WURM ZCB-ADP/PAT Product information

Type
Product information
ZCB-ADP/PAT
Product information
ZCB-ADP-PAT_Vx.x_PI_2018-08_EN Subject to technical changes Page 1 of 4
Front view
Feature
CAN bus adapter between RJ45 patch cable and CAN bus cable applied to individual terminals.
Writing conventions
Symbol
Meaning
CAUTION!
Avoid the described hazard: otherwise minor or medium physical injury or
damage to property will result.
WARNING!
Avoid the described hazard: otherwise there is danger from electric voltage
that could lead to death or serious physical injury.
For your safety
For safe operation and to avoid personal injury and equipment damage through operating error, always read
these instructions, become familiar with the device, and follow all safety instructions on the product and in this
document, as well as the safety guidelines of Wurm GmbH & Co. KG Elektronische Systeme. Keep these
instructions ready to hand for quick reference and pass them on with the device if the product is sold.
Wurm GmbH & Co. KG Elektronische Systeme accepts no liability in case of improper use or use for other than
the intended purpose.
Target group
These instructions are intended for "service technicians".
Intended use
The FIO 24V PAT is a universal input and output module for 8 operating or fault
messages and for control commands.
CAUTION!
Malfunctions due to improper installation and cabling!
Installation and wiring of the device should be carried out only by a qualified electrician!
Use only the correct tools for all work!
Damage to device if handled incorrectly!
Take the device out of operation if it is faulty or damaged and is therefore compromising safe
operation!
Do not repair the device yourself! If required, send it in for repair with an exact description of the
fault!
Validity of the documentation
Date
2018-08
Documentation basis
This document automatically ceases to be valid if a new technical description is issued.
Manufacturer: Wurm GmbH & Co. KG Elektronische Systeme. For further information, see our website at www.wurm.de
ZCB-ADP/PAT
Product information
Page 2 of 4 Subject to technical changes ZCB-ADP-PAT_Vx.x_PI_2018-08_EN
1 Wiring diagram
Fig. 1 Wiring diagram
Channel 1
Channel 2
70
80
71
81
72
82
73
83
74
84
75
85
76
86
D B Screened connections: each consisting of a screened connection
surface on the board and mounting clip For strain relief and
- - - - - - -
- - - - - - -
A
C
2 Installation and connection
CAUTION! Malfunctions due to improper installation and cabling!
Installation and wiring of the device should be carried out only by a qualified electrician!
Use only the correct tools for all work!
Fig. 2 Dimensions: ZCB-ADP/PAT on top-hat rail
ZCB-ADP/PAT
Product information
ZCB-ADP-PAT_Vx.x_PI_2018-08_EN Subject to technical changes Page 3 of 4
2.1 RJ45 patch cable
Connect RJ45 patch cable to RJ45 CAN bus socket.
2.2 CAN bus cable on single wires
To increase protection against interference, use pairwise-twisted cable according to DIN 47100, such
as the 4-wire cable type LiYCY(TP) 2x2x0.75mm². Alternatively, use the 3-core cable type LiYCY
3x0.75mm².
Remove sheathing from cable
1. Remove 70mm of the cable sheathing and braided screen.
2. Strip 8mm of insulation from the wires and press on wire end sleeves with a maximum of
0.75mm².
Put on cable screening (
Fig. 5)
1. Remove sheathing from the cable for an additional 8mm so that 8mm of the braided screen
is exposed.
2. Pull the 8mm of braided screen over the sheathing. ( Fig. 3)
Fig. 3 Pull over braided screen
3. Screw open the mounting clip of the screened connection enough so that the cable can be
threaded through it.
4. Thread the cable through and put the braided screen onto the screened connection surface.
CAUTION! Malfunction due to a lack of screen contact!
The braided screen must absolutely have contact to the screened connection surface.
The contact to the mounting clip is not a secure connection!
Do not put on cable screening (
Fig. 6)
1. Cleanly remove remains of screen that protrude over the sheathing.
2. Screw open the mounting clip of the screened connection enough so that the cable can be
threaded through it.
3. Thread the cable through and check that no braided screen is touching the screened
connection surface or the mounting clip.
CAUTION! Malfunction due to screen contact!
The braided screen must not have contact with the screened connection surface and
mounting clip.
Fasten cable
Fix the threaded cable with the mounting clip. Do not screw the mounting clip on too tightly
to keep the screw from damaging the mounting rail bracket.
2.3 Recommendation for wire assignment for 6-pin connection
Terminal number
3-wire
4-wire
Wire pairs
Function
71
81
Green
Green
2
CAN GND
72
82
White
White
1
CAN Low
73
83
Screened connection terminal
74
84
Brown
Brown
1
CAN High
75
85
----
Yellow
2
No function. Wire is placed on empty terminal.
76
86
Screened connection terminal
Table 1 Wire assignments
ZCB-ADP/PAT
Product information
Page 4 of 4 Subject to technical changes ZCB-ADP-PAT_Vx.x_PI_2018-08_EN
3 Connection examples
Fig. 4
Fig. 5
Fig. 6
Fig. 4
Screens of cable 2 and 4 are applied.
Screens of cable 1 and 2 are connected to each other.
Screens of cable 3 and 4 are connected to each other.
Fig. 5
Screen of cable 4 is applied.
Screen of cable 2 is not applied.
Screens of cable 3 and 4 are connected to each other.
Screens of cable 1, 3 and 4 are connected to each
other.
Fig. 6
Screens of cable 2 and 4 are not applied.
Screens of cable 1 and 2 are separated.
Screens of cable 3 and 4 are separated.
4 Technical data
Connections
Per channel: RJ45 CAN bus socket, 6-pin CAN bus connection, screened connection
Dimensions
(WxH) 33 x 73 x 38 mm
Fastening
Top-hat rail TH 35-15 or TH 35-7,5 (DIN EN 60715)
Ambient temperature
Operation: 0…+55°C, storage: -25…+70°C
Weight
About 32g