systems operating under positive pressure.
Solvent cements are combustible. Keep away from heat,
sparks, and open ame. Use only in well ventilated areas.
Avoid breathing in vapor or allowing contact with skin or
eyes.
FAILURE TO FOLLOW THE AFOREMENTIONED
WARNINGS COULD RESULT IN FIRE, PROPERTY
DAMAGE, PERSONAL INJURY, OR DEATH.
Keep boiler area clean of debris and free of amable and
combustible materials, vapors and liquids.

Condensate drain line to be pitched down to oor drain at a
minimum of ¼” per foot. An external condensate pump (not
furnished) may be used if oor drain is not available. e
condensate pump must be designed for ue gas condensate
application.

CAUTION
!
WARNING
!
Notes:
1. Condensate trap is built into the boiler, an external trap is
not required and should not be used.
2. Wood frame or blocks may be used to raise the boiler to
maintain drain pitch or to be above external condensate
pump reservoir.
3. ere is a 115 Volt AC receptacle provided on the service
switch junction box which is located at the boiler right
side, to provide power for an external condensate pump (if
needed).
13
on clothes dryer and any appliance not connected to the
common venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhaust, so they will operate
at maximum speed. Close re dampers.
Place in operation the appliance being inspected. Follow
4.
the lighting instructions. Adjust thermostat so appliances
will operate continuously.
Test for spillage at the dra hood relief opening aer 5
5.
minutes of main burner operation. Use the ame of a
match or candle, or the smoke from a cigarette, cigar or
pipe.
Aer it has been determined that each appliance remain-
6.
ing connected to the common venting system properly
vents when tested as outlined above, return doors, win-
dows, exhaust fans and any other gas-burning appliance to
their previous condition of use.
Any improper operation of the common venting system
7.
should be corrected so the installation conforms with the
National Fuel Code, NFPA-54/ANSI -Z223.1-latest revi-
sion, or section 5 of CSA-B 149 for Canadian standards.
When resizing any portion of the common venting system,
the common venting system should be resized to approach
the minimum size as determined using the appropriate
tables in part 11 in the National Fuel Gas Code, NFPA-54/
ANSI- Z223.1-latest revision, or section 5 of CSA-B 149
for Canadian standards.

Boiler must be placed on level surface. Boiler is NOT to be
installed on carpeting.
Notes:
If boiler is not level condensate drain lines will not function
properly. Adjustable feet are located on the boiler to make
up for minor surface irregularities or tilt.
Wood frame or blocks may be used to raise boiler to main-
tain drain pitch or to be above external condensate pump
reservoir.


When an existing boiler is removed from a common venting
system, the common venting system is likely to be too large for
proper venting of the appliances remaining connected to it. At
the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected
to the common venting system placed in operation, while the
other appliances remaining connected to the common venting
system are not in operation.
Seal any unused openings in the common venting system.
1.
Visually inspect the venting system for proper size and
2.
horizontal pitch and determine there is no blockage, or re-
strictions, leakage, corrosion and other deciencies which
could cause an unsafe condition.
Insofar as is practical, close all building doors and win-
3.
dows and all doors between the space in which the ap-
pliances remaining connected to the common venting
system are located and other spaces of the building. Turn

14
Copper supply and return piping must NOT be installed di-
rectly into aluminum boiler section casings due to galvanic
corrosion between dissimilar metals. Iron or steel bushings
or pipe nipples should be used between copper system pip-
ing and boiler to make nal connection to boiler. Also, the
use of dielectric unions is acceptable. e packaged boiler is
furnished with iron piping in the front boiler section for the
supply and return connections.
When the installation of the boiler is for a new heating system,
rst install all of the radiation units (panels, radiators, base-
board, or tubing) and the supply and return mains. Aer all
heating system piping and components have been installed,
make nal connection of the system piping to the boiler. A hot
water boiler installed above radiation level must be equipped
with a low water cut o device. A periodic inspection is neces-
sary us is ushing of oat type devices, per low water cut o
manufacturers specic instructions.

e packaged boiler unit is set up to receive 1
¼” NPT supply
and return piping from top access. e boiler unit can also
be piped from the le side by turning the supply elbow, and
from the rear of the unit by removing plugs in the rear boiler
section.
NOTE: e circulator pump and isolation valves are fur-
nished within a carton inside the boiler cabinet and can be
installed at the installer preferred location.

CAUTION
!

e boiler should be placed to provide the most direct connec-
tions to the combustion air, vent and system piping as possible.
Place crated boiler as close to selected location as possible and
uncrate boiler. e uncrated boiler may be moved into position
with an appliance dolly or 2-wheel hand truck. e dolly or
hand truck should be inserted under the le hand side of the
boiler. It is possible to slide the boiler for a short distance on a
smooth oor or surface.
Note: refer to manual section “locating the boiler” for
required clearances for servicing and maintenance.
15


16


17
NOTE: When zoning with circulators, the furnished circulator pump should be used as one of the zone
pumps. Each stripped end of the electrical wires for the circulator pump inside the junction box should be
taped or wire nutted to prevent short circuits. Unplug the circulator pump wiring at the integrated boiler
control.


18

e boiler is furnished with a factory installed relief valve in
the top of the boiler. Provide ¾” piping from the supplied
relief valve to a local oor drain, but leave an air gap between
piping and drain. No shuto of any description shall be placed
between safety relief valve and the boiler, or on the discharge
pipes between such safety valve and the atmosphere. Instal-
lation of the safety relief valve shall conform to ANSI/ASME
Boiler and Pressure Vessel Code, Section IV. e manufacturer
is not responsible for any water damage.

Determine required system ll pressure, system design tem-
perature, and system water content. Boiler contains 2.6 gallons
(U.S.). Size expansion tank accordingly. Consult expansion
tank manufacturer for proper sizing information. Connect
properly sized expansion tank (not furnished) as shown in
Figure #6 for diaphragm type expansion tank and
Figure #7
for conventional closed type expansion tanks. For diaphragm
type expansion tanks, adjust the tank air pressure to match the
system ll pressure. Install air vent (furnished) as shown for
diaphragm type expansion tank system only. Install make-
up water connections as shown per local codes. If a pressure
reducing valve is used, adjust to match the system ll pressure.
In connecting the cold make-up water supply to the boiler,
make sure that clean water supply is available. When the water
supply is from a well or pump, sand strainer should be installed
at the pump.


19


20


  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Lennox Q90-100 Series IV Installation Instructions Manual

Category
Water heaters & boilers
Type
Installation Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI