RM-204/208 Relay Module Installation Instructions
LT-1010 Rev. 1
February 2007
RM-204/208 Relay Adder Module Installation Instructions
Board Layout
P1: Connect to P1 on the Main Fire Alarm Board.
By factory setting, the 4 or 8 relays are controlled by Initiating Circuits 1 to 8 respectively. This is configured by
selecting
• JW1: Initiating Circuit #1 controls Relay #1.
• JW2: Initiating Circuit #2 controls Relay #2.
to....
• JW8: Initiating Circuit #8 controls Relay #8.
Alternately, each relay may be set as a Common Alarm or Common Supervisory Relay by removing the jumper
from JW1 to JW1A, etc. These jumpers have two positions to select Alarm or Supervisory each.
• JW1A: Alarm or Supv. control for Relay #1.
• JW2A
: Alarm or Supv. control for Relay #2.
to....
• JW8A: Alarm or Supv. control for Relay #8.
Finally, there are jumpers JW1.2, JW2.3, up to JW7.8 that allow a relay to have the same control as an adjacent
relay. For example, starting with the factory default setting, moving the jumper from JW2 to JW1.2 will make both
Relays 1 & 2 operate with Initiating Circuit #1.
Contact Mircom Technical Support for assistance if required.