TS400-DM serial
Control panel:
1. Display
2. Visual alarm indicator lamp
3. Horn acknowledgement (HQ)
4. Lamp acknowledgement (LQ)
5. Double acknowledgement
6. Input, Delete button
7. Input, Confirm button
8. Navigation buttons
Sequence of functions:
In basic mode, the display backlight is dimmed and shows the system status, date and time.
In this mode, any button pressed will illuminate the display and list the current alarms.
An alarm caused by a fault signal is represented by the system as followed:
The horn is reset und shut off by pressing the button horn acknowledgment (3).
The Navigation buttons, illuminated during an alarm, allow the selection of a listed alarm
, or additional information regarding the selected alarm .
Pressing the button lamp acknowledgement causes the visual alarm indicator lamp to
change from flashing red to steady red when a fault signal remains, or extinguishes when
the fault signal is resolved (DIN 19235).
In case the system is set up for double acknowledgement, press the button double
acknowledgement (5) to do so.
The in the display listed alarms expires automatically after the fault signal is acknowledged
and solved.
The button Input Delete (6) is used to exit whilst being in menu.
The Input Confirm button (7) is used to confirm an entry e.g. after setting the clock.
Status display:
Possibility 1:
The horn and the fault are acknow-
ledged when the fault is still active
Possibility 2:
The horn and the fault are acknow-
ledged after the fault was solved
Possibility 3:
The horn was acknow., the fault solved
then the fault was acknowledged
1Ahl: Fault was initiated
1Ahl: Fault was initiated
1AHl: Horn was acknowledged
1AHl: Horn was acknowledged
1AHL: Fault was acknowledged
0AHl: Horn was acknowledged
0AHL: Fault was solved
(expires automatically)
0AHL: Fault was acknowledged
(expires automatically)
0AHL: Fault was acknowledged
(expires automatically)