Fujitsu ARTG65LHTA Installation guide

Category
Split-system air conditioners
Type
Installation guide
En-1
1. SAFETY PRECAUTIONS
•Besuretoreadthismanualthoroughlybeforeinstallation.
•Thewarningsandprecautionsindicatedinthismanualcontainimportantinformation
pertainingtoyoursafety.Besuretoobservethem.
•Handthismanual,togetherwiththeoperationmanual,tothecustomer.Requestthe
customertokeepthemonhandforfutureuse,suchasforrelocatingorrepairingtheunit.
WARNING
Indicatesapotentiallyorimminentlyhazardoussituationwhich,
ifnotavoided,couldresultindeathorseriousinjury.
Installationofthisproductmustbedonebyexperiencedservicetechniciansorprofes-
sionalinstallersonlyinaccordancewiththismanual.Installationbynonprofessionalor
improperinstallationoftheproductmaycauseseriousaccidentssuchasinjury,water
leakage,electricshock,orre.Iftheproductisinstalledindisregardoftheinstructions
inthismanual,itwillvoidthemanufacturer’swarranty.
Donotturnonthepoweruntilallworkhasbeencompleted.Turningonthepower
beforetheworkiscompletedcancauseseriousaccidentssuchaselectricshockor
re.
Toavoidgettinganelectricshock,nevertouchtheelectricalcomponentssoonafter
thepowersupplyhasbeenturnedo.Afterturningothepower,alwayswait
10minutesormorebeforeyoutouchtheelectricalcomponents.
Ifrefrigerantleakswhenyouareworking,ventilatethearea.Iftheleakingrefrigerant
isexposedtoadirectameitmayproduceatoxicgas.
Donotusethisequipmentwithairoranyotherunspeciedrefrigerantintherefriger-
antlines.Excesspressurecancausearupture.
Installationmustbeperformedinaccordancewithregulations,codes,orstandardsfor
electricalwiringandequipmentineachcountry,region,ortheinstallationplace.
Thisapplianceisnotintendedforusebypersons(includingchildren)withreduced
physical,sensoryormentalcapabilities,orlackofexperienceandknowledge,unless
theyhavebeengivensupervisionorinstructionconcerninguseoftheappliancebya
personresponsiblefortheirsafety.Childrenshouldbesupervisedtoensurethatthey
donotplaywiththeappliance.
Toavoiddangerofsuocation,keeptheplasticbagorthinlmusedasthepackaging
materialawayfromyoungchildren.
CAUTION
Indicatesapotentiallyhazardoussituationthatmayresultin
minorormoderateinjuryordamagetoproperty.
Readcarefullyallsafetyinformationwritteninthismanualbeforeyouinstallorusethe
airconditioner.
Installtheproductbyfollowinglocalcodesandregulationsinforceattheplaceof
installation,andtheinstructionsprovidedbythemanufacturer.
Thisproductispartofasetconstitutinganairconditioner.Theproductmustnotbe
installedaloneorbeinstalledwithnon-authorizeddevicebythemanufacturer.
Alwaysuseaseparatepowersupplylineprotectedbyacircuitbreakeroperatingon
allwireswithadistancebetweencontactof3mmforthisproduct.
Toprotectthepersons,earth(ground)theproductcorrectly,andusethepowercable
combinedwithanEarthLeakageCircuitBreaker(ELCB).
Theproductisnotexplosionproof,andthereforeshouldnotbeinstalledinexplosive
atmosphere.
Donottouchthensoftheheatexchanger.Touchingtheheatexchangernscould
resultindamagetothensorpersonalinjurysuchasskinrupture.
Thisproductcontainsnouser-serviceableparts.Alwaysconsultexperiencedservice
techniciansforrepairing.
Whenmovingorrelocatingtheairconditioner,consultexperiencedservicetechni-
ciansfordisconnectionandreinstallationoftheproduct.
Donotplaceanyotherelectricalproductsorhouseholdbelongingsundertheproduct.
Condensationdrippingfromtheproductmightgetthemwet,andmaycausedamage
ormalfunctionoftheproperty.
PARTNo.9381386260-02
Forauthorizedservicepersonnelonly.
AIR CONDITIONER
Indoor Unit (Duct type)
INSTALLATION MANUAL
NOTE: Thismanualdescribeshowtoinstalltheairconditionerdescribedabove.Handling
andinstallationshallonlybedonebyprofessionalsasoutlinedinthismanual.
1. SAFETYPRECAUTIONS.................................................................................1
2. PRODUCTSPECIFICATION............................................................................2
2.1. PrecautionsforusingR410Arefrigerant ………………………………… 2
2.2. Installationtools …………………………………………………………… 2
2.3. Accessories ………………………………………………………………… 2
2.4. Selectingthepipematerial………………………………………………… 2
2.5. Piperequirement…………………………………………………………… 3
2.6. Electricalrequirement……………………………………………………… 3
2.7. Optionalparts ……………………………………………………………… 3
3. INSTALLATIONWORK....................................................................................3
3.1. Selectinganinstallationlocation ………………………………………… 3
3.2. Installationdimension……………………………………………………… 4
3.3. Installingtheunit …………………………………………………………… 4
3.4. Installingthedrainhose…………………………………………………… 5
3.5. Freshairintake……………………………………………………………… 6
4. PIPEINSTALLATION.......................................................................................7
4.1. Pipeconnection …………………………………………………………… 7
4.2. Installingheatinsulation…………………………………………………… 7
5. ELECTRICALWIRING.....................................................................................8
5.1. Wiringmethod ……………………………………………………………… 8
6. REMOTECONTROLLERSETTING................................................................9
7. FUNCTIONSETTING......................................................................................9
7.1. Functiondetails …………………………………………………………… 9
7.2. Staticpressure……………………………………………………………… 11
8. GROUPCONTROL........................................................................................ 11
8.1. Groupcontrolsystem ……………………………………………………… 11
8.2. Multipleremotecontrol ……………………………………………………12
9. OPTIONALPARTS.........................................................................................12
9.1. Optionalparts ……………………………………………………………… 12
9.2. Externalinputandoutput …………………………………………………12
9.3. Remotesensor ……………………………………………………………13
9.4. Installationdetails……………………………………………………………13
9.5. Fandelaysetting……………………………………………………………13
9.6. Wiringconnection …………………………………………………………13
10. CHECKLIST..................................................................................................14
11. TESTRUN.....................................................................................................14
12. CUSTOMERGUIDANCE...............................................................................14
13. ERRORCODES.............................................................................................14
9381386260-02_IM.indd 1 27-Oct-20 09:01:38
En-2
2. PRODUCT SPECIFICATION
2. 1. Precautions for using R410A refrigerant
WARNING
Donotintroduceanysubstanceotherthantheprescribedrefrigerantintotherefrigera-
tioncycle.Ifairenterstherefrigerationcycle,thepressureintherefrigerationcycle
willbecomeabnormallyhighandcausethepipingtorupture.
Ifthereisarefrigerantleak,makesurethatitdoesnotexceedtheconcentrationlimit.
Ifarefrigerantleakexceedstheconcentrationlimit,itcanleadtoaccidentssuchas
oxygenstarvation.
Donottouchrefrigerantthathasleakedfromtherefrigerantpipeconnectionsorother
area.Touchingtherefrigerantdirectlycancausefrostbite.
Ifarefrigerantleakoccursduringoperation,immediatelyvacatethepremisesand
thoroughlyventilatethearea.Iftherefrigerantcomesincontactwithaame,itpro-
ducesatoxicgas.
2. 2. Installation tools
WARNING
ToinstallaunitthatusesR410Arefrigerant,usededicatedtoolsandpipingmateri-
alsthathavebeenmanufacturedspecicallyforR410Ause.Becausethepressure
ofR410Arefrigerantisapproximately1.6timeshigherthantheR22,failuretouse
dedicatedpipingmaterialorimproperinstallationcancauseruptureorinjury.
Furthermore,itcancauseseriousaccidentssuchaswaterleakage,electricshock,orre.
Tool name Changes
Gauge manifold
Thepressureintherefrigerantsystemisextremelyhigh
andcannotbemeasuredwithaconventionalgauge.
Topreventerroneousmixingofotherrefrigerants,
thediameterofeachporthasbeenchanged.Itis
recommendedtouseagaugemanifoldwithahigh
pressuredisplayrangeof–0.1to5.3MPaandalow
pressuredisplayrangeof–0.1to3.8MPa.
Charging hose
Toincreasepressureresistance,thehosematerialand
basesizewerechanged.(Thechargingportthread
diameterforR410Ais1/2-20UNF.)
Vacuum pump
Aconventionalvacuumpumpcanbeusedbyinstallinga
vacuumpumpadapter.
Besurethatthepumpoildoesnotbackowintothe
system.Useonecapableforvacuumsuctionof
–100.7kPa(5Torr,–755mmHg).
Gas leakage detector SpecialgasleakagedetectorforR410Arefrigerant.
2. 3. Accessories
WARNING
Forinstallationpurposes,besuretousethepartssuppliedbythemanufactureror
otherprescribedparts.Theuseofnon-prescribedpartscancauseseriousaccidents
suchastheunitfalling,waterleakage,electricshock,orre.
•Thefollowinginstallationpartsarefurnished.Usethemasrequired.
•KeeptheInstallationManualinasafeplaceanddonotdiscardanyotheraccessories
untiltheinstallationworkhasbeencompleted.
Name and Shape Q’ty Description
OperationManual
1
InstallationManual
(indoorunit)
1 (Thisbook)
InstallationManual
(remotecontroller)
1
Name and Shape Q’ty Description
SpecialnutA
(largeange)
4
Forsuspendingtheindoorunit
fromceiling
SpecialnutB
(smallange)
4
Washer
8
Couplerheatinsulation(large)
1
Forindoorsidepipejoint
(gaspipe)
Couplerheatinsulation(small)
1
Forindoorsidepipejoint
(liquidpipe)
Cabletie(large)
4 Forxingtheheatinsulation
Cabletie(medium)
1
Forxingtheremotecontroller
cable
Cabletie(small)
1
Forxingtheremotecontroller
cable
Remotecontroller
(WDDtype)
1 Forairconditioneroperation
Remotecontrolleraccessories
1set
Seeinstallationmanualfor
remotecontroller
Drainhoseinsulation
1
Insulatesthedrainhoseand
vinylhose
Drainhose
1
Forinstallingdrainpipe
VP25(O.D.32,I.D.25)
Hoseband
1 Forinstallingdrainhose
2. 4. Selecting the pipe material
CAUTION
Donotuseexistingpipes.
Usepipesthathavecleanexternalandinternalsideswithoutanycontaminationwhich
maycausetroubleduringuse,suchassulfur,oxide,dust,cuttingwaste,oil,orwater.
Itisnecessarytouseseamlesscopperpipes.
Material:Phosphordeoxidizedseamlesscopperpipes
Itisdesirablethattheamountofresidualoilislessthan40mg/10m.
Donotusecopperpipesthathaveacollapsed,deformed,ordiscoloredportion(es-
peciallyontheinteriorsurface).Otherwise,theexpansionvalveorcapillarytubemay
becomeblockedwithcontaminants.
Improperpipeselectionwilldegradeperformance.AsanairconditionerusingR410Ain-
curspressurehigherthanwhenusingconventionalrefrigerant,itisnecessarytochoose
adequatematerials.
•ThicknessesofcopperpipesusedwithR410Aareasshowninthetable.
•Neverusecopperpipesthinnerthanthoseindicatedinthetableeveniftheyareavailable
onthemarket.
Pipe outside diameter [mm (in.)] Thickness [mm]
6.35(1/4) 0.8
9.52(3/8) 0.8
12.70(1/2) 0.8
15.88(5/8) 1.0
19.05(3/4) 1.2
22.22(7/8) 1.0
25.40(1) 1.0
9381386260-02_IM.indd 2 27-Oct-20 09:01:40
En-3
2. 7. Optional parts
Parts name Model No. Summary
WiredRemoteController UTY-RNRYZ3
Forairconditioneroperation
(2-wiretype)
WiredRemoteController
UTY-RNNYN
UTY-RVNYN
Forairconditioneroperation
(3-wiretype)
SimpleRemoteController
UTY-RSRY
Forairconditioneroperation
(2-wiretype)
UTY-RSNYN
Forairconditioneroperation
(3-wiretype)
IRreceiverunit UTY-LBTYM Forairconditioneroperation
Zonecontrolinterface
UTY-CDPXZC
Usetocontrolindividualairow
toeachzone
UTY-CDPXZD
Remotesensor UTY-XSZX Roomtemperaturesensor
Externalinputandoutput
PCB
UTY-XCSX
Forconnectingexternal
devices
Externalconnectkit UTY-XWZXZG Forcontroloutputport
Airlterkit UTD-LFKA
Drainpumpkit UTZ-PX1NAB
Separationkitforduct UTD-TJKA Toaccommodaterooftrusses
3. INSTALLATION WORK
WARNING
Donotturnonthepoweruntilallinstallationworkiscomplete.
Carryingandinstallationoftheunitshouldbeperformedbyasucientnumberof
peopleandwithsucientequipmentthatisadequatefortheweightoftheunit.
Performingsuchworkwithaninsucientnumberofpeopleorwithinadequate
equipmentcouldresultindroppingoftheunitorpersonalinjury.
CAUTION
Forinstallationdetails,refertothetechnicaldata.
3. 1. Selecting an installation location
Decidethemountingpositiontogetherwiththecustomerasfollows.
WARNING
Selectinstallationlocationsthatcanproperlysupporttheweightoftheindoorunit
andwhichwillnotamplifysoundorvibration.Iftheinstallationlocationisnotstrong
enough,theindoorunitmayfallandcauseinjuries.
Installtheunitssecurelysothattheydonottoppleorfall.
CAUTION
Donotinstalltheindoorunitinthefollowingareas:
• Areawithhighsaltcontent,suchasattheseaside.
Itwilldeterioratemetalparts,causingthepartstofallortheunittoleakwater.
• Arealledwithmineraloilorcontainingalargeamountofsplashedoilorsteam,
suchasakitchen.
Itwilldeteriorateplasticparts,causingthepartstofallortheunittoleakwater.
• Areathatgeneratessubstancesthatadverselyaecttheequipment,suchassulfuric
gas,chlorinegas,acid,oralkali.Itwillcausethecopperpipesandbrazedjointsto
corrode,whichcancauserefrigerantleakage.
• Areathatcancausecombustiblegastoleak,containssuspendedcarbonbersor
ammabledust,orvolatileinammablessuchaspaintthinnerorgasoline.Ifgas
leaksandsettlesaroundtheunit,itcancauseare.
• Areawhereanimalsmayurinateontheunitorammoniamaybegenerated.
Donotusetheunitforspecialpurposes,suchasstoringfood,raisinganimals,growing
plants,orpreservingprecisiondevicesorartobjects.Itcandegradethequalityofthe
preservedorstoredobjects.
Donotinstallwherethereisthedangerofcombustiblegasleakage.
Donotinstalltheunitnearasourceofheat,steam,orammablegas.
Installtheunitwheredrainagedoesnotcauseanytrouble.
Installtheindoorunit,outdoorunit,powersupplycable,transmissioncable,andremote
controlcableatleast1mawayfromatelevisionorradioreceivers.Thepurposeofthis
istopreventTVreceptioninterferenceorradionoise.
(Eveniftheyareinstalledmorethan1mapart,youcouldstillreceivenoiseunder
somesignalconditions.)
Installtheunitwhereambienttemperaturedoesnotreach60°Cormore.
Takeameasuresuchasventilationforanenvironmentinwhichheatisretained.
Ifchildrenunder10yearsoldmayapproachtheunit,takepreventivemeasuressothat
theycannotreachtheunit.
2. 5. Pipe requirement
CAUTION
Refertotheinstallationmanualoftheoutdoorunitfordescriptionofthelengthofcon-
nectingpipeorfordierenceofitselevation.
Diameter [mm (in.)]
Liquid
12.70(1/2)
Gas
25.40(1)
• Usepipewithwater-resistantheatinsulation.
CAUTION
•Wrapheatinsulationaroundbothgaspipeandliquidpipe.
Noheat-insulationworkorincorrectheat-insulationworkmaycausewaterleaks.
•Inareversecyclemodel,useheatinsulationwithheatresistanceabove120°C.
•Ifexpectedhumidityoftheinstallationlocationofrefrigerantpipesishigherthan
70%,wraptheheatinsulationaroundtherefrigerantpipes.
Iftheexpectedhumidityisbetween70%and80%,useheatinsulationthathas
athicknessof15mmormore.
Iftheexpectedhumidityishigherthan80%,useheatinsulationthathasa
thicknessof20mmormore.
•Theuseofthinnerheatinsulationthanspeciedabove,maycauseacondensation
onthesurfaceoftheinsulation.
•Useheatinsulationwiththermalconductivityof0.045W/(
m•K
)orless,at20
°C
.
2. 6. Electrical requirement
2. 6. 1. Cable specication
WARNING
Standardforelectricalwiringandequipmentdiersineachcountryorregion.Beforeyou
startelectricalworking,conrmrelatedregulations,codes,orstandards.
Cable
Conductor size
(mm
2
)
Type
Remarks
Connectioncable 1.5(MIN.) Type60245IEC57
3Wire+Earth(Ground),
1φ240V
Powersupplycable
1.5(MIN.) Type60245IEC57
2Wire+Earth(Ground),
1φ240V
Max.CableLength:Limitvoltagedroptolessthan2%.Increasecablegaugeifvoltage
dropis2%ormore.
Cable
Conductor size
(mm
2
)
Type
Remarks
Remotecontroller
cable
(2-wiretype)
0.33to1.25
Non-polar2core,
twistedpair
Useshieldedcable(locally
purchased)inaccordance
withtheregionalcable
standard.
Remotecontroller
cable
(3-wiretype)
0.33 Polar3core
2. 6. 2. Circuit breaker specication
CAUTION
Besuretoinstallabreakerofthespeciedcapacity.
Regulationforbreakersdiersfromeachlocality,referinaccordancewithlocalrules.
Breaker capacity
[A]
Earth leakage breaker
[mA]
10 30
•Selecttheappropriatebreakerofthedescribedspecicationaccordingtothenationalor
regionalstandards.
•Selectthebreakerthatenoughloadcurrentcanpassthroughit.
•Beforestartingworkcheckthatpowerisnotbeingsuppliedtoallpolesoftheindoorunit
andoutdoorunit.
•Installallelectricalworksinaccordancetostandard.
•Installthedisconnectdevicewithacontactgapofatleast3mminallpolesnearbythe
units.(Bothindoorunitandoutdoorunit)
9381386260-02_IM.indd 3 27-Oct-20 09:01:40
En-4
(1) Theinletandoutletportsshouldnotbeobstructed;theairshouldbeabletoblowall
overtheroom.
(2) Leavethespacerequiredtoservicetheairconditioner.
(3) Installtheunitwhereconnectiontotheoutdoorunitiseasy.
(4) Installtheunitwheretheconnectionpipecanbeeasilyinstalled.
(5) Installtheunitwherethedrainpipecanbeeasilyinstalled.
(6) Installtheunitwherenoiseandvibrationsarenotamplied.
(7) Takeservicing,etc.,intoconsiderationandleavethespaces.Alsoinstalltheunitwhere
theltercanberemoved.
(8) Donotinstalltheunitwhereitwillbeexposedtodirectsunlight.
Correctinitialinstallationlocationisimportantbecauseitisdiculttomoveunitafteritis
installed.
3. 2. Installation dimension
Installation by which service space is made on top of the unit
(recommended)
Ifmaintenanceworkistobedonefromthetop,keepthespaceofthemorethan
450mmbetweentheindoorunitandceiling.
(Front view)
Unit: mm
20ormore
450ormore
2500ormore
(Whennoceiling)
500ormore
150or
more
(Bottom view) Unit: mm
Serviceaccess
700ormore
700ormore
500ormore
Controlbox
AIR
Installation by which service is carried out from the bottom of the unit
(Front view)
Unit: mm
2500ormore
(Whennoceiling)
150or
more
20ormore
20ormore
500ormore
Provideaserviceaccessformaintenancepurposes.
(1) Maintenanceworkofthecontrolboxispossiblewiththeserviceaccessofthe
measurementshowninthegure.
(2) Ifmaintenanceworkistobedonefromthebottomside,theserviceaccessneedsto
belargerthantheoutsidedimensionofthefanunit.
(Bottom view) Unit: mm
600ormore
100
500ormore
Fanunitside
AIR
Serviceaccess
2000ormore
3. 3. Installing the unit
WARNING
Carryingandinstallationoftheunitshouldbeperformedbyasucientnumber
ofpeopleandwithsucientequipmentthatisadequatefortheweightoftheunit.
Performingsuchworkwithaninsucientnumberofpeopleorwithinadequate
equipmentcouldresultindroppingoftheunitorpersonalinjury.
Ifthejobisdonewiththepanelframeonly,thereisariskthattheunitwillcomeloose.
Pleasetakecare.
Whenfasteningthehangers,maketheboltpositionsuniform.
CAUTION
Conrmthedirectionsoftheairintakeandoutletbeforeinstallingtheunit.
3. 3. 1. Instructions
Unpacking
•Leavethepackingmaterialsonuntiltheunitisattheinstallationsite.
•Removethepackinghardwareanddisposeofit.
•Becarefulnottodisposetheaccessories.
Unitispackedupsidedown.
Separating the unit for installation
Youcanseparatetheheatexchangerunitandfanunitforinstallation.
Refertothe“SEPARATIONMETHOD”labelattachedtotheindoorunitfordetails.
CAUTION
Donotinstallthepairedunits(heatexchangerunitandfanunit)inseparatelocations.
Itmaycausemalfunctionoftheproductorwaterleakage.
Connectionc
9381386260-02_IM.indd 4 27-Oct-20 09:01:41
En-5
3. 3. 2. Hanging bolt installation diagram
(Top side) Unit: mm
Inletport
Outletport
AIR
1500
1440
1400
780
900
850
(Right side) Unit: mm
277
282
316
26
22
22
57
HangingboltM10
(Locallypurchased)
SpecialnutA
(Accessories)
Washer
(Accessories)
Hanger
SpecialnutB
(Accessories)
Bolt Strength 9.81to14.71N·m(100to150kgf·cm)
CAUTION
FastentheunitsecurelywithspecialnutsAandBsothattheunitdoesnotfall.
3. 3. 3. Leveling
Baseverticaldirectionlevelingontheunit(rightandleft).
(Right side)
Level
AIR
AIR
Basehorizontaldirectionlevelingontopoftheunit.
Drainhose
0–5mm
Level
Giveaslighttilttothesidetowhichthedrainhoseisconnected.Thetiltshouldbeinthe
rangeof0mmto5mm.
3. 4. Installing the drain hose
CAUTION
Installthedrainhoseinaccordancewiththeinstructionsinthisinstallationmanualand
keeptheareawarmenoughtopreventcondensation.Problemswiththepipingmay
leadtowaterleaks.
Besuretoproperlyinsulatethedrainhosesothatthewaterwillnotdripfromthe
connectedparts.
Thepositionoftheinstalleddrainhoseshouldhaveadownwardgradientof1/100or
more.
Donotconnectthedrainhoseinwhichammoniaorothertypesofgasaectingthe
unitisgenerated.Heatexchangeerosionmayoccur.
Installthedrainhoseaccordingtothemeasurementsgiveninthefollowinggure.
(Right side) Unit: mm
Drainpipe
Φ32mm(O.D.)
29
145
65
300
40
280
3. 4. 1. How to install the drain hose
(1) Installthedrainhose(accessories)tothedrainportoftheindoorunit.Attachthehose
bandaroundthehosewithinthedimensionshown.Securermlywiththehoseband.
(2) Attachthedrainpipe(locallypurchased).Usegeneralhardpolyvinylchloridepipe
(VP25)[outsidediameter38mm]andconnectitwithadhesive(polyvinylchloride)so
thatthereisnoleakage.
(3) Checkthedrainage.
(4) Wrapthedrainhoseinsulationaroundthedrainhoseconnection.
Hoseband(Accessories)
SoftPVCside
Areato
apply
adhesive
Jointpipe
(Locallypurchased)
Drainpipe(VP25)
(Locallypurchased)
5~10mm
20mm
Drainhose
(Accessories)
4mmorless
15mm
Indoorunit
Drainhose
100mm
Drainhoseinsulation
(Accessories)
Hoseband(Accessories)
Overlaptheheatinsulation.
Drainhoseinsulation
(Accessories)
9381386260-02_IM.indd 5 27-Oct-20 09:01:43
En-6
3. 4. 2. When drain pump is used (Option is necessary)
Gapof1.5to2m
700mmorless
Horizontalor
upwardgradient
Supporter
Max.300mm
Locallyarrangedpipe
GOOD
VP25[O.D
32mmormore]
Rise
Airbleeding
PROHIBITED
Trap
Observe the following procedures to construct centralized drain pipe ttings.
VP30ormore[O.D38mmormore]
Downwardgradient1/100ormore
700mmorless
NOTES:
• Installthedrainpipewithdownwardgradient(1/50to1/100)andsotherearenorisesor
trapsinthepipe.
Drain
pipe
Outlet
airow
Arrangethedrainpipe
lowerthanthisportion
GOOD
Trap
Rise
PROHIBITED
• Whenthepipeislong,installsupporters.
Supporter
1.5to2m
• Donotperformairbleeding.
Airbleeding
CAUTION
Makesurethedrainwaterisproperlydrained.
Topreventpeoplefromtouchingthepartsinsidetheunit,besuretoinstallgrilleson
theinletandoutletports.Thegrillesmustbedesignedinsuchawaythatcannotbe
removedwithouttools.
Settheappropriateexternalstaticpressurewithinthepermissiblerange.(Referto
“7.FUNCTIONSETTING”)
Ifanintakeductisinstalled,takecarenottodamagethetemperaturesensor(the
temperaturesensorisattachedtotheintakeportange).
CAUTION
BesuretoInstalltheairinletgrilleandairoutletgrilleforaircirculation.Thecorrect
temperaturecannotbedetected.
Unit
AirOutletGrille
(Locallypurchased)
AirInletGrille
(Locallypurchased)
(Room)
Duct
(Locallypurchased)
Whenconnectingtheduct,performduct-insulationappropriatefortheinstalling
environment.
Inappropriateinsulationworkmaycausecondensationonthesurfaceoftheinsulating
material,andmayleadtocondensationdripping.
3. 5. Fresh air intake
(Processing before use)
(1) Whentakinginfreshair,cutouttheslitofthecabinetontheleftsideoftheoutercase
withnippers.
Slit
Cabinet(ironplate)
CAUTION
Whenremovingthecabinet(ironplate),becarefulnottodamagetheindoorunit
internalpartsandsurroundingarea(outercase).
Whenprocessingthecabinet(ironplate),becarefulnottoinjureyourselfwithburrs,
etc.
(2) Installtheroundangetothefreshairintake.
Roundange(Locallypurchased)
(3) Connecttheducttotheroundange.
(4) Sealwithabandandvinyltape,etc.sothatairdoesnotleakfromtheconnection.
Duct
9381386260-02_IM.indd 6 27-Oct-20 09:01:44
En-7
4. PIPE INSTALLATION
WARNING
Duringinstallation,makesurethattherefrigerantpipeisattachedrmlybeforeyou
runthecompressor.
Donotoperatethecompressorundertheconditionofrefrigerantpipingnotattached
properlywith2-wayor3-wayvalveopen.Thismaycauseabnormalpressureinthe
refrigerationcyclethatleadstobreakageandeveninjury.
Duringthepump-downoperation,makesurethatthecompressoristurnedobefore
youremovetherefrigerantpiping.
Donotremovetheconnectionpipewhilethecompressorisinoperationwith2-wayor
3-wayvalveopen.Thismaycauseabnormalpressureintherefrigerationcyclethat
leadstobreakageandeveninjury.
Wheninstallingandrelocatingtheairconditioner,donotmixgasesotherthanthe
speciedrefrigerant(R410A)toentertherefrigerantcycle.
Ifairorothergasenterstherefrigerantcycle,thepressureinsidethecyclewillriseto
anabnormallyhighvalueandcausebreakage,injury,etc.
Ifrefrigerantleakswhileworkisbeingcarriedout,ventilatethearea.Iftherefrigerant
comesincontactwithaame,itproducesatoxicgas.
CAUTION
Bemorecarefulsothatforeignmatter(oil,water,etc.)doesnotenterthepiping
thanwithrefrigerantR410Amodels.Also,whenstoringthepiping,securelysealthe
openingsbypinching,taping,etc.
Whilebrazingthepipes,besuretoblowdrynitrogengasthroughthem.
4. 1. Pipe connection
4. 1. 1. Brazing
CAUTION
Ifairoranothertypeofrefrigerantenterstherefrigerationcycle,theinternalpressure
intherefrigerationcyclewillbecomeabnormallyhighandpreventtheunitfrom
exertingitsfullperformance.
Applynitrogengaswhilebrazingthepipes.Nitrogengaspressure:0.02MPa
(=pressurefeltsucientlyonthebackofyourhand)
Cap
Pressureregulatingvalve
Nitrogengas
Brazingarea
Ifapipeisbrazedwithoutapplyingnitrogengas,itwillcreateanoxidationlm.This
candegradeperformanceordamagethepartsintheunit(suchasthecompressoror
valves).
Donotuseuxtobrazepipes.Iftheuxisthechlorinetype,itwillcausethepipes
tocorrode.Inaddition,iftheuxcontainsuoride,itwillaecttherefrigerantpiping
systemduetodeteriorationofrefrigerantoil.
Forbrazingmaterial,usephosphorcopperthatdoesnotrequireux.
Connecting pipes
• Thegasandliquidpipesconnectionsmustbebrazed.
• Besuretobrazethembeforeperforminganywiringworkorinstallingthedrainpipe.
Pinchpipe
Gaspipe
Liquidpipe
Rubber
cap
WARNING
Besuretousewetcloth,etc.,toprotectthepiperubber,pipeheatinsulation,and
theheatinsulationofthesafetydrainpanasshownbelow.Becausethesepartsare
extremelyammable,theycancauseareiftheyarenotproperlyprotected.
Donotexposethethermistorinstalledintheheatexchangertotheame.
Failuretodosocouldresultintrouble.
Donotexposetheunit(controlbox,rearpanel,maintenancepanel,etc.)andtheinlet
grilletotheame.
Theexposureofthesepartstotheamewilladverselyaecttheirappearanceand
functionsorcauseare.
Connection
pipes
Protectthese
areaswithwet
cloth,etc.
Liquidpipe
Completelycover
thepiperubberand
pipeheatinsulationwith
wetcloth,etc.,toprevent
themfromburning.
Gaspipe
CAUTION
Meltthebrazingltermetalonconnectingpartusingaburnerandremovethepinch
pipe.
Removethepinchpipeonlyafterprotectingitfromame.
Removetherubbercapandpinchpipeimmediatelybeforetheconnection.
4. 1. 2. Bending pipes
•Ifpipesareshapedbyhand,becarefulnottocollapsethem.
•Donotbendthepipesinananglemorethan90°.
•Whenpipesarerepeatedlybendorstretched,thematerialwillharden,makingitdicult
tobendorstretchthemanymore.
•Donotbendorstretchthepipesmorethan3times.
CAUTION
Topreventbreakingofthepipe,avoidsharpbends.Bendthepipewitharadiusof
curvatureof150mmorover.
Ifthepipeisbentrepeatedlyatthesameplace,itwillbreak.
4. 2. Installing heat insulation
Installtheheatinsulationmaterialafterperformingarefrigerantleakcheck(seethe
installationmanualfortheoutdoorunitfordetails).
4. 2. 1. Coupler heat insulation
Nogaps
Indoorunitside
Cableties(large)
(Accessories)
Pipes
(Gasandliquidpipes)
Couplerheatinsulation
(Accessories)
Besuretooverlap
theinsulation.
CAUTION
Thereshouldbenogapsbetweentheinsulationandtheproduct.
CAUTION
Afterconnectingthepiping,checkthealljointsforgasleakagewithgasleakdetector.
Oncethepressurecheckinghasbeencompletedusingnitrogen,pleaserefertothe
outdoorunitinstallationmanualtocompletetheevacuationprocess.
Installheatinsulationaroundboththelarge(gas)andsmall(liquid)pipes.Failureto
dosomaycausewaterleaks.
9381386260-02_IM.indd 7 27-Oct-20 09:01:45
En-8
5. ELECTRICAL WIRING
WARNING
ElectricalworkmustbeperformedinaccordancewiththisManualbyaperson
certiedunderthenationalorregionalregulations.Besuretouseadedicatedcircuit
fortheunit.
Aninsucientpowersupplycircuitorimproperlyperformedelectricalworkcancause
seriousaccidentssuchaselectricshockorre.
Beforestartingwork,checkthatpowerisnotbeingsuppliedtotheindoorunitand
outdoorunit.
Toavoidgettinganelectricshock,nevertouchtheelectricalcomponentssoonafter
thepowersupplyhasbeenturnedo.Afterturningothepower,alwayswait
10minutesormorebeforeyoutouchtheelectricalcomponents.
Usetheincludedconnectioncablesandpowercablesoronesspeciedbythe
manufacturer.Improperconnections,insucientinsulation,orexceedingtheallowable
currentcancauseelectricshockorre.
Forwiring,usetheprescribedtypeofcables,connectthemsecurely,makingsure
thattherearenoexternalforcesofthecablesappliedtotheterminalconnections.
Improperlyconnectedorsecuredcablescancauseseriousaccidentssuchas
overheatingtheterminals,electricshock,orre.
Donotmodifythepowercables,useextensioncables,oruseanybranchesinthe
wiring.Improperconnections,insucientinsulation,orexceedingtheallowable
currentcancauseelectricshockorre.
Matchtheterminalboardnumbersandconnectioncablecolorswiththoseofthe
outdoorunit.Erroneouswiringmaycauseburningoftheelectricparts.
Securelyconnecttheconnectioncablestotheterminalboard.Inaddition,securethe
cableswithwiringholders.Improperconnections,eitherinthewiringorattheendsof
thewiring,cancauseamalfunction,electricshock,orre.
Alwaysfastentheoutsidecoveringoftheconnectioncablewiththecableclamp.(If
theinsulatorischafed,electricleakagemayoccur.)
Securelyinstalltheelectricalboxcoverontheunit.Animproperlyinstalledelectrical
boxcovercancauseseriousaccidentssuchaselectricshockorrethroughexposure
todustorwater.
Installsleevesintoanyholesmadeinthewallsforwiring.Otherwise,ashortcircuit
couldresult.
Installagroundleakagebreaker.Inaddition,installthegroundleakagebreakerso
thattheentireACmainpowersupplyiscutoatthesametime.Otherwise,electric
shockorrecouldresult.
Alwaysconnecttheearth(ground)cable.
Improperearthing(grounding)workcancauseelectricshocks.
Installtheremotecontrolcablessoasnottobetoucheddirectlywithyourhand.
Performwiringworkinaccordancewithstandardssothattheairconditionercanbe
operatedsafelyandpositively.
Connecttheconnectioncablermlytotheterminalboard.Imperfectinstallationmay
causeare.
CAUTION
Groundtheunit.
Donotconnecttheearth(ground)cabletoagaspipe,waterpipe,lightningrod,ora
telephoneearth(ground)cable.
Improperearthing(grounding)maycauseelectricshocks.
Donotconnectpowersupplycablestothetransmissionorremotecontrolterminals,
asthiswilldamagetheproduct.
Neverbundlethepowersupplycableandtransmissioncabletogether.Bundlingthese
cablestogetherwillcausemissoperation.
WhenhandlingPCB,staticelectricitychargedinthebodymaycausemalfunctionof
thePCB.Followthecautionsbelow:
• Establishagroundfortheindoorandoutdoorunitsandperipheraldevices.
• Cutpower(breaker)o.
• Touchmetalpartoftheindoorandoutdoorunitsformorethan10secondsto
dischargestaticelectricitychargedinthebody.
• DonottouchterminalsofpartsandpatternsimplementedonPCB.
5. 1. Wiring method
5. 1. 1. Connection diagrams
Connectioncable(tooutdoorunit)
•Powerforindoorandoutdoorunitissuppliedseparately.
Earth(ground)line
(Tooutdoorunit)
Controlline
Earth(ground)line
(Topowersupply)
Powerline
Wiredremotecontrollercable
Red
White
2-wire type
or
3-wire type
Red
White
Black
*Earth(Ground)theremotecontrollerifithasaearth(ground)wire.
5. 1. 2. Connection cable preparation
Earth(ground)wire
Powersupplycable
orconnectioncable
Keeptheearth(ground)wirelongerthantheotherwires.
•Usea4-corewirecable.
30mm
70mmormore
How to connect wiring to the terminals.
(1) Useringterminalswithinsulatingsleevesasshowninthegurebelowtoconnectto
theterminalblock.
(2) Securelycrimptheringterminalstothewiresusinganappropriatetoolsothatthe
wiresdonotcomeloose.
Strip10mm
Ring
terminal
Sleeve
(3) Usethespeciedwires,connectthemsecurely,andfastenthemsothatthereisno
stressplacedontheterminals.
(4) Useanappropriatescrewdrivertotightentheterminalscrews.
Donotuseascrewdriverthatistoosmall,otherwise,thescrewheadsmaybe
damagedandpreventthescrewsfrombeingproperlytightened.
(5) Donottightentheterminalscrewstoomuch,otherwise,thescrewsmaybreak.
(6) Seethetablebelowfortheterminalscrewtighteningtorques.
WARNING
Useringterminalsandtightentheterminalscrewstothespeciedtorques,otherwise,
abnormaloverheatingmaybeproducedandpossiblycauseseriousdamageinside
theunit.
Tightening torque [N·m (kgf·cm)]
M4screw 1.2to1.8(12to18)
M5screw 2.0to3.0(20to30)
Screwwith
specialwasher
Ring
terminal
Terminalblocks
Wire
Wire
Screwwith
special
washer
Ring
terminal
9381386260-02_IM.indd 8 27-Oct-20 09:01:46
En-9
5. 1. 3. Connection wiring
CAUTION
Becarefulnottomistakethepowersupplycableandconnectionwireswhen
installing.
Installsothatthewiresfortheremotecontrollerwillnotcomeincontactwithother
connectionwires.
(1) Removethecontrolboxcoverandinstalleachconnectionwire.
Controlboxcover
Loosenthescrews.(5places)
Controlline
Connection
cable
Power
supplycable
Powerline
Outdoor
unit
Power
supply
Earth(ground)Earth(ground)
NOTE:Besuretoconnectboththepowersupplyandconnectioncablesaccordingly.
Ifbothcablesarenotconnected,theairconditionerwillnotfunctionproperly.
(2) Installthewiringfortheremotecontroller.
• SettheDIPswitchonthePrintedcircuitboardtothepreferredwiretype.
 [2WIREor3WIRE(factorysetting)]
DIPswitch
Printcircuitboard
(PCB)
• Connecttheremotecontrollercable.
Remotecontroller
Remotecontroller
2-wire type
White
Red
Remote
controller
cable
3-wire type
Black
White
Red
Remote
controller
cable
or
*Earth(Ground)theremotecontrollerifithasaearth(ground)wire.
NOTES:BesuretochangetheDIPSWtothecorrespondingremotecontroller.
Whena2-wireremotecontrollerisconnectedtoa“3WIRE”setting,powerwill
notbesupplied.
Whena3-wireremotecontrollerisconnectedtoa“2WIRE”setting,acommuni-
cationerrorwillbedetected.
(3) Afterwiringiscomplete,securetheremotecontrollercable,connectioncable,and
powersupplycablewiththecableclamps.
Connectioncable
(tooutdoorunit)
Powersupply
cable
Powerissupplieddirectlytotheindoorunit.
Remotecontroller
cable
Cabletie(medium)
(Accessories)
Controlbox
(4) Sealthecableoutletorothergapswithputtytopreventdewcondensationorinsect
fromenteringtheelectriccontrolbox.
(5) Replacethecontrolboxcover.
CAUTION
Donotbundletheremotecontrollercable,orwiretheremotecontrollercablein
parallel,withtheindoorunitconnectionwire(totheoutdoorunit)andthepowersupply
cable.Itmaycauseerroneousoperation.
6. REMOTE CONTROLLER SETTING
Toinstallandsettheremotecontroller,refertotheinstallationmanualoftheremote
controller(wiredtype).
7. FUNCTION SETTING
Tochangethefunctionsettings,refertotheproceduresdescribedintheinstallation
manualoftheremotecontroller(wiredtype).
Thefunctionsettingsareasfollows.
7. 1. Function details
Filter sign
Selectappropriateintervalsfordisplayingtheltersignontheindoorunitaccordingtothe
estimatedamountofdustintheairoftheroom.
Iftheindicationisnotrequired,select“Noindication”(03).
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
11
00 Standard(2500hours)
01 Longinterval(4400hours)
02 Shortinterval(1250hours)
03 Noindication
Room temperature control for indoor unit sensor
Dependingontheinstalledenvironment, correctionoftheroomtemperaturesensormay
berequired.
Selecttheappropriatecontrolsettingaccordingtotheinstalledenvironment.
Thetemperature correction values show the dierence from the Standard setting “00”
(manufacturer’srecommendedvalue).
(♦...Factorysetting)
Function Number
Setting
Value
Setting Description
30
(Forcooling)
31
(Forheating)
00 Standardsetting
01 Nocorrection0.0°C(0°F)
02 -0.5°C(-1°F)
More
Cooling
Less
Heating
03 -1.0°C(-2°F)
04 -1.5°C(-3°F)
05 -2.0°C(-4°F)
06 -2.5°C(-5°F)
07 -3.0°C(-6°F)
08 -3.5°C(-7°F)
09 -4.0°C(-8°F)
10 +0.5°C(+1°F)
Less
Cooling
More
Heating
11 +1.0°C(+2°F)
12 +1.5°C(+3°F)
13 +2.0°C(+4°F)
14 +2.5°C(+5°F)
15 +3.0°C(+6°F)
16 +3.5°C(+7°F)
17 +4.0°C(+8°F)
9381386260-02_IM.indd 9 27-Oct-20 09:01:47
En-10
Room temperature control for wired remote controller sensor
Dependingontheinstalledenvironment,correctionofthewireremotetemperaturesensor
mayberequired.
Selecttheappropriatecontrolsettingaccordingtotheinstalledenvironment.
Tochangethissetting,setFunction42toBoth“01”.
EnsurethattheThermoSensoriconisdisplayedontheremotecontrollerscreen.
(♦...Factorysetting)
Function number
Setting
value
Setting description
35
(Forcooling)
36
(Forheating)
00 Nocorrection
01 Nocorrection0.0°C(0°F)
02 -0.5°C(-1°F)
More
Cooling
Less
Heating
03 -1.0°C(-2°F)
04 -1.5°C(-3°F)
05 -2.0°C(-4°F)
06 -2.5°C(-5°F)
07 -3.0°C(-6°F)
08 -3.5°C(-7°F)
09 -4.0°C(-8°F)
10 +0.5°C(+1°F)
Less
Cooling
More
Heating
11 +1.0°C(+2°F)
12 +1.5°C(+3°F)
13 +2.0°C(+4°F)
14 +2.5°C(+5°F)
15 +3.0°C(+6°F)
16 +3.5°C(+7°F)
17 +4.0°C(+8°F)
Auto restart
Enableordisableautomaticrestartafterapowerinterruption.
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
40
00 Enable
01 Disable
*Autorestartisanemergency functionsuchasforpoweroutageetc.Donotattemptto
usethisfunctioninnormaloperation.Besuretooperatetheunitbyremotecontrolleror
externaldevice.
Room temperature sensor switching
(Onlyforwiredremotecontroller)
Whenusingthewiredremotecontrollertemperaturesensor,changethesettingto“Both”
(01).
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
42
00 Indoorunit
01 Both
00:Sensorontheindoorunitisactive.
01:Sensorsonbothindoorunitandwiredremotecontrollerareactive.
*
Remotecontrollersensormustbeturnedonbyusingtheremotecontroller
Cold air prevention
*Thissettingistodisablethecoldairpreventionfunctionduringheatingoperation.When
disabled,thefansettingwillalwaysfollowthesettingontheremotecontroller.(Excluding
defrostmode).
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
43
00 Enable
01 Disable
External input control
“Operation/Stop”modeor“Forcedstop”modecanbeselected.
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
46
00 Operation/Stopmode1
01 (Settingprohibited)
02 Forcedstopmode
03 Operation/Stopmode2
Room temperature sensor switching (Aux.)
Tousethetemperaturesensoronthewiredremotecontrolleronly,changethesettingto
“Wiredremotecontroller”(01).Thisfunctionwillonlyworkifthefunctionsetting42isset
at“Both”(01)
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
48
00 Both
01 Wiredremotecontroller
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation
whentheoutdoorunitisstoppedduringcoolingoperation.
(♦...Factorysetting)
Function
Number
Setting
Value
Setting description
49
00 Disable
01 Enable
02 Remotecontroller
00:Whentheoutdoorunitisstopped,theindoorunitfanoperatescontinuouslyfollowing
thesettingontheremotecontroller.
01:Whentheoutdoorunitisstopped,theindoorunitfanoperatesintermittentlyatavery
lowspeed.
02:Enableordisablethisfunctionbyremotecontrollersetting.
*WhenusingawiredremotecontrollerwithoutIndoorunitfancontrolforenergysavingfor
coolingfunction,orwhenconnectingasinglesplitconverter,thesettingcannotbemade
byusingtheremotecontroller.Setto“00”or“01”.
Toconrmiftheremotecontrollerhasthisfunction,refertotheoperationmanualofeach
remotecontroller.
Switching functions for external output terminal
Functionsoftheexternaloutputterminalcanbeswitched.
(♦...Factorysetting)
Function Number
Setting
Value
Setting Description
60
00 Operationstatus
01to08 (Settingprohibited)
09 Errorstatus
10 Freshaircontrol
11 Auxiliaryheater
Setting record
 Recordanychangestothesettingsinthefollowingtable.
Function setting
Setting Value
Filtersign
Staticpressure
Roomtemperaturecontrolforindoorunitsensor
cooling
heating
Roomtemperaturecontrolforwiredremote
controllersensor
cooling
heating
Autorestart
Roomtemperaturesensorswitching
Coldairprevention
Externalinputcontrol
Roomtemperaturesensorswitching(Aux.)
Indoorunitfancontrolforenergysavingforcooling
Switchingfunctionsforexternaloutputterminal
AftercompletingtheFunctionSetting,besuretoturnothepowerandturnitonagain.
9381386260-02_IM.indd 10 27-Oct-20 09:01:47
En-11
7. 2. Static pressure
Thestaticpressurecanbesetbythefollowing2methods.Chooseaccordingly.
a. Manual setting (Function setting)
Selecttheappropriatestaticpressureaccordingtotheinstallationconditions.
(♦...Factorysetting)
Function
Number
Setting
Value
Setting Description
26
06 60Pa
07 70Pa
08 80Pa
09 90Pa
10 100Pa
11 110Pa
12 120Pa
13 130Pa
14 140Pa
15 150Pa
16 160Pa
17 170Pa
31 Standard60Pa
32 Automaticairowadjustment
Record the setting value of Function 26 inthe Setting record table in“7.1. Function
details”.
b. Automatic airow adjustment
CAUTION
Thisfunctioncannotbeusedwhenthereisaboosterfanbetweentheducts.
Besurethatthestaticpressureiswithintheallowedrange.Incorrectsettingmay
causeincorrectadjustmentandmayresultininsucientairoworwaterleakage.
Whentheexternalstaticpressureischangeableintheinstallationbyuseofautomatic
changeabledampers,etc.,setsothattheexternalstaticpressureisthelowest.
NOTES:
Besuretoconductthissettingbeforeanyotheroperation.Ifthemotoriswarmortheheat
exchangeriswet,falsedetectionmayleadtoincorrectadjustments.
Checkiftheelectricalwiringsandductinstallationsarecomplete.
Ifthereisadamperinstalledinthesystem,makesurethedamperisopen.
Checkiftheairlter(optional)isattached.
Ifthereareseveralinlet,outletports,makesuretheairowratesofeachportmatchthe
designedairowratebyadjustingthethrottles.
Automaticairowadjustmentispossiblebythefollowingprocedures.
1) ChangethesettingofFunction26to“Automaticairowadjustment”(32).
2) RuntheairconditioneronFanmode(High).
*Forinstructionsonhowtooperatetheairconditioner,refertotheoperationmanual
oftheremotecontroller.
 DuringAutomaticairowadjustment,themodewillbexedatFanmode(High).
 Whenthisfunctionisactive,donotoperatetheOutdoorunit.
3) Theairconditionerwillrunforabout1to8min.thenstopautomatically.
*Donotchangethethrottlesoftheinletandoutletportsduringoperation.
 WhenusedinaGroupcontrolsystem,thesettingwilltakeabout10min.
4) Turntheairconditioneroandonagain.
5) CheckthesettingvalueofFunction26andrecordtheobtainedsettingvalueinthe
followingtable.
*Ifthesettingvaluehasnotchanged,repeattheprocedurefromstep1.

Function Number Setting value
26
CAUTION
Ifthedetectedsettingvalueisnotwithintherangeofstaticpressure,pleasecheck
andre-arrangetheinstallation,thenrepeattheprocedurefromstep1.Incorrect
settingmayresultininsucientairoworwaterleakage.
WhentheductoroutletinstallationsarechangedaftertheAutomaticairow
adjustmentiscompleted,repeattheprocedurefromstep1.
8. GROUP CONTROL
CAUTION
Besuretoturnotheelectricalbreakerbeforemakingsettings.
WhensettingDIPswitches,donottouchanyotherpartsonthecircuitboarddirectly
withyourbarehands.
8. 1. Group control system
CAUTION
Groupcontrolisonlypossiblebetweenunitswithremotecontrollersofthesametype.
Toconrmthetypeofremotecontroller,seethebackoftheremotecontrolleror
“2.3.Accessories”.
Anumberofindoorunitscanbeoperatedatthesametimeusingasingleremotecontroller.
(1) Connectupto16indoorunitsinasystem.(indoorunittoremotecontroller)
A
BCDE
I.U. I.U. I.U. I.U.
Remote
controller
A,B,C,D,E:Remotecontrollercable.(Referto“2.6.Electricalrequirement”)
A+B+C+D+E≤500m.
Exampleofwiringmethod(3-wiretype)
1 2 3 1 2 3 1 2 3 1 2 3
1 2 3
Indoorunit1 Indoorunit2 Indoorunit3 Indoorunit4
Remote
controllercable
Remote
controllercable
Remotecontroller
RWB
(2) SettheR.C.address(DIPswitchsetting)
SettheR.C.addressofeachindoorunitusingtheDIPswitchontheindoorunit
circuitboard.
(a)2-wiretype
DIPswitch(RCADSW)...Factorysetting“00”
Sincetheremotecontrolleraddresssettingsareautomaticallycongured,youdonot
needtocongurethem.
Ifconguringmanually,itisnecessarytocongureboththeindoorunitandtheremote
controller.Fordetails,pleaserefertotheremotecontrollerinstallationmanual.
(b)3-wiretype
DIPswitch(RCADSW)...Factorysetting“00”
Whenconnectingmultipleindoorunitsto1standardwiredremotecontroller,setthe
addressatRCADSWinsequencefrom“00”.
Setting Setting range Switch 100
Remotecontroller
address
00to15
Setting
example00
1234
ON
RCAD
9381386260-02_IM.indd 11 27-Oct-20 09:01:48
En-12
Example
If4indoorunitsareconnected.
RC AD SW
00
RC AD SW
01
RC AD SW
02
RC AD SW
03
Indoorunit1
Remote
controller
Indoorunit2 Indoorunit3 Indoorunit4
Set the R.C. address in accordance with the table below.
Indoor unit
R.C. address
DIP SWITCH No.
1 2 3 4
1 00 OFF OFF OFF OFF
2 01 ON OFF OFF OFF
3 02 OFF ON OFF OFF
4 03 ON ON OFF OFF
5 04 OFF OFF ON OFF
6 05 ON OFF ON OFF
7 06 OFF ON ON OFF
8 07 ON ON ON OFF
9 08 OFF OFF OFF ON
10 09 ON OFF OFF ON
11 10 OFF ON OFF ON
12 11 ON ON OFF ON
13 12 OFF OFF ON ON
14 13 ON OFF ON ON
15 14 OFF ON ON ON
16 15 ON ON ON ON
NOTES:
BesuretosetconsecutiveR.C.address.
Theindoorunitscannotbeoperatedifanumberisskipped.
8. 2. Multiple remote control
Upto2remotecontrollerscanbeusedtooperateoneindoorunit
CAUTION
Multipleinstallationmethoddescribedaboveisprohibitedtocombine3-wiretypewith
2-wireType.
A
I.U.
AB
I.U.
Primary Primary Secondary
A,B:Remotecontrollercable.(Referto“2.6.Electricalrequirement”)
A≤500m,A+B≤500m
9. OPTIONAL PARTS
WARNING
Regulationofcablediersfromeachlocality,referinaccordancewithlocalrules.
Y1 Y2 Y3 12Y1 Y2 Y3 12
Terminal
(Externalin)
CN71
(Drainpump)
CN9
(Floatswitch)
CN47
(Externalout)
CN65
(Externalcom.1)
CN8
(Remotesensor)
CN48
(IRreceiver)
9. 1. Optional parts
Thisairconditionercanbeconnectedwiththefollowingoptionalkits.
Fordetailsonhowtoinstalloptionalparts,refertotheinstallationmanualincludedineach
item.
Optiontype ConnectorNo.
UTY-LBTYM(IRReceiver) CN48
UTY-XSZX(Remotesensor) CN8
UTY-XWZXZG(Externalconnectkit) CN47
*1
UTY-XCSX(ExternalinputandoutputPCB)
*2
CN65
*3
UTZ-PX1NAB
(Drainpump) CN71
(Floatswitch) CN9
*1
:
F
or
externaloutputterminalsetting,refertoFunctionNo.60in“7.FUNCTIONSETTING”.
*2
:VarioussettingsareavailablebyusingtheoptionalExternalinputandoutputPCB.
*3
:Otheroptions(convertersetc.)maybeconnectable.Pleaserefertothetechnicaldata
fordetails.
NOTES:OptionsconnectingtoCN65cannotbeusedatthesametime.
9. 2. External input and output
9. 2. 1. External input
• IndoorunitfunctionssuchasOperation/StoporForcedstopcanbedonebyusing
indoorunitterminals.
• “Operation/Stop”modeor“Forcedstop”modecanbeselectedwithfunctionsettingof
indoorunit.
•
Atwistedpaircable(22AWG)shouldbeused.Maximumlengthofcableis150m(492ft.).
• Useanexternalinputandoutputcablewithappropriateexternaldimension,depending
onthenumberofcablestobeinstalled.
• Thewireconnectionshouldbeseparatefromthepowercableline.
Connecteddevice
Terminal
● Dry contact terminal
Whenapowersupplyisunnecessaryattheinputdeviceyouwanttoconnect,usetheDry
contactterminal.
*1
Terminal
(Externalin)
Connecteddevice
*1:Theswitchcanbeusedonthefollowingcondition:DC12Vto24V,1mAto15mA.
Operation behavior
● Input signal type
Edge
ON
OFF
9381386260-02_IM.indd 12 27-Oct-20 09:01:50
En-13
● When function setting is “Operation/Stop” mode 1.
Input signal Command
OFF→ON Operation
ON→OFF Stop
● When function setting is “Forced stop” mode.
Input signal Command
OFF→ON Forcedstop
ON→OFF Normal
* Whentheforcedstopistriggered,indoorunitstopsandOperation/Stopoperationbya
remotecontrollerisrestricted.
● When function setting is “Operation/Stop” mode 2.
Input signal Command
OFF→ON Operation
ON→OFF Stop(R.C.disabled)
9. 2. 2. External output
• Atwistedpaircable(22AWG)shouldbeused.Maximumlengthofcableis25m(82ft.).
• Useanexternalinputandoutputcablewithappropriateexternaldimension,depending
onthenumberofcablestobeinstalled.
• Outputvoltage:HiDC12V±2V,Lo0V.
• Permissiblecurrent:50mA
Output select
When interlocking with external device
CN47
PCB
Connected
device
Relay(locallypurchased)
or
● When displaying “Operation/Stop”
CN47
PCB
Connecteddevice
Resistor
LED
Operation behavior
*Iffunctionsetting“60”issetto“00”
Function setting
Status Output voltage
60
00
Stop 0V
Operation DC12V
09
Normal 0V
Error DC12V
10
Indoorunitfanstop 0V
Indoorunitfanoperation DC12V
11
ExternalheaterOFF 0V
ExternalheaterON DC12V
9. 2. 3. Connection methods
Wire modication
• Removeinsulationfromwireattachedtowirekitconnector.
• Removeinsulationfromlocallypurchasedcable.Usecrimptypeinsulatedbutt
connectortojoineldcableandwirekitwire.
• Connectthewirewithconnectingwirewithsolder.
IMPORTANT:Besuretoinsulatetheconnectionbetweenthewires.
Locallypurchased
Optionparts
Externaloutputwire
Solderandinsulatetheconnectedparts.
•Connectingwirestotheterminals.
Useringterminalswithinsulatingsleevestoconnecttotheterminalblock.
•Connectionterminalsandwiringarrangement
Infollowinggure,allthepossibleconnectionsaredonefordescription.
Inactualinstallation,connectionswilldieraccordingtoeachinstallationrequirements.
9. 3. Remote sensor
Remote sensor
•Removetheexistingconnectorandreplaceitwiththeremotesensorconnector(ensure
thatthecorrectconnectorisused).
•Theoriginalconnectorshouldbeinsulatedtoensurethatitdoesnotcomeintocontact
withotherelectricalcircuitry.
Settingforroomtemperaturecorrection
Whenaremotesensorisconnected,setthefunctionsettingofindoorunitasindicated
below.
•SetFunctionNumber“30”(Roomtemperaturecontrolforcooling)to“00”
•SetFunctionNumber“31”(Roomtemperaturecontrolforheating)to“01”
9. 4. Installation details
Wheninstallingoptionalpartsorlocallyprocureddevices,pleaseconnectthewiringas
shownintheinstallationnotesprovidedwiththismanual.
9. 5. Fan delay setting
Thissettingcanbeusedwhentheauxiliaryheaterismounted.
Whentheoperationisstoppedwhentheindoorunitisoperatingwithanauxiliaryheater,
theoperationcontinues1minutes.
ChangethefollowingsettingsbyusingtheDIPswitch.
SW101
DIP switch 101
DIP SW state
Details
-
Cannotbeused
(Donotchange)
Fandelaysetting
9. 6. Wiring connection
Cable
IRreceiverwire
Drainpumpwire
Floatswitchwire
[A]
Externalconnect
kitwire
Remotesensorwire
Externalin/outPCB
(option)
MainPCB
Externalin/outPCB
cableandEMIcore
(accessoryforoption)
a
EMI
core
a
[A]InstallspacersforExternalin/outPCB.(4places,accessoriesforoption)
NOTES:
Inthegure,allpossibleconnectionsareshownfordescription.
9381386260-02_IM.indd 13 27-Oct-20 09:01:51
En-14
10. CHECK LIST
Payspecialattentiontothecheckitemsbelowwheninstallingtheindoorunit(s).After
installationiscomplete,besuretocheckthefollowingcheckitemsagain.
Check items Check box
Hastheindoorunitbeeninstalledcorrectly?
Hastherebeenacheckforgasleaks(refrigerantpipes)?
Hasheatinsulationworkbeencompleted?
Doeswaterdraineasilyfromtheindoorunits?
Isthevoltageofthepowersourcethesameasthatindicatedonthelabel
ontheindoorunit?
Arethewiresandpipesallconnectedcompletely?
Istheindoorunitgrounded?
Istheconnectioncablethespeciedthickness?
Aretheinletsandoutletsfreeofanyobstacles?
Afterinstallationiscompleted,hastheproperoperationandhandling
beenexplainedtotheuser?
Operatetheunitaccordingtotheoperationmanualprovided,andcheck
thatitisoperatingnormally.
NOTES: Check for drainage
Pourabout1literofwaterorfromtheairflowoutlettothedewtray.Checkforany
abnormalities such as strange noises. For installations with drain pump, check whether
thedrainpumpfunctionsnormally.
CAUTION
Makesurethedrainwaterisproperlydrained.
11. TEST RUN
Forhowtocarryoutthetestrun,refertotheinstallationmanualoftheremotecontroller.
Checkthefollowingitems:
(1) Isoperationofeachbuttonontheremotecontrollernormal?
(2) Donotairowdirectionlouversoperatenormally?
(3) Isthedrainnormal?
(4) Isthereanyerrornoiseandvibrationduringoperation?
• Donotoperatetheairconditionerontestrunforalongtime.
12. CUSTOMER GUIDANCE
Explainthefollowingtothecustomerinaccordancewiththeoperationmanual:
(1) Startingandstoppingmethod,operationswitching,temperatureadjustment,timer,air
owswitching,andotherremotecontrolleroperations.
(2) Cleaningandmaintenanceoftheproduct,andotheritemssuchasairltersandair
louversifapplicable.
(3) Givetheoperatingandinstallationmanualstothecustomer.
(4) Iftheindoorunitcustomcodeischanged,andtheinstallationincludesawireless
remotecontroller,informthecustomerthechangedcode.(Onsomewirelessremote
controllers,thecustomcodemayreturntoAwhenbatteriesarereplaced.)
13. ERROR CODES
Ifyouuseawiredtyperemotecontroller,errorcodeswillappearontheremotecontroller
display.Ifyouuseawirelessremotecontroller,thelampsontheIRreceiverunitwilloutput
errorcodesbywayofblinkingpatterns.Seethelampblinkingpatternsanderrorcodesin
thetablebelow.Anerrordisplayisdisplayedonlyduringoperation.
Formoredetails,refertotheinstallationmanualoftheremotecontroller.
Theerrorcodetablecontainserrorsirrelevanttothisproductaswell.
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp (green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
(1)
(1)
Serialcommunicationerror
(1)
(2)
Wiredremotecontroller
communicationerror
(1)
(5)
Checkrununnished
Automaticairowadjustmenterror
(1)
(6)
PeripheralunittransmissionPCB
connectionerror
(1)
(8)
Externalcommunicationerror
(2)
(1)
UnitnumberorRefrigerantcircuit
addresssettingerror
[Simultaneousmulti-splittype]
(2)
(2)
Indoorunitcapacityerror
(2)
(3)
Combinationerror
(2)
(4)
•Connectionunitnumber
error(indoorsecondaryunit)
[Simultaneousmulti-splittype]
•Connectionunitnumbererror
(indoorunitorbranchunit)
[Flexiblemulti-splittype]
(2)
(6)
Indoorunitaddresssettingerror
(2)
(7)
Primaryunit,secondaryunitsetup
error[Simultaneousmulti-split
type]
(2)
(9)
Connectionunitnumbererrorin
wiredremotecontrollersystem
(3)
(1)
Powersupplyinterruptionerror
(3)
(2)
IndoorunitPCBmodel
informationerror
(3)
(3)
Indoorunitmotorelectricity
consumptiondetectionerror
(3)
(5)
Manualautoswitcherror
(3)
(9)
Indoorunitpowersupplyerrorfor
fanmotor
(3)
(10)
Indoorunitcommunicationcircuit
(wiredremotecontroller)error
(4)
(1)
Roomtemp.sensorerror
(4)
(2)
Indoorunitheatex.middletemp.
sensorerror
(4)
(4)
Humansensorerror
(5)
(1)
Indoorunitfanmotorerror
(5)
(3)
Drainpumperror
(5)
(7)
Dampererror
(5)
(15)
Indooruniterror
(6)
(1)
Outdoorunitreverse/missing
phaseandwiringerror
(6)
(2)
OutdoorunitmainPCB
modelinformationerroror
communicationerror
(6)
(3)
Invertererror
(6)
(4)
Activeltererror,PFCcircuiterror
9381386260-02_IM.indd 14 27-Oct-20 09:01:57
En-15
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp (green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
(6)
(5)
TripterminalLerror
(6)
(8)
Outdoorunitrushcurrentlimiting
resistertemp.riseerror
(6)
(10)
DisplayPCBmicrocomputers
communicationerror
(7)
(1)
Dischargetemp.sensorerror
(7)
(2)
Compressortemp.sensorerror
(7)
(3)
OutdoorunitHeatEx.liquidtemp.
sensorerror
(7)
(4)
Outdoortemp.sensorerror
(7)
(5)
SuctionGastemp.sensorerror
(7)
(6)
•2-wayvalvetemp.sensorerror
•3-wayvalvetemp.sensorerror
(7)
(7)
Heatsinktemp.sensorerror
(8)
(2)
•Sub-coolHeatEx.gasinlet
temp.sensorerror
•Sub-coolHeatEx.gasoutlet
temp.sensorerror
(8)
(3)
Liquidpipetemp.sensorerror
(8)
(4)
Currentsensorerror
(8)
(6)
•Dischargepressuresensorerror
•Suctionpressuresensorerror
•Highpressureswitcherror
(9)
(4)
Tripdetection
(9)
(5)
Compressorrotorposition
detectionerror(permanentstop)
(9)
(7)
Outdoorunitfanmotor1error
(9)
(8)
Outdoorunitfanmotor2error
(9)
(9)
4-wayvalveerror
(9)
(10)
Coil(expansionvalve)error
(10)
(1)
Dischargetemp.error
(10)
(3)
Compressortemp.error
(10)
(4)
Highpressureerror
(10)
(5)
Lowpressureerror
(13)
(2)
Branchboxeserror
[Flexiblemulti-splittype]
Displaymode
:0.5sON/0.5sOFF
:0.1sON/0.1sOFF
() :Numberofashing
9381386260-02_IM.indd 15 27-Oct-20 09:02:02
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

Fujitsu ARTG65LHTA Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI