Fujitsu ARXA30GBLH Installation guide

Category
Split-system air conditioners
Type
Installation guide

This manual is also suitable for

EnglishDeutschFrançaisEspañolItalianoΕλληνικάPortuguêsРусскийTürkçe
PART NO. 9373385202-02
ARXA24GBLH
ARXA30GBLH
ARXA36GBLH
ARXA45GBLH
TM
INSTALLATION MANUAL
INDOOR UNIT (Duct type)
For authorized service personnel only.
INSTALLATIONSANLEITUNG
INNENGERÄT (Kanaltyp)
Nur für autorisiertes Fachpersonal.
MANUEL D’INSTALLATION
MANUAL DE INSTALACIÓN
UNITÉ INTÉRIEURE (type conduit)
UNIDAD INTERIOR (Tipo conducto)
Pour le personnel agréé uniquement.
Únicamente para personal de servicio autorizado.
MANUALE DI INSTALLAZIONE
UNITÀ INTERNA (tipo a condotto)
A uso esclusivo del personale tecnico autorizzato.
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ (Τύπος αγωγού)
Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.
MANUAL DE INSTALAÇÃO
UNIDADE INTERIOR (Tipo de tubagem)
Apenas para técnicos autorizados.
РУКОВОДСТВО ПО УСТАНОВКЕ
ВНУТРЕННИЙ МОДУЛЬ (Короб)
Только для авторизованного обслуживающего персонала.
MONTAJ KILAVUZU
İÇ ÜNİTE (Kanal tipi)
Yalnızca yetkili servis personeli için.
[Original instructions]
MADE IN P.R.C.
Refer to the rating label for the serial number,
manufactured year and month.
En-1
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the Operating Manual to the customer.
Request the customer to keep them on hand for future use, such as for relocating or
repairing the unit.
WARNING
This mark indicates procedures which, if improperly performed,
might lead to the death or serious injury of the user.
Request your dealer or a professional installer to install the unit in accordance with this
Manual.
An improperly installed unit can cause serious accidents such as water leakage,
electric shock, or re.
If the unit is installed in disregard of the instructions in the Installation Manual, it will
void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed.
Turning ON the power before the work is completed can cause serious accidents such
as electric shock or re.
If refrigerant leaks while work is being carried out, ventilate the area.
If the refrigerant comes in contact with a ame, it produces a toxic gas.
Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
Except for EMERGENCY, never turn off main as well as sub breaker of the indoor
units during operation. It will cause compressor failure as well as water leakage.
First, stop the indoor unit by operating the control unit, converter or external input
device and then cut the breaker.
Make sure to operate through the control unit, converter or external input device.
When the breaker is designed, locate it at a place where the users cannot start and
stop in the daily work.
CAUTION
This mark indicates procedures which, if improperly performed,
might possibly result in personal harm to the user, or damage to
property.
Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by qualified personnel with a capacity certificate for handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the place of
installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or
with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3mm for this unit.
The unit must be correctly grounded and the supply line must be equipped with a
differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Never touch electrical components immediately after the power supply has been turned
off. Electric shock may occur. After turning off the power, always wait 5 minutes before
touching electrical components.
This unit contains no user-serviceable parts. Always consult authorized service
personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation of
the unit.
2. ABOUT THIS PRODUCT
2.1. Precautions for using the R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the
refrigeration cycle.
If air enters the refrigeration cycle, the pressure in the refrigeration cycle will become
abnormally high and cause the piping to rupture.
If there is a refrigerant leakage, make sure that it does not exceed the concentration
limit.
If a refrigerant leakage exceeds the concentration limit, it can lead to accidents such
as oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leakage occurs during operation, immediately vacate the premises and
thoroughly ventilate the area.
If the refrigerant comes in contact with a ame, it produces a toxic gas.
2.2. Special tool for R410A
WARNING
To install a unit that uses the R410A refrigerant, use dedicated tools and piping
materials that have been manufactured speci cally for R410A use.
Because the pressure of the R410A refrigerant is approximately 1.6 times higher than
the R22, failure to use dedicated piping material or improper installation can cause
rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or
re.
Tool name Contents of change
Gauge manifold
Pressure is huge and cannot be measured with a
conventional (R22) gauge. To prevent erroneous mixing
of other refrigerants, the diameter of each port has been
changed.
It is recommended to use a gauge manifold with a
high pressure display range –0.1 to 5.3 MPa and a low
pressure display range –0.1 to 3.8 MPa.
Charging hose
To increase pressure resistance, the hose material and
base size were changed.
Vacuum pump
A conventional (R22) vacuum pump can be used by
installing a vacuum pump adapter.
Be sure that the pump oil does not backflow into the
system. Use one capable for vacuum suction of –100.7 kPa
(5 Torr, –755 mmHg).
Gas leakage detector Special gas leakage detector for HFC refrigerant R410A.
Contents
1. SAFETY PRECAUTIONS ............................................................................................ 1
2. ABOUT THIS PRODUCT............................................................................................. 1
2.1. Precautions for using the R410A refrigerant ......................................................... 1
2.2. Special tool for R410A .......................................................................................... 1
2.3. Accessories .......................................................................................................... 2
2.4. Optional parts ....................................................................................................... 2
3. INSTALLATION WORK ............................................................................................... 3
3.1. Selecting an installation location .......................................................................... 3
3.2. Installation dimensions ......................................................................................... 3
3.3. Installing the unit ................................................................................................... 3
4. PIPE INSTALLATION .................................................................................................. 5
4.1. Selecting the pipe material ................................................................................... 5
4.2. Pipe requirement .................................................................................................. 5
4.3. Flare connection (pipe connection) ...................................................................... 5
4.4. Installing heat insulation ....................................................................................... 6
5. INSTALLING DRAIN PIPES ........................................................................................ 6
6. ELECTRICAL WIRING ................................................................................................ 8
6.1. Electrical requirement ........................................................................................... 8
6.2. Wiring method ...................................................................................................... 9
6.3. Unit wiring ............................................................................................................. 9
6.4. Connection of wiring ........................................................................................... 10
6.5. External input and external output (Optional parts) ............................................ 11
6.6. Remote sensor (Optional parts) ......................................................................... 13
6.7. IR receiver unit (Optional parts) .......................................................................... 13
6.8. Drain pump unit (Optional parts) ........................................................................ 14
7. FIELD SETTING ........................................................................................................ 14
7.1. Setting the address ............................................................................................. 14
7.2. Custom code setting ........................................................................................... 15
7.3. Static pressure mode .......................................................................................... 15
7.4. Function setting .................................................................................................. 16
8. TEST RUN ................................................................................................................. 16
8.1. Test run using Outdoor unit (PCB) ...................................................................... 16
8.2. Test run using Remote Controller ....................................................................... 16
9. CHECK LIST .............................................................................................................. 16
10. ERROR CODES ........................................................................................................ 17
INSTALLATION MANUAL
PART NO. 9373385202-02
VRF system indoor unit (Duct type)
En-2
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit to fall,
water leakage, electric shock, or re.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Do not discard any accessories needed for installation until the installation work has been
completed.
Name and Shape Q’ty Application
Operating manual
1
Installation manual
1
(This book)
Cable tie (Large)
5
For fixing the connection pipe (Large
and Small) and drain cap
Cable tie (Medium)
3
For transmission and remote
controller cable binding
Coupler heat insulation
(Small)
1
For indoor side pipe joint (Small)
Coupler heat insulation
(Large)
1
For indoor side pipe joint (Large)
Special nut A
(Large flange)
4
For suspending the indoor unit from
ceiling
Special nut B
(Small flange)
4
Hanger
4
For suspending the indoor unit from
ceiling
Drain hose
1
For installing drain pipe
VP25 (O.D.32, I.D.25)
Hose band
1
For installing drain hose
Drain hose insulation
2
Insulates the drain hose and drain
cap
2.4. Optional parts
When connecting the square duct and round duct, use the optional square flange or
round ange.
Square ange
Model name : UTD–SF045T (P/N 9098180007)
1,063 mm
40 mm
206 mm
Round ange
Model name : UTD–RF204 (P/N 9093160004)
85 mm
ø195 mm
ø205 mm
ø225 mm
ø235 mm
Long-life lter
Model name : UTD–LF25NA (P/N 9079892004)
507 mm
239 mm
Other optional parts
Description Model Application
External connect kit
UTY-XWZXZC
For output function
(Output terminal / CNB01)
UTY-XWZXZB
For control input function
(Apply voltage terminal / CNA01)
UTY-XWZXZD
For control input function
(Dry contact terminal / CNA02)
UTY-XWZXZ7
For forced thermostat off function
(Apply voltage terminal / CNA03)
UTY-XWZXZE
For forced thermostat off function
(Dry contact terminal / CNA04)
Remote sensor UTY-XSZX Room temperature sensor
IR receiver unit UTB-*WC For the wireless remote controller.
Drain pump unit UTZ-PX1NBA
When installing, please refer to the installation manual of each optional part.
En-3
3. INSTALLATION WORK
Correct initial installation location is important because it is dif cult to move unit after it is
installed.
3.1. Selecting an installation location
WARNING
Select installation locations that can properly support the weight of the indoor. Install
the units securely so that they do not topple or fall.
CAUTION
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam, such
as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
Area that can cause combustible gas to leak, contains suspended carbon bers or
ammable dust, or volatile in ammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a re.
Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or ammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, power supply cable, transmission cable, and remote controller
cable at least 1 m away from a television or radio receivers. The purpose of this is to
prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under
some signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Decide the mounting position with the customer as follows:
(1) Install the indoor unit on a place having a suf cient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) A place from where the air can be distributed evenly throughout the room by the unit.
(5) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(6) Install the unit where the connection pipe can be easily installed.
(7) Install the unit where the drain pipe can be easily installed.
(8) Install the unit where noise and vibrations are not ampli ed.
(9) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the lter can be removed.
(10) Providing as much space as possible between the indoor unit and the ceiling will
make work much easier.
(11) If installing in a place where its humidity exceeds 80%, use heat insulation to
prevent condensation.
3.2. Installation dimensions
• Provide the space around the unit as shown in the following gure.
400 mm or more
150 mm or more
*1
*
1
400 mm or more when drain from drain pipe.
• Provide a service access for inspection purposes.
• Do not place any wiring or illumination in the service space, as they will impede service.
• When an air lter is installed on the air inlet, provide enough service space to replace
the lter.
Air
Air
Service access
Indoor unit
(unit : mm)
300 or
more
500 or more
[Top view]
500 or more
100
Air
Air
Service space
Indoor unit
(unit : mm)
300 or
more
1,550 or more
[Top view]
500 or more
100
3.3. Installing the unit
WARNING
Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
3.3.1. Installing the hangers
Hanging bolt installation diagram.
(Top side)
(Right side)
270 mm
Air
Air
740 mm
477 mm
Air
Air
1,135 mm
1,177 mm
En-4
CAUTION
When air is taken in from the bottom side, the operating sound of the product will easily
eater the room.
Install the product and intake grilles where the affect of the operating sound is small.
Install the product and intake grilles where the affect of the operating sound is small.
3.3.4. Outlet duct
Duct installation pattern ( CUT PART)
Round duct outlet
4 (Factory setting.)
Square duct
• When using the square duct, follow the procedure below to process outlet duct.
Cut
Cut
Cut
Cut
(2) Turn up the insulation around the points to be cut according to the outlet port
shape working points so that the insulation does not stick out at the
part.
(1) Cut the slit seam with a cutter.
(3) Cut with nippers and remove the sheet metal.
• The screw holes to install the ange are located behind the round cutouts in the insula-
tion.
WARNING
When fastening the hangers, make the bolt positions uniform.
The distance of
is adjustable according to the place of the hanging bolts.
(MAX : 550 mm, MIN : 410 mm)
Slide the unit in the arrow direction and fasten it.
Hanging bolt M10
(locally purchased)
Special nut A (Accessories)
Washer (locally purchased)
Special nut B (Accessories)
Hanger (Accessories)
Bolt Strength 9.81 to 14.71 N.m
WARNING
Fasten the unit securely with special nuts A and B.
3.3.2. Leveling
Base vertical direction leveling on the unit (right and left).
(Right side)
Level
Air
Air
Base horizontal direction leveling on top of the unit.
Drain hose
0 to 5 mm
Give a slight tilt to the side to which the drain hose is connected. The tilt should be in the
range of 0 mm to 5 mm.
3.3.3. Intake duct
Follow the procedure in the following gure to the ducts.
1,015 mm
240 mm
The air inlet duct can be changed by replacing the intake grille and ange. For the bottom
air intake, follow the procedure of
1
2
for installation. (The factory setting is back air
intake.)
1
2
En-5
CAUTION
To prevent people from touching the parts inside the unit, be sure to install grilles on
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
If an intake duct is installed, take care not to damage the temperature sensor (the
temperature sensor is attached to the intake port ange).
Install the air inlet grille for air circulation. The correct temperature can not be detected.
Unit
Outlet grille
(locally purchased)
Inlet grille
(locally purchased)
(Room)
Duct
(locally purchased)
Be sure to install the air lter in the air inlet. If the air lter is not installed, the heat
exchanger may be clogged and its performance may decrease.
3.3.5. Fresh air intake
(Processing before use)
(1) When taking in fresh air, cut a slit shaped cabinet in the left side of the outer case
with nippers.
Cut
Cut
Cabinet (Iron plate)
Round hole
CAUTION
When removing the cabinet (iron plate), be careful not to damage the indoor unit
internal parts and surrounding area (outer case).
When processing the cabinet (iron plate), be careful not to injure yourself with burrs,
etc.
(2) Install the round ange (optional parts) to the fresh air intake.
Round duct
(3) Connect the duct to the round ange.
(4) Seal with a band and vinyl tape, etc. so that air does not leak from the connection.
Duct
4. PIPE INSTALLATION
CAUTION
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant R410A models. Also, when storing the piping, securely seal the openings
by pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas through them.
4.1. Selecting the pipe material
CAUTION
Do not use existing pipes from another refrigeration system or refrigerant.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion
(especially on the interior surface). Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary
to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than those indicated in the table even if they are
available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in)] Thickness [mm]
6.35 (1/4) 0.80
9.52 (3/8) 0.80
12.70 (1/2) 0.80
15.88 (5/8) 1.00
19.05 (3/4) 1.20
4.2. Pipe requirement
CAUTION
Refer to the Installation Manual of the outdoor unit for description of the length of
connecting pipe or for difference of its elevation.
• Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may
cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70 %, install heat insulation around the refrigerant piping. If the
expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or thicker and
if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as speci ed, condensation may form on
the surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m·K) or less (at 20 °C).
4.3. Flare connection (pipe connection)
WARNING
Tighten the flare nuts with a torque wrench using the specified tightening method.
Otherwise, the are nuts could break after a prolonged period, causing refrigerant to
leak and generate hazardous gas if the refrigerant comes into contact with a ame.
En-6
4.3.1. Flaring
Use special are tool exclusive for R410A.
(1)
Cut the connection pipe to the necessary length with a pipe cutter.
(2)
Hold the pipe downward so that cuttings will not enter the pipe and remove any
burrs.
(3)
Insert the are nut (always use the are nut attached to the indoor and outdoor units
(or RB unit) respectively) onto the pipe and perform the are processing with a are
tool. Use the special R410A are tool. Leakage of refrigerant may result if other are
nuts are used.
(4)
Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
L
Check if [L] is ared uniformly
and is not cracked or scratched.
B
A
Pipe
Die
Pipe outside
diameter
[mm (in)]
Dimension A [mm]
Dimension B
-
0
0.4
[mm]
Flare tool for R410A,
clutch type
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional (R22) are tools to are R410A pipes, the dimension A should
be approximately 0.5 mm more than indicated in the table (for aring with R410A are
tools) to achieve the speci ed aring. Use a thickness gauge to measure the dimension A.
It is recommended that a R410A aring tool is used.
Width across
ats
Pipe outside
diameter [mm (in)]
Width across flats
of Flare nut [mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
4.3.2. Bending pipes
If pipes are shaped by hand, be careful not to collapse them.
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bend or stretched, the material will harden, making it
dif cult to bend or stretch them any more.
Do not bend or stretch the pipes more than 3 times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
4.3.3. Pipe connection
When the are nut is tightened properly by your hand, hold the body side coupling with
a separate spanner, then tighten with a torque wrench. (See the table below for the are
nut tightening torques.)
CAUTION
Be sure to install the pipe against the port on the indoor unit correctly. If the centering
is improper, the are nut cannot tighten smoothly. If the are nut is forced to turn, the
threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before
connecting the connection pipe.
Hold the torque wrench at its grip, keeping at a the right angle with the pipe, in order
to tighten the are nut correctly.
Tighten with 2 wrenches.
Holding wrench
Flare nut
Connection pipe
Torque wrench
Indoor unit pipe
(Body side)
Flare nut [mm (in)] Tightening torque [N·m (kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
4.4. Installing heat insulation
• Insulate by the coupler heat insulation (Accessories) around the gas pipe and liquid pipe
of indoor side.
After installing the coupler heat insulation, wrap both end with vinyl tape so that there is
no gap.
• After af xing the coupler heat insulation, secure it with 2 cable ties (large), one on each
end of the insulation.
• Make sure that the cable ties overlap the heat insulation pipe.
Coupler heat
insulation
(Accessories)
Cable tie (Large)
(Accessories)
Heat insulation
Cover this portion with
heat insulation.
CAUTION
After checking for gas leaks (refer to the Installation Manual of the outdoor unit),
perform this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.
5. INSTALLING DRAIN PIPES
Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride)
so that there is no leakage.
Always heat insulate the indoor side of the drain hose.
Use a drain hose that matches the size of the drain pipe.
Do not perform a rise, trap and air bleeding.
Provide a downward gradient (1/100 or more).
Provide supporters when long pipes are installed.
Use an insulation material as needed, to prevent the pipes from freezing.
Install the pipes in a way that allows for the removal of the control box.
En-7
(Right side)
Liquid pipe
Drain port
Gas pipe
240 mm
32 mm
66 mm
114 mm
(Left side)
Drain port
The drain cap is attached
at the factory setting.
32 mm
240 mm
O.D.
Drain pipe 32 mm (VP25)
When the unit is shipped from the factory, the drain port is on the right side (control box
side).
When using the drain port on the left side of the unit, reinstall the drain cap to the right
side drain port.
Drain port
Drain cap
Cable tie (Large)
(Accessories)
• Cover the drain cap with the drain hose insulation.
Drain hose insulation (Accessories)
Unit
Unit
Drain hose insulation
(Accessories)
Drain cap
0 mm
Install the drain hose
Working procedure
1) Install the attached drain hose to the drain port of the body. Install the hose band from
the top of the hose within the graphic display area. Secure rmly with the hose brnd.
2) Use vinyl adhesive agent to glue the drain piping (PVC pipe VP25) which is prepared on
site or socket. (Apply color adhesive agent evenly until the gauge line and seal)
3) Check the drainage.
4) Install the heat insulation.
5) Use the attached heat insulation to insulate the drain port and band parts of the body.
Ensure there is no space
(Accessories)
Soft PVC side
(Accessories)
Drain hose
Drain pan
10 to 15mm
Hose band
Applying
area of
adhesive
Hard PVC side
Drain pipe (VP25)
(locally purchased)
Joint pipe
(locally purchased)
4 mm or less
Wrap the Drain hose insulation around the drain hose connection.
Drain hose
Drain pan
100mm
Drain hose insulation
(Accessories)
Hose opening view
Wind the attached heat insulation
around the hose band. Make sure the
alignment is on top.
After installing the Drain hose, check if the drainage is smooth.
Downward gradient
2.5 to 5.0mm
GOOD
PROHIBITED
Outlet
air ow
Arrange the drain hose
lower than this portion
Trap Rise
Drain
hose
Air bleeding
Supporter
1.5 to 2.0 m
GOOD GOOD
PROHIBITED
CAUTION
Always check that the drain cap is installed to the unused drain port and is fastened
with the cable tie.
If the drain cap is not installed, or is not suf ciently fastened by the cable tie, water
may drip during the cooling operation.
En-8
6. ELECTRICAL WIRING
6
WARNING
Electrical work must be performed in accordance with this Manual by a person certi ed
under the national or regional regulations. Be sure to use a dedicated circuit for the
unit.
An insuf cient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or re.
Before starting work, check that power is not being supplied to the all units.
For wiring, use the prescribed type of wires, connect them securely, making sure that
there are no external forces of the wires applied to the terminal connections.
Improperly connected or secured wires can cause serious accidents such as
overheating the terminals, electric shock, or re.
Securely install the electrical box cover on the unit.
An improperly installed electrical box cover can cause serious accidents such as
electric shock or re through exposure to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insuf cient insulation, or exceeding the allowable
current can cause electric shock or re.
Do not modify the power cables, use extension cables, or use any branches in the
wiring. Improper connections, insuf cient insulation, or exceeding the allowable current
can cause electric shock or re.
Match the terminal block numbers and connection cable colors with those of the
outdoor unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or re.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric leakage may occur.)
Install an earth leakage breaker. In addition, install the earth leakage breaker so that
the entire AC main power supply is cut off at the same time. Otherwise, electric shock
or re could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cables rmly to the terminal board. Imperfect installation may
cause a re.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly quali ed persons in order to avoid a hazard.
CAUTION
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cables to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of
the PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
Touch metal part of the indoor unit for more than 10 seconds to discharge static electricity
charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.
6.1. Electrical requirement
Voltage rating
230 V
Operating range
198 to 264 V (50 Hz)
198 to 253 V (60 Hz)
• Select the power cable type and size in accordance with relevant local and national
regulations.
• Speci cations for local wiring power cord and branch wiring are in compliance with local
code.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Breaker should be installed at every refrigerant system. Do not use a breaker in a different
refrigerant system.
Refer to the table for the breaker speci cations of each installation condition. Perform
the power crossover wiring within the range of the same refrigerant system. When the
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B
below.
A. Current breaker requirements
Model MCA MFA
ARXA24GBLH 1.00
20 A
ARXA30GBLH 1.12
ARXA36GBLH 1.68
ARXA45GBLH 2.12
MCA: Minimum Circuit Ampacity
MFA: Main Fuse Ampacity
When the power crossover wiring is done, make it so that the total of the MCA of the
connected RB units and indoor units does not exceed the 15 A. For RB unit MCA, refer to
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add
breakers or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Breaker capacity
* Maximum connectable “indoor units” or
“indoor units + RB units”
30 mA, 0.1 sec or less 44 or less
100 mA, 0.1 sec or less
45 to 148 **
* Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
** If the 100 mA capacity breaker is not provided, split the quantity of the indoor units into
small groups of 44 units or less and provide a breaker with capacity of 30 mA for each
group.
6.1.1. Cable speci cations
Follow the speci cations below for the power supply, transmission and remote controller
cable.
Recommended
cable size (mm
2
)
Cable type Remark
Power supply cable 2.5
Type 60245 IEC57
or equivalent
2 Cable + earth
(ground)
Transmission cable 0.33
LONWORKS
compatible cable
22 AWG LEVEL 4
(NEMA)
non-polar 2 core,
twisted pair solid core
diameter 0.65 mm
Remote controller
cable
(2-wire type)
0.33 to 1.25
Sheathed PVC
cable*
Non-polar 2 core,
twisted pair
Remote controller
cable
(3-wire type)
0.33
Sheathed PVC
cable*
Polar 3 core
*: Use shielded cable in accordance with local rules for remote controller cable.
En-9
6.2. Wiring method
Example
Outdoor unit or RB unit *1
Transmission
Transmission
Power supply
Breaker
Power supply Remote controller
(Master)
*1: When connecting to the Heat Recovery System, refer to the installation manual of
the RB unit.
*2: Earth (Ground) the remote controller if it has a earth (ground) cable.
*3: When connecting the 2-wire type remote controller, Y3 is not used.
Remote controller
(Slave)
Remote controller
Breaker Breaker
Indoor unit
Remote
control
*2
*2
*2
*3
*3
*3
Indoor unit Indoor unit
(Crossover wiring of power supply)
Breaker
Indoor unit
Power supply
Pull box
Pull box
Power supply
Power supply Power supply
Indoor unit Indoor unit
* Earth (Ground) the remote controller if it has an earth (ground) wire.
Connect the earth (ground) wire of the remote controller to the earth (ground) terminal of
transmission.
6.3. Unit wiring
Before attaching the cable to terminal block.
6.3.1. Power supply cable
Adjust the length of power supply cable to avoid excessive tension with referring gure
below.
Earth (Ground)
cable
25 mm
30 mm
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after
looping it around the end of the cable.
(2) Use the speci ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not x 2 power supply cables with 1 screw.
Strip 25 mm
Screw with
special washer
Terminal block
Cable end (Loop)
Cable end (Loop)
Loop
Screw with
special washer
Cable
Cable
WARNING
When using solid core cables, do not use the ring terminal. If you use the solid core
cables with the ring terminal, the ring terminal's pressure bonding may malfunction and
cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an
appropriate tool so that the cables do not come loose.
(3) Use the speci ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not x 2 power supply cables with 1 screw.
Strip 10 mm
Ring terminal
Screw with
special washer
Ring terminal
Terminal block
Cable
Screw with
special washer
Sleeve
Ring terminal
Cable
WARNING
Use ring terminals and tighten the terminal screws to the speci ed torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the
unit.
Tightening torque
M4 screw
(Power supply /L, N, GND)
1.2 to 1.8 N·m
(12 to 18 kgf·cm)
6.3.2. Transmission and Remote controller cable
25 mm
35 mm
Shielded cable (no lm)
Transmission cable
Remote controller cable
25 mm
25 mm
For 3-wire type
For 2-wire type
• Connect remote controller and transmission cables as shown in Fig. A.
Fig. A
GOOD PROHIBITED
Different diameter Connect to 1 side
WARNING
Tighten the terminal screws to the speci ed torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
En-10
Tightening torque
M3 screw (Transmission /X1, X2)
(Remote controller /Y1, Y2, Y3)
0.5 to 0.6 N·m
(5 to 6 kgf·cm)
CAUTION
To peel the lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an undertightened screw can cause faulty contact, which
will lead to a communication failure.
6.4. Connection of wiring
(1) Remove the control box cover and install each connection cable.
Screw
Control box cover
(2) After wiring is complete, secure the remote controller cable, connection cable, and
power cable with the cable clamps.
Power supply cable
(locally purchased)
Cable tie (Medium)
(Accessories)
Remote controller
cable, Transmis-
sion cable
(locally purchased)
Cable tie (Medium) (Accessories)
Earth (ground)
Cable clamp
L, N:Power supply cable
X1, X2:
Transmission cable
Y1,Y2,Y3:
Remote controller
cable
CAUTION
When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
Remote controller cable
DIP switch
(SW1)
For 2-wire type For 3-wire type
Connect the remote
controller cable
Y1:Non-polar
Y2:Non-polar
Y3:Do not connect *1
Y1:Red
Y2:White
Y3:Black
Set the DIP switch
(SW1)
2WIRE
(Factory setting)
3WIRE
*1: If you connect the remote controller cable to the terminal
Y3, 2-wire type remote controller does not work.
En-11
6.5. External input and external output (Optional parts)
Controller PCB
Output terminal (CNB01)
Apply voltage terminal
(CNA03)
(CNA01)
Dry contact terminal
(CNA02)
(CNA04)
DIP switch
(SET 2)
OFF ON
SW1
SW2
SW3
SW4
(1) External input
Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
“Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected
with function setting of indoor unit.
Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
Input
device 1
Input
device 2
Input
device 3
Load
resistance
Load
resistance
Load
resistance
*1
DC power supply
12 to 24V
connected unit
*a
*a
*a
P.C.B
CNA01
CNA03
*b
*1
Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power supply
12 to 24V
connected unit
Load
resistance
P.C. B
P.C. B
CNA01
P.C. B
Input
device 1
Input
device 2
Indoor unit
Indoor unit
Indoor unit
Load
resistance
CNA01
CNA01
Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
P.C. B
GND
Ch 1
Ch 3
*c
*c
*c
*d
Ch 2
CNA02
CNA04
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is different from Apply voltage terminals. Be suf ciently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
Power supply for relay
Indoor unit
Indoor unit
Indoor unit
Input device 2
Input device 1
K1 to K6: Relay
(Device for DC Current)
P.C. B
K1
P.C. B
P.C. B
CNA02
K2
K3
K4
K5
K6
CNA02
CNA02
NOTE :
When connected to multiple indoor units directly, it will cause breakdown.
Operation behavior
Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
Pulse
The width of pulse
must be longer than
200msec.
Edge
DIP switch [Set 2 SW2] Input signal type
OFF (Factory setting) Edge
ON Pulse
When function setting is “Operation/Stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of CNA01 or CNA02
OFF ON Operation
ON OFF Stop
En-12
[In the case of “Pulse” input]
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF ON Operation
Ch2 OFF ON Stop
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
When function setting is “Emergency stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of CNA01 or CNA02
OFF ON Emergency stop
ON OFF Normal
[In the case of “Pulse” input]
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF ON Emergency stop
Ch2 OFF ON Normal
* All indoor units of same refrigerant system stops when Emergency stop operates.
When function setting is “Forced stop” mode.
[In the case of “Edge” input]
Connector Input signal Command
Ch1 of CNA01 or CNA02
OFF ON Forced stop
ON OFF Normal
[In the case of “Pulse” input]
Connector Input signal Command
CNA01 or CNA02
Ch1 OFF ON Forced stop
Ch2 OFF ON Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected
with function setting of indoor unit.
Forced thermostat off function
[“Edge” input only]
Connector Input signal Command
Ch3 of CNA03 or CNA04
OFF ON Thermostat off
ON OFF Normal
(2) External output
A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
Output voltage: Hi DC12V±2V, Lo 0V.
Permissible current: 50mA
Output select
When indicator etc. are connected directly
Operation
indicator
Error
indicator
Indoor unit Fan
status indicator
connected unit
P.C. B
CNB
01
When connecting with unit equipped with a power supply
CNB
01
P.C. B
Connected
device 1
Connected
device 2
Connected
device 3
connected unit Relay (locally purchased)
Operation behavior
Connector Output voltage Status
CNB01
External output1
Pins 1-2
0V Stop
DC 12 V Operation
External output2
Pins 1-3
0V Normal
DC 12 V Error
External output3
Pins 1-4
0V Indoor unit fan stop
DC 12 V Indoor unit fan operation
(3) Connection methods
• Wire modi cation
Remove insulation from wire attached to wire kit connector.
Remove insulation from locally purchased cable. Use crimp type insulated butt connector
to join eld cable and wire kit wire.
Connect the wire with connecting wire with solder.
IMPORTANT:
Be sure to insulate the connection between the wires.
Option parts
External input/output wire
Solder and insulate the connected parts.
Locally purchased
• Connection terminals and wiring arrangement
In following gure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
Controller PCB
Clamps Cable tie
(locally purchased)
En-13
6.7. IR receiver unit (Optional parts)
For the installation method, please refer to the INSTALLATION MANUAL of IR receiver
unit.
Connection methods
• Connection terminals
Controller PCB
IR receiver unit
terminal (CN18)
• Wiring arrangement
Controller PCB
Clamps
Cable tie*
(locally purchased)
Core
6.6. Remote sensor (Optional parts)
For the installation method, please refer to the INSTALLATION MANUAL of remote
sensor.
Connection methods
• Connection terminals
Controller PCB
Remote sensor
terminal (CN8)
• Wiring arrangement
Controller PCB
Cable tie
(locally purchased)
Clamps
Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
Use conduit hole when external output cable is used.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
Function Number “30”:
Set the Setting Number to “00”. (Default)
Function Number “31”:
Set the Setting Number to “02”.
* Refer to “7.4. Function setting” for details about Function
Number and Setting Number.
En-14
6.8. Drain pump unit (Optional parts)
For the installation method, please refer to the INSTALLATION MANUAL of drain pump
unit.
Connection methods
• Connection terminals
Drain pump
terminal (CN106)
Front switch
terminal (CNA05)
Power supply PCB Controller PCB
• Wiring arrangement
Controller PCB
Power supply cable
Clamps
Cable clamp
Cable tie*
(Bind with the power supply cable.)
*Accessories of Drain pump unit
Cable tie*
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings..... This section (7.1. Setting the address)
(2) Remote controller settings ....... Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings ...... Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)
CAUTION
• Be sure to turn OFF the power before performing the eld setting.
7.1. Setting the address
Manual address setting method
• If the receiver unit is attached, the indoor unit address and the refrigerant circuit
address can also be set up through the wireless remote controller.
CAUTION
Use an insulated screwdriver to set the DIP switches.
Rotary switch
Example: “0”
Rotary switch
Example: “0”
Setting
Setting
range
Type of switch
Indoor unit address 0 to 63
Setting
example
2
IU AD × 10 IU AD × 1
Refrigerant
circuit
address
0 to 99
Setting
example
63
REF AD × 10
REF AD × 1
(1) Indoor unit address
Rotary switch (IU AD × 1)...Factory setting “0”
Rotary switch (IU AD × 10)...Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1)...Factory setting “0”
Rotary switch (REF AD × 10)...Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
• If working in an environment where the wireless remote controller can be used, the
addresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit
address and refrigerant circuit address to “00”.
(For information on setting using the wireless remote controller.)
Table A
Address
Rotary
Switch Setting
Address
Rotary
Switch Setting
Refrigerant circuit
REF AD SW
Indoor unit
IU AD SW
× 10 × 1 × 10 × 1
000000
101101
202202
303303
404404
505505
606606
707707
808808
909909
10 1 0 10 1 0
11 1 1 11 1 1
12 1 2 12 1 2
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
99 9 9 63 6 3
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
En-15
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting “0”
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting Setting range Type of switch
Remote controller
address
0 to 15
Setting
example
0
RC AD
Example
If 4 indoor units are connected.
RC AD SW
0
RC AD SW
1
RC AD SW
2
RC AD SW
3
Indoor unit
Remote
controller
Indoor unit Indoor unit Indoor unit
RC AD SW
01234567
Address
01234567
RC AD SW
89ABCDEF
Address
8 9 10 11 12 13 14 15
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting “0”
Since the remote controller address settings are automatically con gured, you do
not need to con gure them.
If con guring manually, it is necessary to con gure both the indoor unit and the
remote controller.
For details, please refer to the remote controller manual.
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
DIP switch “SET3”
ON
OFF
SW
1
SW
2
SW
3
SW
4
Table B
Custom code
A (Factory setting) B C D
DIP switch SET3 SW1 OFF ON OFF ON
DIP switch SET3 SW2 OFF OFF ON ON
7.3. Static pressure mode
CAUTION
If the applicable static pressure does not match the static pressure mode, the static
pressure mode may be changed to another mode manually.
It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
Refer to the wired or wireless remote controller manual for detailed setting information.
Function Number Setting Number Setting Static Pressure
26
00 SP mode 00
01 SP mode 01
02 SP mode 02
03 SP mode 03
04 SP mode 04
05 SP mode 05
06 SP mode 06
07 SP mode 07
08 SP mode 08
09 SP mode 09
10 SP mode 10
11 SP mode 11
12 SP mode 12
13 SP mode 13
14 SP mode 14
31 Normal SP (Factory setting)
* Please refer to FAN PERFORMANCE CURVE within Design & Technical Data for the
features of each setting.
* If the Setting Number in AR45 is con gured to "12 to 14", the operation is the same as
that in "11(SP mode 11)".
* If the Setting Number in AR36 is con gured to "13 to 14", the operation is the same as
that in "12 (SP mode 12)".
* If the Setting Number is con gured to be “31” Normal SP (factory setting), the static
pressure is 40Pa(AR24), 50Pa(AR30,AR36), and 60Pa(AR45).
En-16
7.4. Function setting
FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
Refer to the wired or wireless remote controller manual for detailed setting information.
Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping
air tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning
on the power.
Function details
Function
Function
number
Setting number
Default
Details
Filter
indicator
interval
11
00 Standard
Adjust the lter cleaning
interval noti cation. If the
noti cation is too early,
change to setting 01. If the
noti cation is too late, change
to setting 02.
01 Longer
02 Shorter
Filter
indicator
action
13
00 Enable
Enable or disable the lter
indicator. Setting 02 is for
use with a central remote
controller.
01 Disable
02
Display only
on central
remote con-
troller
Cool air
temperature
trigger
30
00 Standard
Adjust the cool air trigger
temperature. To lower the
trigger temperature, use
setting 01. To raise the trigger
temperature, use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00 Standard
Adjust the heat air trigger
temperature. To lower the
trigger temperature by 6
degrees C, use setting 01. To
lower the trigger temperature
by 4 degrees C, use setting
02. To raise the trigger tem-
perature, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart 40
00 Enable
Enable or disable automatic
system restart after a power
outage.
01 Disable
Cool Air
Prevention
43
00 Super low
Restrain the cold air ow
with making the air ow
lower when starting heating
operation. To correspond to
the ventilation, set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00 Start/Stop
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor
unit stops by the input to
the external input terminals,
and Start/Stop by a remote
controller is restricted.
01
Emergency
stop
02 Forced stop
Error report
target
47
00 All
Change the target for report-
ing errors. Errors can either
be reported in all locations,
or only on the central remote
controller.
01
Display only
on central
remote
controller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
When set to 01, the fan stops
when the thermostat is OFF
in cooling operation. Con-
nection of the wired remote
controller (2-wire type or
3-wire type) and switching its
thermistor are necessary.
01 Stop
(Forbidden) 60 00
(Forbidden) 61 00
(Forbidden) 62 00
8. TEST RUN
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using Remote Controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
ash slowly at the same time.
For details, please refer to the Manual of “IR Receiver Unit” or “Wired Remote Controller”.
9. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS If not performed correctly
CHECK
BOX
Has the indoor unit been installed
correctly?
Vibration, noise,
indoor unit may drop
Has there been a check for gas leaks
(refrigerant pipes)?
No cooling, No heating
Has heat insulation work been
completed?
Water leakage
Does water drain easily from the indoor
units?
Water leakage
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
No operation, heat or burn
damage
Are the wires and pipes all connected
completely?
No operation, heat or burn
damage
Is the indoor unit earthed (grounded)? Short circuit
Is the connection cable the specified
thickness?
No operation, heat or burn
damage
Are the inlets and outlets free of any
obstacles?
No cooling, No heating
Does start and stop air conditioner
operation by remote controller
or external device?
No operation
After installation is completed, has the
proper operation and handling been
explained to the user?
En-17
10. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote control-
ler display. If you use a wireless remote controller, the lamp on the photodetector unit
will output error codes by way of blinking patterns. See the lamp blinking patterns and
error codes in the table below.
Error indications
Wired Remote
Controller Error
code
Error contents
OPERATION
lamp (green)
TIMER lamp
(orange)
FILTER lamp
(red)
(1) (2)
Remote controller
communication error
(1) (4)
Network communication
error
(1) (6)
Peripheral unit
communication error
(2) (6)
Indoor unit address
setting error
(2) (9)
Connection unit number
error in wired remote
controller system
(3) (1)
Indoor unit power supply
abnormal
(3) (2)
Indoor unit main PCB
error
(3) (10)
Indoor unit
communication circuit
(wired remote controller)
error
(4) (1)
Indoor unit room temp.
thermistor error
(4) (2)
Indoor unit heat ex.
temp. thermistor error
(5) (1)
Indoor unit fan motor 1
error
(5) (2)
Indoor unit coil
(expansion valve) error
(5) (3)
Indoor unit water drain
abnormal
(9) (15)
Outdoor unit
miscellaneous error
(13) (1) RB unit error
Display mode
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of ashing
Wired remote controller display
UTY-RNK* / UTY-RNKYT (3-wire type)
UTY-RNR*Z* (2-wire type)
Error code
Error icon
Touch the [Status].
Touch the [Error Information].
2-digit numbers are corresponding to
the error code in the preceding table.
For more information, refer to the installation manual of the remote controller.
Touch the [Next Page] (or [previous page])
to switch to other indoor unit information.
UTY-RLR* (2-wire type)
Error code
Error icon
For more information, refer to the installation manual of the remote controller.
For details on marking the ERROR CODES, please refer to the Manual of “IR Receiver
Unit” or “Wired Remote Controller”.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Fujitsu ARXA30GBLH Installation guide

Category
Split-system air conditioners
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI