Seite 12 62.9693.03
6.2.6 TROUBLESHOOTING DISPLAY
A fault in the appliance is registered by the electronic control
system and, dependent on the type of fault, is shown on the
display (AT) by the letters E (error) or A (alarm) combined
with a one- or two-digit number. At the same time as the fault
occurs, an intermittent warning tone will sound, the energy
supply is interrupted and the lamp is switched off. Press button
Q to acknowledge the error message (warning tones).
FAULTY ERROR MESSAGE
If a faulty error message appears, that is to say, a message
that is inappropriate for the appliance, the appliance's parame-
ters are incorrectly set. This situation can be remedied by cor-
recting the parameters for the appliance in question.
MULTIPLE FAULTS
Two faults may be reported at once, e.g. E7 and E10. The dis-
plays follow one another. If, for example, fault display E7 is
reset with button Q, E10 appears on the display (AT). The
appliance will only function perfectly again when the latter has
been remedied and reset.
PROBLEMS WITHOUT DISPLAY
Finding the cause of the fault is dependent on the technician's
skill.
The parts of the control system can be accessed by removing
the control panel (F) as described in chapter 5.
6.2.7 OPERATING BOARD (UP)
If a fault is identified, no repairs can be made to the board. It is
replaced as a complete unit.
Removal
Pull off the operating knobs (BK) on the front of the switch
panel. Then remove the control board (see below). Remove
the long spacing sleeves (HP1). Remove the 6 nuts (MP2) and
washers from the steel panel (ST). Remove the steel panel
and the short spacing sleeves (HP2). Remove the operating
board.
Installation
Proceed in the reverse order to removal. Plug the flat cable
(FL) connector firmly into the board. Make sure that the board
is centered in relation to the windows in the switch panel and
the nuts (MPx) are not tightened excessively to avoid damage
to the board. Replace the operating knobs firmly on the front
panel to ensure that the seals are in place.
When replacing the operating circuit board the jumper JP1 the
position of the jumper JP1 must be checked resp. corrected.
A Jumper JP1 in the upper position
clock time is activated and will be stored
B Jumper JP1 in the lower position
clock time will be not stored, the battery will not get
unloaded. Condition of the board when getting as spare
part (position of the jumper JP1 for prints on stock).
Display/
failure
code
Problem Action
E1 Defective food temperature sensor
(J15); appliance switches off
Reset the error message and alarm with
button (Q); repair cause of problem
(loose connector, broken sensor, short
circuit)
E2 Defective jacket temperature sensor
(J16); appliance switches off
Reset the error message and alarm with
button (Q); repair cause of problem
(loose connector, broken sensor, short
circuit)
E3 Defective deaeration temperature
sensor (J17); appliance switches off
Reset the error message and alarm with
button (Q); repair cause of problem
(loose connector, broken sensor, short
circuit)
E5 Defective control board temperature
sensor
Reset the error message and alarm with
button (Q); replace control board
E6 Temperature of food sensor J15 is
too high
Reset the error message and alarm with
button (Q); repair cause of problem
(defective contactor)
E7 Temperature of jacket sensor J16 is
too high
Reset the error message and alarm with
button (Q); repair cause of problem
(defective contactor)
E8 Pressure in jacket is too high Reset the error message and alarm with
button (Q); repair cause of problem
(defective contactor)
E9 Defective analogue/digital transfor-
mer
Reset the error message and alarm with
button (Q); replace control board
E10 Response of safety thermostat to
lack of water; lack of water in the jak-
ket
Reset the error message and alarm with
button (Q); find cause of lack of water;
leakage at welds/ seals/ safety valve,
check valve; defective control unit; refill
jacket with demineralized water; reset
safety thermostat (F1) by pressing the
red button
E11 Temperature of deaeration sensor
J17 is too high
Reset the error message and alarm with
button (Q)
E21 HACCP Master Personal Computer
is not connected.
Discharge fault display and signal by
pressing button (Q).
E22 HACCP Interface COP485.1 is not
connected.
Discharge fault display and signal by
pressing button (Q).
E23 HACCP configuration; EEPROM
COP485.1 (memory chip) has found
a reading fault.
Discharge fault display and signal by
pressing button (Q) and repair fault.
E24 HACCP configuration; EEPROM
COP485.1 (memory chip) has found
a spelling fault.
Discharge fault display and signal by
pressing button (Q) and repair fault.
Alarm Problem Action
A02 Error when the burner is ignited. Acknowledge the error message by pres-
sing the button (Q) and restart by pres-
sing the button (TT). Wait for the delay
time of 30 to 60 seconds.
A31 Lack of water in the jacket; alterna-
ting display (AT) of food temperature
and A31; this is an advance warning
to refill the jacket with water; the
deaeration valve has reached the
programmed max. amount of ope-
nings (8000) according to PNo..9.5.
Reset the error message and alarm with
button (Q); The appliance can continue
to be used normally. After starting each
time, error message A31 will be dis-
played.
To remedy the continuous message, add
demineralized water to the jacket. Reset
parameter PNo. 1.6.5. to 0 either by
changing the parameter content or by
button combination (as described in the
section "Test functions for service appli-
cation" action 3.)
Problem Reasons
Displays do not light up when
the appliance is switched on
Control fuse (X4) is faulty
Only the lamp (LS) lights up
when the control switch (S) is
switched on. Other functions
cannot be activated.
- Water on the printed circuit
board. Blow it off and dry
the board.
- Microprocessor is not pro-
grammed
The operating displays go
crazy
- Water on the control- and/or
operating board
- The flat cable between the
control- and operating board
is faulty or there is a poor
connection somewhere.