  • Hello! I've reviewed the Safety and Installation Instructions for SunPower Type E, Type G, and Type H AC Modules. This document outlines crucial safety measures, proper mounting methods, and electrical connection guidelines. I'm ready to assist you with any questions you may have about these modules, including their fire rating, grounding techniques, and maximum allowed modules per circuit.
  • What should be done before installing the modules?
    What is required for grounding the modules?
    How many modules can be connected to a single branch circuit?
SafetyandInstallationInstructionsfor
SunPowerTypeE,TypeGandTypeHACModules
UnitedStatesandCanada
Contentsaresubjecttochangewithoutnotice.
Forthelatestversionvisitwww.sunpower.maxeon.com/int/PVInstallGuideULAC
SunPowerCorporation
www.sunpower.com
531725RevJ
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
SafetyandInstallationInstructionsforACModules
IMPORTANTSAFETYINSTRUCTIONS
SAVETHESEINSTRUCTIONS
1.0 Introduction
ThisdocumentprovidessafetyandinstallationinstructionsfortheUL
ListedSunPowerACphotovoltaic(PV)modulesdescribedherein,allof
whichbeartheULlogoontheproductlabel:
1.1DisclaimerofLiability
Theinstallationtechniques,handlinganduseofthisproductarebeyondcompany
control.Therefore,SunPowerdoesnotassumeresponsibilityforloss,damage,or
expenseresultingfromimproperinstallation,handling,oruse.
1.2NationallyRecognizedTestingLaboratory(NRTL)Listing
Information
ThisproductmeetsorexceedstherequirementssetforthbyUL1703orUL61730,
UL1741andUL1741SAforACPVModules.TheUL1703Standardcoversflat
platePVmodulesintendedforinstallationonbuildings;orthoseintendedtobe
freestanding.TheUL1741SAStandardcoversinverters,converters,controllers,
andinterconnectionsystemequipmentforusewithdistributedenergyresources,
includingACmodules.TheNRTLlistingdoesnotincludeintegrationintoabuilding
surfacebecauseadditionalrequirementsmayapply.Thisproductisnotintended
forusewhereartificiallyconcentratedsunlightisappliedtothemodule.TheType
EandtheTypeGACmodulemodelscomplywithHECORule14H,CACPUCRule
21,15472003and1547a2014.
1.3LimitedWarranty
ModulelimitedwarrantiesaredescribedinfullintheSunPowerwarranty
certificatesobtainableatwww.sunpower.com.Insummary,theLimited
Warrantiesdonotapplytoanyofthefollowing:
PVmoduleswhichinSunPower'sabsolutejudgmenthavebeensubjectedto:
misuse,abuse,neglect,oraccident;alteration,improperinstallation,application,
orremoval.Including,butnotlimitedtoinstallation,application,orremovalby
anypartyotherthanaSunPowerauthorizedDealer;nonobservanceof
SunPower'sinstallation,user’sand/ormaintenanceinstructions;repairor
modificationsbysomeoneotherthananapprovedservicetechnicianof
SunPower;powerfailuresurges,lightning,flood,fire,accidentalbreakageorother
eventsoutsideSunPower'scontrol.
2.0 SafetyPrecautions
Beforeinstallingthisdevice,readallsafetyinstructionsinthisdocument.
DisconnecttheutilityACsourcefromallmodulesinthearraybeforemaking
orbreakingelectricalconnections.
UseonlytheAClockingconnectorsinordertodefendagainstuntrained
personneldisconnectingthemodulesaftertheyhavebeeninstalled.
AllinstallationsmustbeperformedincompliancewiththeNationalElectrical
Code(NEC)andanyapplicablelocalcodes.
Installationshouldbeperformedonlybyqualifiedpersonnel.
Removeallmetallicjewelrypriortoinstallingthisproducttoreducethe
chanceofaccidentalexposuretolivecircuits.
Useonlyinsulatedtoolstoreduceyourriskofelectricshock.
Donotstandon,drop,scratch,orallowobjectstofallonmodules.
Brokenglass,Jboxes,brokenconnectors,and/ordamagedbacksheetsare
electricalhazardsaswellaslacerationhazards.Ifamoduleiscrackedafter
installation,aqualifiedpersonshouldremovethemodulefromthearrayand
contactthesupplierfordisposalinstructions.
Donotinstallorhandlemoduleswhentheyarewetorduringperiodsofhigh
wind.
Unconnectedconnectorsmustalwaysbeprotectedfrompollution(e.g.dust,
humidity,foreignparticles,etc),priortoinstallation.Donotleave
unconnected(unprotected)connectorsexposedtotheenvironment.Aclean
installationenvironmentisessentialinordertoavoidperformance
degradation.
Donotblockdrainholesorallowwatertopoolinornearmoduleframes
Contactyourmodulesupplierifmaintenanceisnecessary.
Savetheseinstructions!
3.0 ElectricalCharacteristics
AllelectricalcharacteristicsandgridinteractiondataareshowninSection7.Itis
theinstaller’sresponsibilitytosetthegridprofile—thiscanonlybedonewith
internetaccessandtheSunPowermonitoringsystem.
IfaninstallationinvolvesaSunPowerACmodulewhichdoesnotappearonthis
listpleaseconsulttheproductlabelonthebackofthemoduleorvisit
www.sunpower.comfortheproductdatasheet.
3.1FireRating
TheACmodulemaintainsthesameType2fireratingassociatedwithDC
modules.
4.0 ElectricalConnections
ModulesmustonlybeconnectedusingthesuppliedACcablingandintegrated
connectors.Donotalteranyconnectors.PlugandSocketconnectorsmated
togetherinaPVsystemmustbeofthesametype(model,rating)fromthesame
manufactureri.e.aplugconnectorfromonemanufacturerandasocketconnector
fromanothermanufacturer,orviceversa,shallnotbeusedtomakeaconnection.
Ensurethatthecablingisnotundermechanicalstress(complywithbendingradius
of≥60mm)andmustnotbebentonthedirectexitoftheconnectororjunction
box.TheACmodulecablesystemfeatureslockingconnectorswhich,after
connected,requiretheuseofatooltodisconnect.Thisdefendsagainstuntrained
personneldisconnectingthemoduleswhenunderload.ACcableconnectorsare
ratedandtestedtointerruptloadcurrent;however,SunPowerrecommendsthat
youalwaysopentheutilitydedicatedbranchcircuitprotectortoremovepower
beforepluggingorunplugginganyconnectors;butalocalACdisconnectisnot
requiredbySunPower.
WheninstallingACmodulestheNationalElectricCode,ANSI/NFPA70wiring
methodsshallbeused.
4.1EquipmentGrounding
Toreducethepossibilityofelectricalshock,groundthemoduleframeorarray
perNECbeforewiringthecircuit.InordertoinstallinaccordancewiththeirUL
Listing,SunPowerACmodulesmustbegroundedusingListedgrounding
hardwarethatmeetsrequirementsforgroundingsystemsinUL467,UL1703,UL
1741,orUL2703;onanodizedaluminumframes.SunPowerrecommendsusing
oneofthefollowingmethodsofgroundingthemoduleframe.ASeries‐BLK
modulesmustbeinstalledwiththeGroundLugAssemblyoftheInvisimount
mountingsystemusingtheIlscoGBL4DBTgroundinglugtightenedtoatorqueof
85inlbstobondthemoduleframetotherail.Inaddition,toavoidcorrosiondue
totheuseofdissimilarmetalsSunPowerrecommendsstainlesssteelbetween
copperandaluminum.
Important!Pleasereadtheseinstructionsintheirentiretybefore
installing,wiring,orusingthisproductinanyway.Failuretocomply
withtheseinstructionswillinvalidatetheSunPowerLimited
WarrantyforPVModules.
Danger
!
ACmodulesgenerateinternaldirectcurrent(DC)andoutput
alternatingcurrent(AC);andareasourceofvoltagewhenunderloadand
whenexposedtolight.Electricalcurrentscanarcacrossgapsandmay
causeinjuryordeathifimproperconnectionordisconnectionismade;orif
contactismadewithmoduleleadsthatarefrayedortorn.
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
1) ModulesmaybegroundedthroughtheuseofanInvisiMount™midclamp
thatbondsthemoduleframetotheInvisiMountrail.ThismethodisUL
2703Listed.InvisiMountrailsectionsmustbebondedandconnectedtoa
groundingconductorusingmethodsandmaterialsspecifiedinthe
InvisiMountResidentialMountingSystemInstallationGuide508988.
2) Modulesmaybegroundedbyattachingalayinlug(IlscoGBL4DBT,Burndy
CL50DBTorTycoSolklip19543812)tooneofthegroundingholesonthe
moduleframe,andattachthegroundconductortothelug.Usestainless
steelhardware(bolt,washers,andnut).Useanexternaltoothstarwasher
betweenthelugandthemoduleframeinordertopiercetheanodizingand
establishelectricalcontactwiththealuminumframe.Theassemblymust
endwithanutthat’storquedto20–25inlb(fora#1032bolt).Alock
washerorotherlockingmechanismisrequiredtomaintaintension
betweentheboltandtheassembly.Theconductormustbeattachedtothe
groundlugusingthelug’ssetscrew.RefertoNEC690.
Note:Method3isevaluatedtoUL1703byETL.Assuch,theuseofthesedevices
isnotconsideredpartoftheULListingofthesemodules.
3) IftheUniracSOLARMOUNTsystemisused,modulesmaybegroundedby
usingeitheraBURNDYWileyWEEBUMCorWEEBUGC1groundingclipin
combinationwithUniracMidorEndclampsand1/420boltandflanged
nut,torquedto120inlbs.IftheSolarmountIsystemisusedgroundingis
achievedwiththeUniracUGC2groundingclipsincombinationwithUnirac
MidorEndclampsandSliderswitha1/420boltandflangednuttorquedto
120inlbs.
Note:Method4wasevaluatedtoUL2703byTUV.Assuch,theuseofthese
devicesisnotconsideredpartoftheULListingofthesemodules.
4) ModulesmaybegroundedusingaWEEB9.5NLgroundclipbetweenthe
moduleandsupportingstructure.Thiscombinationissecuredwitha1/4″
stainlesssteelrivetora1/420×3/4″zincplatedboltwithzincplatedKnut
torquedtomin.6ftlbstosecurethemoduletominimum12ga.G90
coatedsteelorZpurlin,eitherpaintedorunpainted.TheWEEB9.5NLisfor
singleuseonly.
5) Othergroundingmethodsmaybeusedinconjunctionwithamodule
mountingsystemcompliantwithUL2703.Fortheseinstallations,the
SunPowermoduleandframestylemustbetestedandpartofthe
instructionsfortheListedmountingproduct.TheSunPowermodulemust
beinstalledinaccordancewiththeseinstructionsaswellasthemounting
system’sListedinstructions.
4.2ConnectiontoACCircuits
Itistheinstaller’sresponsibilitytoverifygridcompatibility(120/240or120/208
wye3phase4wire2pole).SunPowerACmodulesmustbeconnectedtoautility
sourceatthecorrectvoltageandfrequencyinordertooperateandproduce
power.TheyarenotstandalonegeneratorsanddonotcreateACvoltagethusare
notcapableofoperationindependentofautilitygeneratedACsignal.TheAC
modulesmustbeconnectedonlytoadedicatedbranchcircuit.TheACcablesand
connectorsarecertifiedandratedforthemaximumnumberofACunitsinparallel
only.Whenconnectingmodules,DONOTexceedthefollowingsinglebranch
circuitmaximumnumberofmodules:
240VAC:12(singlephase)
208VAC:10(twopolewye)
Thiscircuitmustbeprotectedbyovercurrentprotection.
CAUTION!Toreducetheriskoffire,connectonlytoa
circuitprovidedwith20Amaximumbranchcircuit
overcurrentprotectioninaccordancewiththeNational
ElectricalCode,ANSI/NFPA70.
Belowarethemajorinstallationsteps:
1. InstalltheFieldwireableconnectorpair,optionalJBox
2. PositiontheEnphaseQCable
Permodule:
3. PositionACmoduleandpopoutmicroinverters.RefertoSection
5.3forillustration
4. ConnectmicroinverterstoQCableconnector
5. InstallACModules
6. ManageQcabletomoduleframeandrail
Perrow:
7. Createinstallationmap
8. TerminateQcableatlastmicroinverter
9. ConnecttoJBox
10. Energizesystem
4.3CableManagement
UsecableclipsorcabletieswrapstoattachtheACcabletotheracking.Thecable
mustbesupportedtoavoidanycable
unduesagasperlocalrequirement.
ForPerformance3ACmodules,becareful
tonotunplugtheDCcablepremountedin
factoryintospecificcablesupports.
Dressanyexcesscablinginloopssothatit
doesnotcontacttheroof.Donotform
loopssmallerthan4.75inch(12cm)in
diameter.
4.4MicroinvertersConnection
RefertothemajorinstallationstepsdefinedinSection4.2andlistenforaclick:
1)whenthemicroinvertersarepopoutand
2)whenACconnectorsengage
InspecttheACconnectorstoensurethattheyare
notbroken,misshapen,orotherwisedegraded
priortoconnection.
CoveranyunusedconnectorsontheACcable
withEnphaseSealingCaps.Listenforaclickas
thesealingcapsengage.
CAUTION!InstallsealingcapsonallunusedACconnectors
astheseconnectorsbecomelivewhenthesystemis
energized.Sealingcapsarerequiredforprotectionagainst
moistureingress.
5.0 ModuleMounting
ThissectioncontainsinformationforSunPowerTypeEACmodules;TypeGAC
andSunPowerTypeHACmodules.Ensurethatyouusethecorrectinformation
foryourmoduletype.
TheSunPowerLimitedWarrantyforPVModulesiscontingentuponmodules
beingmountedinaccordancewiththerequirementsdescribedinthissection.
5.1SiteConsiderations
SunPowermodulesshouldonlybemountedinlocationsthatmeetthefollowing
requirements:
OperatingTemperature:AllSunPowerACmodulesmustbemountedin
environmentsthatensurethatthemoduleswilloperatewithinthefollowing
maximumandminimumtemperatures:
Max.OperatingCellTemp.+85°C(+185°F)
Max.AmbientTemp.+50°C(+122°F)
Min.OperatingTemp.−40°C(40°F)
DesignStrength:SunPowerTypeE,TypeGandTypeHACmodulesaredesigned
tomeetamaximumpositive(orupward,e.g.wind)andnegative(ordownward,
e.g.staticload)designpressurewhenmountedinthemountingconfigurations
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
specifiedinSection5.2.(Designstrengthof2400Pacorrespondsapproximatelyto
awindspeedof130km/h(81mph).SunPowerACmoduleshavealsobeen
evaluatedtoUL1703forapositiveornegativedesignloadof30psf.)
TypeE.ThefollowingimageandtableshowwheretomounttotheTypeE
moduleframe;anddefinesmountingrangesandtheresultingloadratings
achievedforeachrange:
MountingRange
Toleranceareidenticalat
eachmodulecorner
in./mmfromcorner
LoadRating
(Pa)*
Wind
(upanddown)
Snow
(down)
R1
02/050
DONOTMOUNT!
R2
211.8/5030030006000
R3
11.815.75/30040030006000
R4
214.75/5037530003000
R5DONOTMOUNT!
R6DONOTMOUNT!
*DesignloadvaluesmaybeusedasASDdesignloads.
TypeGandTypeH.
Important!ThefollowingimageandtablesshowwheretomounttotheTypeG
andHmoduleframeandtheallowableloadratingscorrespondingtothe
mountingzoneschosen.Tousethetables,identifythetwomountingzonesin
whichyouwishtomount.YoumaychoosetomountatanylocationinzonesA,B,
andC,aslongasthemountingpointsaresymmetricaboutoneaxisofthe
module.Identifythecombinationofmountingzonesyouhavechoseninthe
tableandthenrefertothecorrespondingloadrating.Notealsothatloadratings
aredifferentformodulessupportedbyrails;versussystemsthatattachmodules
withoutrails.
Table1.MountingConfigurationandLoadResistance
Mounting
Method
Mounting
(1)
Test/
Design
Load(2)
Downward(+)/
Upward()Pressure
(Pa)(1)
ASeries/MSeries
Rail
Supported
w/oRail
Support
TopClamp
BB
TestLoad8100/40505400/3600
DesignLoad5400/27003600/2400
CC
TestLoad2400/25502400/2400
DesignLoad1600/17001600/1600
AA
TestLoad3600/24002400/2400
DesignLoad2400/16001600/1600
EE
TestLoad
NA2400/2400
DesignLoad1600/1600
Boltor
Invisimount
Clamps
BB
TestLoad9000/54005400/5400
DesignLoad6000/36003600/3600
CC
TestLoad4200/42003600/4200
DesignLoad2800/28002400/2800
AA
TestLoad4500/30003000/3000
DesignLoad3000/20002000/2000
 DDDONOTMOUNT
(1) Ifmountinginmultiplezones,mustusethelowervalueofthetwozones.
(2) Testloadsareevaluatedat1.0factorofsafety,andDesignloadsare
calculatedusing1.5factorofsafety(Testload=1.5xDesignload).Design
loadvaluesmaybeusedasASDdesignloads.
Whenmountingmodulesinsnowproneorhighwindenvironments,specialcare
shouldbetakentomountthemodulesinamannerthatprovidessufficientdesign
strengthwhilemeetinglocalcoderequirements.
ExcludedOperatingEnvironmentsandReconfigurations
CertainoperatingenvironmentsarenotrecommendedforSunPowerACmodules,
andareexcludedfromtheSunPowerLimitedWarrantyforthesemodules.Contact
SunPowerifthereareanyunansweredquestionsconcerningtheoperating
environment.
5.2MountingConfigurations
Modulesmaybemountedattheappropriateorientationtomaximizesunlight
exposure.
Inordertopreventwaterfromenteringthejunctionbox(whichcouldpresenta
safetyhazard),modulesshouldbeorientedsuchthatthejunctionboxisinthe
uppermostpositionandshouldnotbemountedsuchthatthetopsurfacefaces
downward.Inaddition,ensurethemoduleorientationalsopreventsthe
microinverterfromdirectexposuretorain,UVandotherharmfulweatherevents
(ice/snow).
Clearancebetweenthemoduleframeandmountingstructureorgradeisrequired
topreventwiringdamageandtoenableairtocirculatebehindthemodule.A
minimumof2″ (5cm)isrequiredbetweenthemoduleframeandstructureor
ground.
SunPowerACmodulesareonlyNRTLListedforusewhentheirfactoryframesare
fullyintact.Donotremoveoralteranymoduleframe.Creatingadditional
mountingholesmaydamagethemoduleandreducethestrengthoftheframe.
Modulesmaybemountedusingthefollowingmethodsonly:
1) PressureClampsorClips:Mountthemodulewiththeclipsattachedtothe
longersidesofthemodule.RefertotheallowablerangesinSection5.0.
Installersmustensuretheclampsareofsufficientstrengthtoallowforthe
maximumdesignpressureofthemodule.
2) EndMount:Endmountingisthecapturemountingofthemodule’sshorter
sidestoasupportingrail.Theendmountingrailandclipsorclampsmustbe
ofsufficientstrengthtoallowforthemaximumdesignpressureofthe
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
module.Verifythiscapacitywiththemountingsystemvendorbefore
installation.
3) SunPower,SunPowerspecified,orSunPowersuppliedmountingsystems:
ModulesmountedwithstrictadherencetoSunPowerdocumentation,using
hardwaresystemssuppliedbyorspecifiedbySunPower.
5.3HandlingofModulesduringInstallation
Neverliftormovethemodulesusingcablesorthejunctionboxunderany
circumstances.Donotplacemodulesfaceforwardindirectcontactwithabrasive
surfacessuchasroofs,driveways,woodenpallets,railings,orwalls.Thefront
surfaceofamoduleissensitivetooilsandabrasivesurfaces,whichmayleadto
scratchesandirregularsoiling.
SunPowerrecommendshandlingmoduleswithglovesandnottouchingthefront
surface.Anyfingerprintsresultingfrominstallationcanbereducedbyfollowing
thewashingguidelinesinSection6.0.Agivenmodule’sproductdatasheetspecifies
theglasstypeituses.
BeforeinstallingtheACmodule,themicroinvertersmustbeliftedfromthe
shippingposition,facesyou.Usingbothhands,liftthemicroinverterup.Youwill
hearfourclicksasthemicroinverterlocksintotheinstallationposition.Ensurethe
fourlatchesarelocked,andthemicroinverterisnottilted.
ShippingPosition:
InstallPosition:
6.0 Maintenance
Visuallyinspectallmodulesannuallytoverifytheintegrityofboththeelectrical
andthemechanicalconnections;andtoverifytheabsenceofcorrosion.Thisvisual
inspectionshouldbeperformedbyanauthorizedSunPowerDealerortrained
SunPowersupportpersonnel.
Periodiccleaningofmodulesisrecommendedbutisnotrequired.Periodic
cleaninghasresultedinimprovedmoduleperformance,especiallyinregionswith
lowlevelsofannualprecipitation(fewerthan18.25inchesannually).Consultyour
Dealerorsupplieraboutrecommendedcleaningschedulesforyourarea.Toclean
amodule,sprayitwithpotable,nonheatedwater.Normalwaterpressureismore
thanadequate,butpressurizedwater(upto1500psi)maybeused.Fingerprints,
stains,oraccumulationsofdirtonthefrontsurfaceofthemodulemayberemoved
asfollows:rinsetheareaandwait5minutes.Rewettheareaandthenuseasoft
spongeorseamlessclothtowipetheglasssurfaceinacircularmotion.NEVERuse
harshcleaningmaterialssuchasscouringpowder,steelwool,scrapers,blades,or
othersharpinstrumentstocleanmoduleglass.Useofsuchmaterialsonthe
moduleswillvoidtheproductwarranty.
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
7.0 ElectricalCharacteristicsandGridInteraction
TypeE.
VoltageandFrequencyLimitsforUtilityInteraction
c
Condition
SimulatedSourceMaximumTime(sec)at60Hz
a
beforecessationofcurrentto
thesimulatedutility
Voltage(V)Frequency(Hz)
A<0.50V
norb
Rated0.16
B0.50V
norb
≤V<1.20
V
nor
Rated2
C1.10V
norb
≤V<1.20
V
nor
Rated 1
D1.20V
nor
≤VRated 0.16
ERatedf>rated+0.50.16
FRatedf<rated0.70.16
GVoltVarAccuracyx

aNonadjustablemaximumclearingtimes
bNominalvoltageequals240Vlinetoline
cTripLimitaccuracy:Voltage±1.0%basedon240Vnominal,frequency‐±0.1Hz
IrmsTotaldurationSynchronizationinrush
current
TripTimeAccuracy
5.8A100ms0.2A20ms
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
TypeG.
VoltageandFrequencyLimitsforUtilityInteraction
c
Condition
SimulatedSource
MaximumTime(sec)at60Hz
a
beforecessationofcurrentto
thesimulatedutility
Voltage(V)
Frequency
(Hz)
A
<0.50V
norb
Rated
0.16
B
0.50V
norb
≤V<1.20V
nor
Rated
2
C
1.10V
norb
≤V<1.20V
nor
Rated
1
D
1.20V
nor
≤V
Rated
0.16
E
Rated
f>rated+0.5
0.16
F
Rated
f<rated0.7
0.16
G
VoltVar
Accuracy
6%
aNonadjustablemaximumclearingtimes
bNominalvoltageequals240Vlinetoline
cTripLimitaccuracy:Voltage±1.0%basedon240Vnominal,frequency‐±0.1Hz
IrmsTotaldurationSynchronizationinrush
current
TripTimeAccuracy
5.8A100ms0.2A2linecycles
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
TypeH.

VoltageandFrequencyLimitsforUtilityInteraction
c
Condition
SimulatedSource
MaximumTime(sec)at60Hz
a
beforecessationofcurrentto
thesimulatedutility
Voltage(V)
Frequency
(Hz)
A
<0.50V
norb
Rated
0.16
B
0.50V
norb
≤V<1.20V
nor
Rated
2
C
1.10V
norb
≤V<1.20V
nor
Rated
1
D
1.20V
nor
≤V
Rated
0.16
E
Rated
f>rated+0.5
0.16
F
Rated
f<rated0.7
0.16
G
VoltVar
Accuracy
6%
aNonadjustablemaximumclearingtimes
bNominalvoltageequals240Vlinetoline
cTripLimitaccuracy:Voltage±1.0%basedon240Vnominal,frequency‐±0.1Hz
IrmsTotaldurationSynchronizationinrush
current
TripTimeAccuracy
5.8A100ms0.2A2linecycles
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
TypeE.
TypeG.

18351835 72.2
1017 40.0
30[1.2] 22[.87]
32[1.26] 24[.94]
Gen 5.1 Frame Profile
Gen 5.2 Frame Profile
40[1.57] 40[1.57]
40[1.57] 40[1.57]
367.7[14.32]
46.5[1.83]
SUNPOWERCORPORATION
531725RevJ
©2022SunPowerCorporation.Allrightsreserved.Specificationsincludedinthisdocumentaresubjecttochangewithoutnotice.
TypeH.
1872 73.7
1032 40.6
32[1.26] 24[.94]
Gen 5.2 Frame Profile
40[1.57] 40[1.57]
375.2[14.77]
46.5[1.83]
Ground Holes
24[.94]
40[1.57]
32[1.26]
40[1.57]
Gen 5.2 Frame Profile
382.70
[15.07]
249mm [9.79]
1100 mm [43.3]
1872 mm [73.7]
1032 mm [40.6]
Mounng Holes
4X Ø 6.8mm [0.27]
4X Ø 4.2mm [0.17]
Ground Holes
/