Danfoss VLT AutomationDrive FC 360 User guide

Type
User guide
ENGINEERING TOMORROW
Programming Guide
PROFINET
VLT
®
AutomationDrive FC 360
vlt-drives.danfoss.com
Contents
1 Introduction
3
1.1 Purpose of the Manual
3
1.2 Additional Resources
3
1.3 Document and Software Version
3
1.4 Product Overview
3
1.5 Approvals and Certications
4
1.6 Symbols, Abbreviations, and Conventions
4
2 Safety
5
2.1 Safety Symbols
5
2.2 Qualied Personnel
5
2.3 Safety Precautions
5
3 Conguration
7
3.1 Congure the PROFINET Network
7
3.2 Congure the Controller
7
3.3 Congure the Frequency Converter
9
4 Control
10
4.1 PPO Types
10
4.2 Process Data
11
4.3 Control Prole
13
4.4 PROFIdrive Control Prole
14
4.5 FC Drive Control Prole
18
5 Acyclic Communication (DP-V1)
21
5.1 Features of an IO Controller System
21
5.2 Features of an IO Supervisor System
21
5.3 Addressing Scheme
22
5.4 Acyclic Read/Write Request Sequence
23
5.5 Data Structure in the Acyclic Telegrams
24
5.6 Header
24
5.7 Parameter Block
24
5.8 Data Block
24
6 Parameters
26
6.1 Parameter Group 0-** Operation/Display
26
6.2 Parameter Group 8-** Communication and Option
26
6.3 Parameter Group 9-** PROFIdrive
28
6.4 Parameter Group 12-** Ethernet
32
6.5 PROFINET-specic Parameters
34
Contents Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 1
6.6 Supported Object and Data Types
38
7 Application Examples
40
7.1 Example: Process Data with PPO Type 6
40
7.2 Example: Control Word Telegram Using Standard Telegram 1/PPO3
41
7.3 Example: Status Word Telegram Using Standard Telegram 1/PPO3
42
7.4 Example: PLC Programming
43
7.5 Example: PLC and Network Monitoring
44
8 Troubleshooting
48
8.1 No Response to Control Signals
48
8.2 Warnings and Alarms
50
8.2.1 Warning/Alarm Messages 52
Index
57
Contents PROFINET
2 Danfoss A/S © 04/2017 All rights reserved. MG06G102
1 Introduction
1.1 Purpose of the Manual
The PROFINET Programming Guide provides information
about conguring the system, controlling the frequency
converter, accessing parameters, programming, trouble-
shooting, and some typical application examples.
The programming guide is intended for use by qualied
personnel, who are familiar with the VLT
®
frequency
converters, PROFINET technology, and the PC or PLC that is
used as a master in the system.
Read the instructions before programming and follow the
procedures in this manual.
VLT
®
is a registered trademark.
1.2 Additional Resources
Resources available for the frequency converter and
optional equipment are:
The VL AutomationDrive FC 360 Quick Guide
provides the necessary information for getting
the frequency converter up and running.
The VL AutomationDrive FC 360 Design Guide
provides detailed information about capabilities
and functionality to design motor control
systems.
The VL AutomationDrive FC 360 Programming
Guide provides more details on working with
parameters and many application examples.
Supplementary publications and manuals are available
from Danfoss. See drives.danfoss.com/knowledge-center/
technical-documentation/ for listings.
1.3
Document and Software Version
This manual is regularly reviewed and updated. All
suggestions for improvement are welcome. Table 1.1 shows
the document version and the corresponding software
version. The rmware version of the PROFINET interface
can be read in parameter 15-61 Option SW Version.
Edition Remarks
Software
version
MG06G1xx The rst edition of this manual. 3.0x
Table 1.1 Document and Software Version
1.4
Product Overview
This programming guide relates to PROFINET interface for
VLT
®
AutomationDrive FC 360.
The PROFINET interface is designed to communicate with
any system complying with the PROFINET schema version
2.2 and 2.3 standards.
Since the introduction in 2001, PROFINET has been
updated to handle low and medium performance
requirements supported by PROFINET RT up to high-end
servo performance in PROFINET IRT. PROFINET is the
Ethernet-based eldbus oering and is the most scalable
and versatile technology today.
PROFINET provides the network tools to deploy standard
Ethernet technology for manufacturing applications while
enabling Internet and enterprise connectivity.
The PROFINET control cassette is intended for use with
VLT
®
AutomationDrive FC 360.
Terminology
In this manual, several terms for Ethernet are used.
PROFINET is the term used to describe the
PROFINET protocol.
Ethernet is a common term used to describe the
physical layer of the network, and does not relate
to the application protocol.
Introduction Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 3
1 1
1.5 Approvals and Certications
More approvals and certications are available. For more
information, contact a local Danfoss partner.
1.6 Symbols, Abbreviations, and
Conventions
Abbreviation Denition
CC Control card
CTW Control word
DCP Discovery and conguration protocol
DHCP Dynamic host conguration protocol
EMC Electromagnetic compatibility
GSDML General station description mark-up language
I/O Input/output
IP Internet protocol
IRT Isochronous real time
LCP Local control panel
LED Light emitting diode
LSB Least signicant bit
MAV Main actual value (actual speed)
MSB Most signicant bit
MRV Main reference value
PC Personal computer
PCD Process control data
PLC Programmable logic controller
PNU Parameter number
PPO Process parameter object
REF Reference (= MRV)
RT Real time
STW Status word
Table 1.2 Symbols and Abbreviations
Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information and description of
illustrations.
Italicized text indicates:
Cross reference.
Link.
Parameter name.
Parameter group.
Parameter option.
Introduction PROFINET
4 Danfoss A/S © 04/2017 All rights reserved. MG06G102
11
2 Safety
2.1 Safety Symbols
The following symbols are used in this guide:
WARNING
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
2.2 Qualied Personnel
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the trouble-
free and safe operation of the frequency converter. Only
qualied personnel are allowed to install or operate this
equipment.
Qualied personnel are dened as trained sta, who are
authorized to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Additionally, the qualied personnel must be
familiar with the instructions and safety measures
described in this document.
2.3
Safety Precautions
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when
connected to AC mains input, DC supply, or load sharing.
Failure to perform installation, start-up, and maintenance
by qualied personnel can result in death or serious
injury.
Only qualied personnel must perform instal-
lation, start-up, and maintenance.
WARNING
UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor can start at any
time. Unintended start during programming, service, or
repair work can result in death, serious injury, or
property damage. The motor can start with an external
switch, a eldbus command, an input reference signal
from the LCP or LOP, via remote operation using MCT 10
Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:
Press [O/Reset] on the LCP before
programming parameters.
Disconnect the frequency converter from the
mains.
Completely wire and assemble the frequency
converter, motor, and any driven equipment
before connecting the frequency converter to
AC mains, DC supply, or load sharing.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. High voltage can be present
even when the warning LED indicator lights are o.
Failure to wait the specied time after power has been
removed before performing service or repair work can
result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The
minimum waiting time is specied in the
chapter Safety in the operating guide supplied
with the frequency converter.
Before performing any service or repair work,
use an appropriate voltage measuring device to
make sure that the capacitors are fully
discharged.
Safety Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 5
2 2
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
by a certied electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
Ensure that only trained and qualied personnel
perform installation, start-up, and maintenance.
Ensure that electrical work conforms to national
and local electrical codes.
Follow the procedures in this document.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
Safety PROFINET
6 Danfoss A/S © 04/2017 All rights reserved. MG06G102
22
3 Conguration
3.1 Congure the PROFINET Network
Ensure that all PROFINET devices connected to the same
bus network have a unique station name (host name).
Set the PROFINET host name of the frequency converter
via parameter 12-08 Host Name.
3.2 Congure the Controller
3.2.1 GSDML File
To congure a PROFINET controller, the conguration tool
needs a GSDML le for each type of device on the
network. The GSDML le is a PROFINET xml le containing
the necessary communication set-up data for a device.
Download the latest version of GSDML le at
www.danfoss.com/BusinessAreas/DrivesSolutions/pronet. The
name of the GSDML le may dier from what is described
in this manual.
The following example shows how to congure the
controller.
Frequency converter GSDML le
VLT
®
AutomationDrive FC 360
GSDML-V2.3-Danfoss-
FC360-20151212.xml
Table 3.1 GSDML le
When conguring the PROFINET controller, the rst step is
to import the GSDML le in the conguration tool. The
following steps, outlined in Illustration 3.1, Illustration 3.2,
and Illustration 3.3, show how to add a new GSDML le to
the Simatic Manager software tool. For each frequency
converter, a GSDML le is typically imported once only,
following the initial installation of the software tool.
130BE934.10
Illustration 3.1 Import the GSDML File in the Conguration
Tool
130BE935.10
Illustration 3.2 Add a New GSDML File to the Simatic Manager
Software Tool
The GSDML le is now imported and is accessible via the
following path in the hardware catalog:
130BE936.10
Illustration 3.3 Path in the Hardware Catalog
Open a project, set up the hardware, and add a PROFINET
master system. Select Danfoss FC PN, then drag and drop
it onto the PROFINET IO system.
To enter the device name, open the properties for the
inserted frequency converter. See Illustration 3.4.
Conguration Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 7
3 3
130BE937.10
Illustration 3.4 Open the Properties for the Inserted
Frequency Converter to Enter the Device Name
NOTICE
The name must match the name in parameter 12-08 Host
Name. If the check mark Assign IP address via the IO
controller is set, the controller downloads the IP address
to the IO device with the corresponding device name.
The IP address is stored in the non-volatile memory of
the frequency converter.
130BE938.10
Illustration 3.5 Set Up the Hardware and Add a PROFINET
Master System
The next step is to set up the peripheral input and output
data. Data set-up in the peripheral area is transmitted
cyclically via telegrams/PPO types. In the example below, a
PPO type 6 is dragged and dropped to slot 1.
130BE939.10
Illustration 3.6 Set up the Peripheral Input and Output Data
The
conguration tool automatically assigns addresses in
the peripheral address area. In this example, the input and
output area have the following conguration:
PPO type 6
PCD word
number
0 1 2 3
Input
address
256–257 258–259 260–261 262–263
Set-up STW MAV
Parameter 9-16
PCD Read
Conguration
Parameter 9-16
PCD Read
Conguration
Table 3.2 PCD Read (Frequency Converter to PLC)
PCD word
number
0 1 2 3
Output
address
256–257 258–259 260–261 262–263
Set-up CTW MRV
Parameter 9-15
PCD Write
Conguration
Parameter 9-15
PCD Write
Conguration
Table 3.3 PCD Write (PLC to Frequency Converter)
Assign the PCDs via parameter 9-16 PCD Read Conguration
for inputs and parameter 9-15 PCD Write Conguration for
outputs.
Download the conguration le to the PLC. The PROFINET
system starts the data exchange when the PLC is set to
Run mode.
Conguration PROFINET
8 Danfoss A/S © 04/2017 All rights reserved. MG06G102
33
3.3 Congure the Frequency Converter
3.3.1 VLT Parameters
The following parameters are important when conguring
the frequency converter with a PROFINET interface:
Parameter 0-40 [Hand on] Key on LCP. If [Hand On]
is activated, control of the frequency converter
via the PROFINET interface is disabled.
After an initial power-up, the frequency converter
automatically detects whether a eldbus option is
installed in slot A and sets parameter 8-02 Control
Source to [Option A]. When an option is added,
changed, or removed from an already commis-
sioned frequency converter, it does not change
parameter 8-02 Control Source but enters Trip
mode, and the frequency converter shows an
error.
Parameter 8-10 Control Word Prole. Select
between the Danfoss frequency converter prole
and the PROFIdrive prole.
Parameter 8-50 Coasting Select to
parameter 8-58 Prodrive OFF3 Select. Select how
to gate PROFINET control commands with the
digital input command of the control card.
NOTICE
When parameter 8-01 Control Site is set to [2] Control
word only, the settings from parameter 8-50 Coasting
Select to parameter 8-58 Prodrive OFF3 Select are
overruled and only act on bus control.
Conguration Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 9
3 3
4 Control
4.1 PPO Types
The PROFINET prole for frequency converters species a
number of standard telegrams and provides space for
vendor-specic telegrams. The PROFIdrive prole for
frequency converters is suitable for data exchange
between a process controller (for example PLC) and a
frequency converter. All telegrams are dened for cyclic
data transfer of high-priority data.
Pure process data objects
PPO types 3, 4, 6, 7, and 8 are pure process data objects
for applications requiring no cyclic parameter access. The
PLC sends out process control data, and the frequency
converter then responds with a PPO of the same length,
containing process status data.
Illustration 4.1 shows the available PPO types:
PCD 1: The
rst 2 bytes of the process data area
(PCD 1) comprise a xed part present in all PPO
types.
PCD 2: The next 2 bytes are xed for PCD write
entries (see parameter 9-15 PCD Write Congu-
ration [1]), but congurable for PCD read entries
(see parameter 9-16 PCD Read Conguration [1]).
PCD 3–10: In the remaining bytes, the process
data can be parameterized with process signals,
see parameter 9-23 Parameters for Signals.
The setting in parameter 9-15 PCD Write Conguration
determines the signals for transmission (request) from the
master to the frequency converter.
The setting in parameter 9-16 PCD Read Conguration
determines the signals for transmission (response) from the
frequency converter to the master.
Select the PPO type in the master conguration. The
selection is automatically recorded in the frequency
converter. No manual setting of PPO types in the
frequency converter is required. Read the current PPO type
in parameter 9-22 Telegram Selection. The setting [1]
Standard telegram 1 is equivalent to PPO type 3.
In addition, all PPO types can be set up as word-consistent
or module-consistent. The process data area can be word-
consistent or module-consistent, whereas the parameter
channel must always be module-consistent.
Word-consistent data is transmitted as individual,
independent words between the PLC and the
frequency converter.
Module-consistent data is transmitted as sets of
interrelated words transferred simultaneously
between the PLC and the frequency converter.
Standard telegram
1
PPO 6
PPO 7
PPO 8
Danfoss telegram
(The old PPO type 3)
CTW/STW
REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
PCD 4
Read/
Write
PCD 5
Read/
Write
PPO 4
CTW/STW REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
CTW/STW
REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
PCD 4
Read/
Write
PCD 5
Read/
Write
PCD 6
Read/
Write
PCD 7
Read/
Write
PCD 8
Read/
Write
PCD 9
Read/
Write
CTW/STW REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
PCD 4
Read/
Write
PCD 5
Read/
Write
PCD 6
Read/
Write
PCD 7
Read/
Write
CTW/STW REF/MAV
CTW/STW REF/MAV
PPO 3
130BE941.10
Illustration 4.1 Available PPO Types
Control PROFINET
10 Danfoss A/S © 04/2017 All rights reserved. MG06G102
44
4.2 Process Data
Use the process data part of the PPO to control and
monitor the frequency converter via the PROFINET.
4.2.1 PCD
Control word (CTW) according to PROFIdrive prole:
Control words consist of 16 bits. The meaning of each bit
is explained in and . The following bit pattern sets all
necessary start commands:
0000 0100 0111 1111 = 047F hex.
1)
0000 0100 0111 1110 = 047E hex.
1)
0000 0100 0111 1111 = 047F hex.
1) For restart after power-up:
Set bits 1 and 2 of the CTW to 1.
Toggle bit 0 0–1.
These values are for bytes 9 and 10 in Table 4.1.
Quick stop: 0000 0100 0110 1111 = 046F hex.
Stop: 0000 0100 0011 1111 = 043F hex.
4.2.2 MRV
MRV is the speed reference with data format Standardized
value. 0 hex = 0% and 4000 hex = 100%.
In the example, 2000 hex is used corresponding to 50% of
the maximum frequency in parameter 3-03 Maximum
Reference. See the values for bytes 11 and 12 in Table 4.1.
The whole PPO therefore has the following values in hex:
Byte Value
PCD
CTW 9 04
CTW 10 7F
MRV 11 20
MVR 12 00
Table 4.1 Request Example: PPO Values in Hex
The process data within the PCD part acts immediately
upon the frequency converter and can be updated from
the master as quickly as possible.
Table 4.2 shows a positive response to the request example
from Table 4.1.
Byte Value
PCD
STW 9 0F
STW 10 07
MAV 11 20
MAR 12 00
Table 4.2 Response Example: Positive Response
The PCD part responds according to the state and parame-
terization of the frequency converter.
PCD part response:
STW: 0F07 hex means that the motor is running
and there are no warnings or faults.
MAV: 2000 hex indicates that the output
frequency is 50% of the maximum reference.
Table 4.3 shows a negative response to the request
example from Table 4.1.
Byte Value
PCD
STW 9 0F
STW 10 07
MAV 11 20
MAR 12 00
Table 4.3 Response Example: Negative Response
4.2.3 Process Control Data
Process control data (PCD) is the process data sent from
the PLC to the frequency converter.
Master/slave
1 2 3 ....... 10
CTW MRV PCD ....... PCD
PCD write
Table 4.4 Process Control Data
PCD 1 contains a 16-bit control word, and each bit controls
a specic function of the frequency converter. See
chapter 4.3 Control Prole.
PCD 2 contains a 16-bit speed setpoint in percentage
format. See chapter 4.2.5 Reference Handling.
The settings in parameter 9-15 PCD Write Conguration and
parameter 9-16 PCD Read Conguration dene the content
of PCD 3 to PCD 10.
Control Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 11
4 4
4.2.4 Process Status Data
Process status data is the process data sent from the
frequency converter and contains information about the
current state.
Slave/master
1 2 3 ...... 10
STW MAV PCD ...... PCD
PCD read
Table 4.5 Process Status Data
PCD 1 contains a 16-bit status word, and each bit contains
information regarding a possible state of the frequency
converter.
PCD 2 contains each default value of the frequency
converters current speed in percentage format (see
chapter 4.2.5 Reference Handling). PCD 2 can be congured
to contain other process signals.
The settings in parameter 9-16 PCD Read Conguration
dene the content of PCD 3–10.
4.2.5 Reference Handling
The reference handling is an advanced mechanism that
sums up references from dierent sources as shown in
Illustration 4.2.
For more information on reference handling, refer to the
frequency converters design guide.
Illustration 4.2 Reference
The reference or speed setpoint is sent via PROFINET and
is always transmitted to the frequency converter in
percentage format as integers shown in hexadecimal (0–
4000 hex).
The reference (MRV) and feedback (MAV) are always scaled
equally. The setting of parameter 3-00 Reference Range
determines the scaling of the reference and feedback
(MAV), see Illustration 4.3.
-100%
(C000 hex)
0%
(0 hex)
100%
(4000 hex)
P 3-00 set to
[1] -Max to +Max
P 3-03
Max reference
0 P 3-03
Max reference
0%
(0 hex)
100%
(4000 hex)
P 3-00 set to
[0] Min - Max
P 3-02
Min reference
P 3-03
Max reference
130BA198.10
Illustration 4.3 Reference (MRV) and Feedback (MAV), Scaled
NOTICE
When parameter 3-00 Reference Range is set to [0] Min -
Max, a negative reference is handled as 0%.
The actual output of the frequency converter is limited by
the speed limit parameters Motor Low/High Speed Limit
[RPM/Hz] in parameter 4-11 Motor Speed Low Limit [RPM] to
parameter 4-14 Motor Speed High Limit [Hz].
The nal speed limit is set in parameter 4-19 Max Output
Frequency.
Table 4.6 lists the reference (MRV) and the feedback (MAV)
formats.
MRV/MAV Integer in hex Integer in decimal
100% 4000 16384
75% 3000 12288
50% 2000 8192
25% 1000 4096
0% 0 0
-25% F000 -4096
-50% E000 -8192
-75% D000 -12288
-100% C000 -16384
Table 4.6 Reference/Feedback (MRV/MAV) Format
NOTICE
Negative numbers are formed as complement of 2.
NOTICE
The data type for MRV and MAV is an N2 16-bit
standardized value, expressing a range from -200% to
+200% (8001 to 7FFF).
Control PROFINET
12 Danfoss A/S © 04/2017 All rights reserved. MG06G102
44
Example
The following settings determine the speed as shown in
Table 4.7:
Parameter 1-00 Conguration Mode set to [0]
Speed open loop.
Parameter 3-00 Reference Range set to [0] Min-Max.
Parameter 3-02 Minimum Reference set to 0 Hz.
Parameter 3-03 Maximum Reference set to 50 Hz.
MRV/MAV Actual speed [Hz]
0% 0 hex 0
25% 1000 hex 12.5
50% 2000 hex 25
75% 3000 hex 37.5
100% 4000 hex 50
Table 4.7 Actual Speed for MRV/MAV
4.2.6 Process Control Operation
In process control operation, parameter 1-00 Conguration
Mode is set to [3] Process.
The reference range in parameter 3-00 Reference Range is
always [0] Min - Max.
MRV is the process setpoint.
MAV expresses the actual process feedback (range
±200%).
4.2.7 Inuence of the Digital Input
Terminals on FC Control Mode
In parameter 8-50 Coasting Select to
parameter 8-58 Prodrive OFF3 Select, set the inuence of
the digital input terminals on the control of the frequency
converter.
NOTICE
The setting of parameter 8-01 Control Site overrules the
settings in parameter 8-50 Coasting Select to
parameter 8-58 Prodrive OFF3 Select.
Program each of the digital input signals to logic AND,
logic OR, or to have no relation to the corresponding bit in
the control word. In this way, the following signal sources
initiate a specic control command, for example stop/
coast:
Fieldbus only.
Fieldbus AND digital input.
Either eldbus OR digital input terminal.
NOTICE
To control the frequency converter via PROFINET, set
parameter 8-50 Coasting Select to either [1] Bus or [2]
Logic AND. Then set parameter 8-01 Control Site to [0]
Digital and ctrl.word or [2] Controlword only.
For more detailed information and examples of logical
relationship options, see chapter 8 Troubleshooting.
4.3 Control Prole
Control the frequency converter according to:
The PROFIdrive prole, see chapter 4.4 PROFIdrive
Control Prole, or
The Danfoss FC control, see chapter 4.5 FC Drive
Control Prole.
Select the control prole in parameter 8-10 Control Word
Prole. The choice of prole aects the control word and
status word only.
Chapter 4.4 PROFIdrive Control Prole and chapter 4.5 FC
Drive Control Prole provide a detailed description of
control and status data.
Control Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 13
4 4
4.4 PROFIdrive Control Prole
This section describes the functionality of the control word
and status word in the PROFIdrive prole.
4.4.1 Control Word According to
PROFIdrive Prole (CTW)
The control word is used to send commands from a master
(for example a PC) to a slave.
Bit Bit = 0 Bit = 1
00 OFF 1 ON 1
01 OFF 2 ON 2
02 OFF 3 ON 3
03 Coasting No coasting
04 Quick stop Ramp
05 Hold frequency output Use ramp
06 Ramp stop Start
07 No function Reset
08 Jog 1 OFF Jog 1 ON
09 Jog 2 OFF Jog 2 ON
10 Data invalid Data valid
11 No function Slow down
12 No function Catch up
13 Parameter set-up Selection lsb
14 No function No function
15 Forward Reverse
Table 4.8 Control Word Bits
Explanation of the control bits
Bit 00, OFF 1/ON 1
Normal ramp stops using the ramp times of the actual
selected ramp.
Bit 00 = 0 stops and activates the output relay 1 or 2 if the
output frequency is 0 Hz, and if [31] Relay 123 is selected
in parameter 5-40 Function Relay.
When bit 0 = 1, the frequency converter is in state 1,
switching on inhibited.
Refer to Illustration 4.4.
Bit 01, OFF 2/ON 2
Coast stop.
Bit 01 = 0 coast stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if [31] Relay 123 is
selected in parameter 5-40 Function Relay.
When bit 01 = 1, the frequency converter is in state 1,
switching on inhibited. Refer to Illustration 4.4.
Bit 02, OFF 3/ON 3
Quick stop using the ramp time of parameter 3-81 Quick
Stop Ramp Time.
Bit 02 = 0 quick stops and activates the output relay 1 or 2
if the output frequency is 0 Hz, and if [31] Relay 123 is
selected in parameter 5-40 Function Relay.
When bit 02 = 1, the frequency converter is in state 1,
switching on inhibited.
Refer to Illustration 4.4.
Bit 03, coasting/no coasting
Bit 03 = 0 leads to a coast stop.
When bit 03 = 1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-50 Coasting Select
determines how bit 03 is linked with the corresponding
function of the digital inputs.
Bit 04, quick stop/ramp
Quick stop using the ramp time of parameter 3-81 Quick
Stop Ramp Time.
When bit 04 = 0, a quick stop occurs.
When bit 04 = 1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-51 Quick Stop Select
determines how bit 04 is linked with the corresponding
function of the digital inputs.
Bit 05, hold frequency output/use ramp
When bit 05 = 0, the present output frequency is
maintained, even if the reference value is modied.
When bit 05 = 1, the frequency converter can perform its
regulating function again according to the respective
reference value.
Bit 06, ramp stop/start
Normal ramp stop using the ramp times of the actual
ramp selected. In addition, if [31] Relay 123 is selected in
parameter 5-40 Function Relay, and if the output frequency
is 0 Hz, this bit activates output relay 01 or 04.
Bit 06 = 0 stops the frequency converter.
When bit 06 = 1, if the other start conditions are fullled,
the frequency converter can start.
NOTICE
The selection in parameter 8-53 Start Select determines
how bit 06 is linked with the corresponding function of
the digital inputs.
Bit 07, no function/reset
Reset after switching o. Acknowledges event in fault
buer.
When bit 07 = 0, no reset occurs.
When there is a slope change of bit 07 to 1, a reset occurs
after switching o.
Bit 08, jog 1 OFF/ON
Activation of the pre-programmed speed in
parameter 8-90 Bus Jog 1 Speed. Jog 1 is only possible if bit
04 = 0 and bits 00–03 = 1.
Bit 09, jog 2 OFF/ON
Activation of the pre-programmed speed in
parameter 8-91 Bus Jog 2 Speed. Jog 2 is only possible if bit
04 = 0 and bits 00–03 = 1.
Control PROFINET
14 Danfoss A/S © 04/2017 All rights reserved. MG06G102
44
Bit 10, data invalid/valid
Tells the frequency converter whether to use or ignore the
control word.
Bit 10 = 0 ignores the control word, making it possible to
turn o the control word when updating/reading
parameters.
Bit 10 = 1 uses the control word. This function is relevant
because the control word is always contained in the
telegram, regardless of which type of telegram is used.
Bit 11, no function/slow down
Used to reduce the speed reference value by the amount
given in parameter 3-12 Catch up/slow Down Value.
When bit 11 = 0, no modication of the reference value
occurs.
When bit 11 = 1, the reference value is reduced.
Bit 12, no function/catch up
Used to increase the speed reference value by the amount
given in parameter 3-12 Catch up/slow Down Value.
When bit 12 = 0, no modication of the reference value
occurs.
When bit 12 = 1, the reference value is increased.
If both slowing down and accelerating are activated (bits
11 and 12 = 1), slowing down has priority, and the speed
reference value is reduced.
Bits 13, set-up selection
Bits 13 is used to select between the 2 parameter set-ups
according to Table 4.9.
The function is only possible if [9] Multi Set-up has been
selected in parameter 0-10 Active Set-up. The selection in
parameter 8-55 Set-up Select determines how bit 13 is
linked with the corresponding function of the digital
inputs. Changing set-up while the frequency converter is
running is only possible if the set-ups have been linked in
parameter 0-12 This Set-up Linked to.
Set-up Bit 13
1 0
2 1
Table 4.9 Parameter Set-ups
Bit 14, not used
Bit 15, no function/reverse
Bit 15 = 0 causes no reversing.
Bit 15 = 1 causes reversing.
NOTICE
In the factory setting, reversing is set to [0] Digital in
parameter 8-54 Reversing Select.
NOTICE
Bit 15 causes reversing only when Ser. communication,
Logic or, or Logic and is selected.
4.4.2 Status Word According to PROFIdrive
Prole (STW)
The status word is used to notify a master (for example a
PC) about the status of a slave.
Bit Bit = 0 Bit = 1
00 Control not ready Control ready
01
Frequency converter
not ready
Frequency converter ready
02 Coasting Enable
03 No error Trip
04 OFF 2 ON 2
05 OFF 3 ON 3
06 Start possible Start not possible
07 No warning Warning
08
Speed reference
Speed = reference
09 Local operation Bus control
10 Out of frequency limit Frequency limit ok
11 No operation In operation
12
Frequency converter
OK
Stopped, auto-start
13 Voltage OK Voltage exceeded
14 Torque OK Torque exceeded
15 Thermal OK Limit exceeded
Table 4.10 Status Word Bits
Explanation of the status bits
Bit 00, control not ready/ready
When bit 00 = 0, bit 00, 01, or 02 of the control word is 0
(OFF 1, OFF 2, or OFF 3) - or the frequency converter is
switched
o (tripped).
When bit 00 = 1, the frequency converter control is ready,
but power is not necessarily supplied to the unit (in case
of a 24 V external supply of the control system).
Bit 01, VLT not ready/ready
Same signicance as bit 00, however, power is supplied to
the unit. The frequency converter is ready when it receives
the necessary start signals.
Bit 02, coasting/enable
When bit 02 = 0, bit 00, 01, or 02 of the control word is 0
(OFF 1, OFF 2, OFF 3, or coasting) - or the frequency
converter is switched o (trip).
When bit 02 = 1, bit 00, 01, or 02 of the control word is 1,
and the frequency converter has not tripped.
Bit 03, no error/trip
When bit 03 = 0, no error condition exists in the frequency
converter.
When bit 03 = 1, the frequency converter has tripped and
requires a reset signal before it can start.
Bit 04, ON 2/OFF 2
When bit 01 of the control word is 0, bit 04 = 0.
When bit 01 of the control word is 1, bit 04 = 1.
Control Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 15
4 4
Bit 05, ON 3/OFF 3
When bit 02 of the control word is 0, bit 05 = 0.
When bit 02 of the control word is 1, bit 05 = 1.
Bit 06, start possible/start not possible
If [1] PROFIdrive has been selected in
parameter 8-10 Control Word Prole, bit 06 is 1 after a
switch-o acknowledgement, after activation of OFF2 or
OFF3, and after switching on the mains voltage. To reset
Start not possible, set bit 00 of the control word to 0, and
bits 01, 02, and 10 to 1.
Bit 07, no warning/warning
Bit 07 = 0 means that there are no warnings.
Bit 07 = 1 means that a warning has occurred.
Bit 08, speed reference/speed = reference
When bit 08 = 0, the current speed of the motor deviates
from the set speed reference value. The deviation may
occur, for example, when the speed is being changed
during start/stop through ramp up/down.
When bit 08 = 1, the current speed of the motor
corresponds to the set speed reference value.
Bit 09, local operation/bus control
Bit 09 = 0 indicates that the frequency converter has been
stopped with [Stop] on the LCP, or that [0] Linked to hand
or [2] Local has been selected in parameter 3-13 Reference
Site.
When bit 09 = 1, the frequency converter can be
controlled through the serial interface.
Bit 10, out of frequency limit/frequency limit OK
When bit 10 = 0, the output frequency is outside the limits
set in parameter 4-52 Warning Speed Low and
parameter 4-53 Warning Speed High.
When bit 10 = 1, the output frequency is within the
indicated limits.
Bit 11, no operation/operation
When bit 11 = 0, the motor does not turn.
When bit 11 = 1, the frequency converter has a start
signal, or the output frequency is higher than 0 Hz.
Bit 12, drive OK/stopped, auto-start
When bit 12 = 0, there is no temporary overload of the
inverter.
When bit 12 = 1, the frequency converter has stopped due
to overload. However, the frequency converter has not
switched o (tripped) and starts again after the overload
has ended.
Bit 13, voltage OK/voltage exceeded
When bit 13 = 0, the voltage limits of the frequency
converter are not exceeded.
When bit 13 = 1, the direct voltage in the DC link of the
frequency converter is too low or too high.
Bit 14, torque OK/torque exceeded
When bit 14 = 0, the motor torque is below the limit
selected in parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode.
When bit 14 = 1, the limit selected in
parameter 4-16 Torque Limit Motor Mode or
parameter 4-17 Torque Limit Generator Mode is exceeded.
Bit 15, thermal OK/limit exceeded
When bit 15 = 0, the timers for the motor thermal
protection and thermal frequency converter protection
have not exceeded 100%.
When bit 15 = 1, one of the limits has exceeded 100%.
Control PROFINET
16 Danfoss A/S © 04/2017 All rights reserved. MG06G102
44
4.4.3 PROFIdrive State Transition Diagram
In the PROFIdrive control prole, the control bits:
0–3 perform the basic start-up/power-down functions.
4–15 perform application-oriented control.
Illustration 4.4 shows the basic state transition diagram where control bits 0–3 control the transitions, and the corresponding
status bit indicates the actual state. The black bullets indicate the priority of the control signals where fewer bullets indicate
lower priority, and more bullets indicate higher priority.
130BD806.10
Pulses
Disabled
Coast Stop
STW bit 1=false
Quick Stop
Quick Stop
STW bit 2=false
OFF
STW bit 0=false
ON
STW bit 0=true
Ramp Stop
Quick Stop
STW bit 2=false
S3: Switching ON inhibited
STW bit 6=true; 0, 1, 2=false
OFF
AND No Coast Stop
AND No Quick Stop
STW bit 0=false
AND bit 1=true
AND bit 2=true
Coast Stop
OR Quick Stop
STW bit 1=false
OR bit 2=false
Coast Stop
OR Quick Stop
STW bit 1=false
OR bit 2=false
Coast Stop
STW bit 1=false
Enable
Operation
STW bit 3=true
1st priority
2nd priority
3rd priority
Disable
Operation
STW bit 3=false
ON
STW bit 0=true
OFF
STW bit 0=true
Pulses
Disabled
S2: Ready For Switching ON
STW bit 0=true; 1, 2, 6=false
S5: Switching
OFF
STW bit 0, 1=true
bit 2, 6=false
S3: Switched ON
STW bit 0, 1=true; 2, 6=false
S4: Operation
STW bit 0, 1,2=true; 6=false
Illustration 4.4 PROFIdrive State Transition Diagram
Control Programming Guide
MG06G102 Danfoss A/S © 04/2017 All rights reserved. 17
4 4
4.5 FC Drive Control Prole
4.5.1 Control Word According to FC Prole
(CTW)
To select Danfoss FC protocol in the control word, set
parameter 8-10 Control Word Prole to [0] FC prole. Use the
control word to send commands from a master (PLC or PC)
to a slave (frequency converter).
Bit Bit value = 0 Bit value = 1
00 Reference value External selection lsb
01 Reference value External selection msb
02 DC brake Ramp
03 Coasting No coasting
04 Quick stop Ramp
05 Hold output frequency Use ramp
06 Ramp stop Start
07 No function Reset
08 No function Jog
09 Ramp 1 Ramp 2
10 Data invalid Data valid
11 No function Relay 01 active
12 No function Relay 02 active
13 Parameter set-up Selection lsb
14 No function No function
15 Forward Reverse
Table 4.11 Bit Values for FC Control Word
Explanation of the control bits
Bits 00/01, reference value
Use bits 00 and 01 to select between the 4 reference
values, which are pre-programmed in parameter 3-10 Preset
Reference according to Table 4.12.
NOTICE
In parameter 8-56 Preset Reference Select, a selection is
made to dene how bit 00/01 gates with the
corresponding function on the digital inputs.
Bit
01
Bit
00
Programmed
reference value
Parameter
0 0 1 [0] Parameter 3-10 Preset Reference
0 1 2 [1] Parameter 3-10 Preset Reference
1 0 3 [2] Parameter 3-10 Preset Reference
1 1 4 [3] Parameter 3-10 Preset Reference
Table 4.12 Programmed Reference Values for Bits
Bit 02, DC brake
Bit 02 = 0 leads to DC braking and stop. Braking current
and duration are set in parameter 2-01 DC Brake Current
and parameter 2-02 DC Braking Time.
Bit 02 = 1 leads to ramping.
Bit 03, coasting
Bit 03 = 0 causes the frequency converter immediately to
coast the motor to a standstill.
Bit 03 = 1 enables the frequency converter to start the
motor if the other starting conditions have been fullled.
NOTICE
In parameter 8-50 Coasting Select, a selection is made to
dene how bit 03 gates with the corresponding function
on a digital input.
Bit 04, quick stop
Bit 04 = 0 quick stops the frequency converter and ramps
the motor speed down to stop via parameter 3-81 Quick
Stop Ramp Time.
Bit 04 = 1 makes the frequency converter ramp the motor
speed down to stop via parameter 3-42 Ramp 1 Ramp
Down Time or parameter 3-52 Ramp 2 Ramp Down Time.
Bit 05, hold output frequency
Bit 05 = 0 freezes the present output frequency (in Hz).
The frozen output frequency can only be changed with the
digital inputs (parameter 5-10 Terminal 18 Digital Input to
parameter 5-15 Terminal 33 Digital Input) programmed to
[21] Speed up and [22] Speed down.
Bit 05 = 1 uses ramp.
Bit 06, ramp stop/start
Bit 06 = 0 stops the frequency converter and the motor
speed ramps down to stop via the selected ramp-down
parameter.
Bit 06 = 1 allows the frequency converter to start the
motor if the other starting conditions have been fullled.
NOTICE
In parameter 8-53 Start Select, dene how bit 06 ramp
stop/start gates with the corresponding function on a
digital input.
Bit 07, reset
Bit 07 = 0 does not cause a reset.
Bit 07 = 1 resets a trip. Reset is activated on the signal’s
leading edge, that is, when changing from logic 0 to logic
1.
Bit 08, jog
Bit 08 = 0, no function.
Bit 08 = 1, parameter 3-19 Jog Speed [RPM] determines the
output frequency.
Bit 09, selection of ramp 1/2
Bit 09 = 0, ramp 1 is active (parameter 3-40 Ramp 1 Type to
parameter 3-47 Ramp 1 S-ramp Ratio at Decel. Start).
Bit 09 = 1, ramp 2 is active (parameter 3-50 Ramp 2 Type to
parameter 3-57 Ramp 2 S-ramp Ratio at Decel. Start).
Control PROFINET
18 Danfoss A/S © 04/2017 All rights reserved. MG06G102
44
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Danfoss VLT AutomationDrive FC 360 User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI