Korenix JetNet 5628G Series User manual

Category
Network switches
Type
User manual
1
Korenix JetNet 5628G/5828G Series
IEC61850-3 Modular Managed Ethernet Switch
User Manual
Version 1.6
Oct. 2013
www.korenix.com
2
Korenix JetNet 5628G/5828G
Industrial Modular Managed Ethernet Switch
User’s Manual
Copyright Notice
Copyright 2006-2011 Korenix Technology Co., Ltd.
All rights reserved.
Reproduction in any form or by any means without permission is prohibited.
3
Federal Communications Commission (FCC) Statement
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to correct the interference
at his expense.
The user is cautioned that changes and modifications made to the equipment without approval
of the manufacturer could void the users authority to operate this equipment.
Index
1 Introduction ....................................................................................................................... 2
1.1 Overview .............................................................................................................. 2
1.2 Major Features ..................................................................................................... 4
1.3 Package List ........................................................................................................ 4
1.4 Optional Module ................................................................................................... 5
2 Hardware Installation ........................................................................................................ 6
2.1 Hardware Introduction.......................................................................................... 6
2.2 Wiring Power Inputs ............................................................................................. 9
2.3 Wiring Digital Input ............................................................................................... 9
2.4 Wiring Digital Output .......................................................................................... 10
2.5 Wiring Earth Ground .......................................................................................... 10
2.6 Choosing Fast Ethernet Module ........................................................................ 10
2.7 Mounting Fast Ethernet Module .......................................................................... 11
2.8 Wiring Fast Ethernet Ports ................................................................................. 12
2.9 Wiring Fiber Ports .............................................................................................. 12
2.10 Wiring Gigabit Combo Ports .............................................................................. 14
2.11 Wiring RS-232 Console Cable ........................................................................... 14
2.12 Rack Mounting Installation ................................................................................. 14
2.13 Safety Warming.................................................................................................. 16
3 Preparation for Management .......................................................................................... 17
3.1 Preparation for Serial Console ........................................................................... 17
3.2 Preparation for Web Interface ............................................................................ 18
3.3 Preparation for Telnet Console .......................................................................... 20
4 Feature Configuration ..................................................................................................... 23
4.1 Command Line Interface Introduction ................................................................ 24
4.2 Basic Setting (Y2011, 0604) .............................................................................. 29
4.3 Port Configuration .............................................................................................. 55
4.4 Network Redundancy......................................................................................... 66
4.5 VLAN .................................................................................................................. 85
4.6 Private VLAN ..................................................................................................... 95
4.7 Traffic Prioritization .......................................................................................... 102
4.8 Multicast Filtering ............................................................................................. 107
4.9 Routing .............................................................................................................. 113
4.10 SNMP ............................................................................................................... 141
4.11 Security ............................................................................................................ 145
4.12 Warning ............................................................................................................ 157
1
4.13 Monitor and Diag .............................................................................................. 166
4.12 Device Front Panel ............................................................................................. 182
4.13 Save to Flash ................................................................................................... 184
4.14 Logout .............................................................................................................. 185
5 Appendix ....................................................................................................................... 186
5.1 Pin Assignment of the RS-232 Console Cable ................................................ 186
5.2 Korenix SFP family .......................................................................................... 187
5.3 Korenix Private MIB ......................................................................................... 188
5.4 Revision History ............................................................................................... 189
5.5 About Korenix .................................................................................................. 190
2
1 Introduction
Welcome to Korenix JetNet 5628G/5828G Industrial Modular Managed Ethernet Switch
User Manual. Following topics are covered in this chapter:
1.1 Overview
1.2 Major Features
1.3 Package Checklist
1.1 Overview
JetNet 5628G/5828G is an IEC61850-3 Modular Managed Ethernet Switch, equipped with 4
on-board Gigabit RJ45 / MINI GBIC combo ports plus 3 modular slots for maximum 24 10/100
Base-TX Ports or 18 100Base-FX Fiber interfaces ports. The JNM5 series modules are flexible
for different port volume, media types and application needs.
JetNet 5628G/5828G, a special design for substation automation and industrial control
room, is compliant with the IEC61850-3, IEEE1613 high level environmental certifications.
JetNet 5628G/5828G has the capability of forwarding Data, GOOSE, SCADA message
without any loss or collision. JetNet 5628G/5828G also pass the NEMA TS-2 and EN50121-4
certification which are requested in Transportation and Railway market.
The advantage of choosing JetNet 5628G/5828G is that the switch supports on board 4
gigabit ports which allow users to trunk up to 8G uplink bandwidth or to form 2 independent
Gigabit rings. The 24 100M interface allows to form 12 100M rings for a reliable network
redundancy. This is the Korenix MultiRing redundancy design. The recovery time when ring
failure can still remains 10ms high performance.
The JetNet 5628G/5828G series also supports the advanced management, control and
security requirements in power substations and control rooms, such as the VLAN, QoS, IGMP,
layer 2/4 Access Control List, 802.1x, SNMP V3, LLDP, etc. The JetNet 5828G support Layer
3 routing features, such as static route, dynamic unicast routing protocols, RIP and OSPF,
dynamic multicast routing protocol, DVMRP and VRRP for router redundancy. With all the
layer 2 and layer 3 features complete the demand and greatly satisfy technicians requests.
The JetNet 5628G/5828G Series include below models with the different power input types.
The model name and power input type is listed as below.
JetNet 5628G IEC61850-3 24+4G Modular Managed Ethernet Switch
Power Input: 1 x 85-264VAC/88-370VDC, Standard AC Plug + 2 x 24/48VDC
JetNet 5628G-2AC IEC61850-3 24+4G Modular Managed Ethernet Switch with Dual AC
3
input, Power Input: 2 x 85-264VAC/88-370VDC, Standard AC Plug
JetNet 5628G-2HDC IEC61850-3 24+4G Modular Managed Ethernet Switch with Dual
88-370VDC input, Power Input: 2 x 85-264VAC/88-370VDC, 3 Pin Terminal Block
JetNet 5828G IEC61850-3 24+4G Layer 3 Modular Managed Ethernet Switch
Power Input: 1 x 85-264VAC/88-370VDC, Standard AC Plug + 2 x 24/48VDC
JetNet 5828G-2AC IEC61850-3 24+4G Layer 3 Modular Managed Ethernet Switch with
Dual AC input, Power Input: 2 x 85-264VAC/88-370VDC, Standard AC Plug
JetNet 5628G-R IEC61850-3 24+4G Modular Managed Ethernet Switch, Ethernet Ports
on the Rear panel
Power Input: 2 x 85-264VAC/88-370VDC, 6-pin Terminal Block
JetNet 5828G-R IEC61850-3 24+4G Layer 3 Modular Managed Ethernet Switch,
Ethernet Ports on the Rear panel
Power Input: 2 x 85-264VAC/88-370VDC, 6-pin Terminal Block
PWR 1
PWR 2
AC/HDC
Connector
Low
Voltage
DI/DO
5628G
5828G
85~264VAC
1x Standard
three-pronged AC
plug
2x DC
24/48V
2DI + 2DO
5628G-2AC/
5828G-2AC
85~264VAC
85~264VAC
2x Standard
three-pronged AC
plug
2DI + 2DO
5628G-2HDC
85~264VAC
88~370VDC
85~264VAC
88~370VDC
2x 3 pin Terminal
Block
2DI + 2DO
5628G-R/
5828G-R
85~264VAC
88~370VDC
85~264VAC
88~370VDC
6 pin Terminal
Block
1 DO
Note: The PWR 1 and PWR2 can support both 85-264VAC and 88-370VDC High Voltage
DC input. The AC connector is standard three-pronged AC connector, the High Voltage DC
connector is 3-pin terminal block represent for L, N and PE. The LDC connector is a 4 pin
terminal block for dual input.
4
1.2 Major Features
Korenix JetNet 5628G/5828G has the below different models as below.
Feature
5628G-R
5828G
5828G-R
IEC 61850-3 Design
V
V
V
Ethernet Port on the Rear
V
V
On Board free 4G combo ports
V
V
V
3 Flexible Modules
V
V
V
Max. Ring
14
14
14
Multiple Spanning Tree Protocol
V
V
V
256VLANs
V
V
V
8 physical priority queues
V
V
V
Private VLAN, QinQ
V
V
V
Modbus/TCP
V
V
V
Layer 2+ ACL, 802.1x
V
V
V
SNMP, LLDP & JetView Pro NMS
V
V
V
Layer 3 Unicast Routing Protocols - RIP,
OSPF
V
V
Virtual Router Redundancy Protocol
V
V
Layer 3 Multicast Routing Protocols
DVMRP (coming soon)
V
V
Advanced PIM-DM/SM (coming soon)
V
V
The detail spec is listed in latest datasheet. Please download the latest datasheet in
Korenix Web site.
1.3 Package List
Korenix JetNet 5628G/5828G Series products are shipped with following items:
JetNet 5628G/5828G (4G Combo on board, No Fast Ethernet modules, no SFP
transceivers)
Rack Mount Kit
Console Cable
Power Cord
Quick Installation Guide
Document CD
If any of the above items are missing or damaged, please contact your local sales
representative.
5
1.4 Optional Module
Additional Fast Ethernet Modules:
JNM5-8TX: 8 ports 10/100Base-TX module
JNM5-4TX/4SFP: 4 ports 10/100TX + 4 100FX-SFP Socket
JNM52SFP/4MSC: 2 ports 100Base-FX + 4 ports 100Base-FX/SC Multi-mode
JNM52SFP/4SSC: 2 ports 100Base-FX + 4 ports 100Base-FX/SC Single-mode
Notice: The system only allow Maximum 12 SC type Fiber Links within one Switch. Less
than 12 Fiber links is Korenix recommend in high temperature environment, especially
no- air condition environment.
6
2 Hardware Installation
This chapter includes hardware introduction, installation and configuration information.
Following topics are covered in this chapter:
2.1 Hardware Introduction
Dimension
Panel Layout
Bottom View
2.2 Wiring Power Inputs
2.3 Wiring Digital Input
2.4 Wiring Relay Output
2.5 Wiring Earth Ground
2.6 Choosing Fast Ethernet Module
2.7 Wiring Ethernet Ports
2.8 Wiring Fiber Ports
2.9 Wiring Gigabit Combo Ports
2.10 Wiring RS-232 console cable
2.11 Rack Mounting Installation
2.12 Safety Warming
2.1 Hardware Introduction
2.1.1 JetNet 5628G/5828G (Ethernet Ports on the Front) Series
LED
System LED
Color
Port LED
Color
PWR/AC 1, PWR/AC 2
Green On/Off
Port 1~8 (JNM5-8TX)
Green/Green Blinking
LDC 1, LDC 2 (DC Power)
Green On/Off
Port 1~8 (JNM5-4TX/4SFP)
Green/Green Blinking
RDY (System Ready)
Green On/Off
Port 1~6 (JNM5-2SFP/4MSC)
Green/Green Blinking
DI 1, DI 2 (Digital Input)
Green On/Off
Port 1~6 (JNM5-2SFP/4SSC)
Green/Green Blinking
R.M. (Ring Master)
Green On/Off
Port 25~28 (Gigabit RJ45)
Green/Green Blinking
DO 1, DO 2 (Digital Output)
Red On/Off
Port 25~28 (Gigabit SFP)
Green/Green Blinking
R.F. (Ring Failure)
Red On/Off
For one AC model, the PWR2/AC2 LED is always not light. For dual AC/HDC model, the
LDC1/2 LED is always not light.
7
Dimension
JetNet 5628G/5828G Industrial Modular Managed Ethernet Switch dimension (W x H x D)
is 44mm(H) x 431mm (W) x 376mm (D)
Panel Layout
The front panel includes 3 modular slots for Fast Ethernet Module.
4 On-Board Gigabit Combo Port which support 10/100/1000 Copper and Gigabit SFP.
Power switch is used when you want change modular or save power.
In the back of the switch, there are AC, HDC or LDC power input socket, Digital
Input/Output socket and RS232 console port.
8
2.1.1 JetNet 5628G-R/5828G-R (Ethernet Ports on the Rear) Series
LED
LED on the Front
Color
LED on the Module
Color
P1, P2 (Power LED)
Green On/Off
Port 1~8 (JNM5-8TX)
Green/Green Blinking
DO 1 (Digital Output)
Red On/Off
Port 1~8 (JNM5-4TX/4SFP)
Green/Green Blinking
R.S. (Ring Status)
Green: Ring state is normal
Green Flashing: Incorrect
configuration
Amber: Ring state is
abnormal
Amber Flashing: One of the
ring ports break has been
detected
Port 1~6 (JNM5-2SFP/4MSC)
Green/Green Blinking
Port 1-28
Green/Green Blinking
Port 1~6 (JNM5-2SFP/4SSC)
Green/Green Blinking
Note: Port 25-28 is gigabit combo port, there is no LED on the rear panel.
Dimension
JetNet 5628G-R/5828G-R Industrial Modular Managed Ethernet Switch dimension (W x
H x D) is 44mm(H) x 431mm (W) x 376mm (D)
Panel Layout
The front panel includes RS-232 console and LED information only.
The rear panel includes 3 modular slots for Fast Ethernet Module. 4 On-Board Gigabit
Combo Port which support 10/100/1000 Copper and Gigabit SFP. And 6-pin High
Voltage Power Input socket and 1 Digital Output socket
9
2.2 Wiring Power Inputs
JetNet 5628G/5828G provides 2 types power input, AC power input and DC power input.
The front power switch can switch off all the power input at the same time.
AC Power Input
Connect the attached power cord to the AC power input connector, the available AC
power input is range from 85-264VAC.
High Voltage Power Input
The power input support both 85-264VAC and 88-370VDC power input. Connect the
power cord to the PE for Protective Earth, L / V+ for LINE or V+, N/V- for Neutral or V-.
For high power input, tighten the wire-clamp screws to prevent DC wires from being
loosened is must.
The pin assignment sequence of JetNet 5628G-R/5828G-R is N, L, PE for Power input 1
and PE, N, L for Power Input 2.
DC Power Input
Follow below steps to wire JetNet 5628G/5828G redundant DC power inputs.
1. Insert positive and negative wires into V+ and V-
contacts respectively of the terminal block
connector
2. Tighten the wire-clamp screws to prevent DC
wires from being loosened.
3. Power 1 and Power 2 support power redundancy
and polarity reverse protection functions.
Note 1: It is a good practice to turn off input and load power, and to unplug power terminal
block before making wire connections. Otherwise, your screwdriver blade can
inadvertently short your terminal connections to the grounded enclosure.
Note 2: The range of the suitable DC electric wire is from 12 to 24 AWG.
Note 3: If the 2 power inputs are connected, JetNet 5628G/5828G will be powered from
the highest connected voltage. The unit will alarm for loss of power, either PWR1 or
PWR2.
2.3 Wiring Digital Input
JetNet 5628G/5828G provides 2 digital inputs. It allows users to connect the termination
units’ digital output and manage/monitor the status of the connected unit. The Digital Input
pin can be pulled high or low; thus the connected equipments can actively drive these
pins high or low. The embedded software UI allows you to read and set the value to the
connected device.
The power input voltage of logic low is DC 0~10V. Logic high is DC 11~30V.
10
Wire the digital input just like wiring the power input introduced in chapter 2.2.
The JetNet 5628G-R/5828G-R doesnt support Digital Input.
2.4 Wiring Digital Output
JetNet 5628G/5828G provide 2 digital outputs and JetNet 5628G-R/5828G-R provide 1
digital output, also known as Relay Output. The relay contacts are energized (open) for
normal operation and will close for fault conditions. The fault conditions include power
failure, Ethernet port link break or other pre-defined events which can be configured in
JetNet 5628G/5828G UI.
The default (without power) state of the Digital Output is normal OPEN state. The
ON/OFF state is controlled by software configuration.
The JetNet 5628G-R and JetNet 5828G-R support both OPEN and CLOSE mode.
Follow the installation guide print in the panel to wire.
Pin No.
State
1
NO (Normal Open)
2
COM
3
COM
4
NC (Normal Close)
Loosen the Digital Output screw by screw drive, then tighten the screw after digital output
wire is connected.
Note: When installed the Digital Output in your environment, remember to check the
environment protection, like Surge protection of the connected device. The digital output
contact of the JetNet 5628G/5828G do not provide high level Surge protection, this should
be protected by connected device.
2.5 Wiring Earth Ground
To ensure the system will not be damaged by noise or any electrical shock, we suggest
you to make exact connection with JetNet 5628G/5828G with Earth Ground.
For AC input, the 3
pin include V+, V- and GND. The GND pin must be connected to the
earth ground.
For High Voltage DC (HVDC) input, PE is Protective Earth pin.
For DC input, loosen the earth ground screw by screw drive; then tighten the screw after
earth ground wire is connected.
2.6 Choosing Fast Ethernet Module
The JetNet 5628G/5828G provides several types of Fast Ethernet modules. There are 8
10/100Base-TX ports, 4 100Base-FX/SC ports plus 2 100Base-FX SFP and 4
10/100Base-TX plus 4 100Base-FX modules.
11
The module type includes:
The modular design is more flexible for purchasing, less storage of stock and field
installations. Once the distance is over 100 meters, users can exchange modules without
replacing device. The 3 modules allow you connect maximum 24 10/100Base-TX Copper
ports or maximum 18 100Base-FX Fiber ports.
As purchasing the JetNet 5628G/5828G, please confirm the media type and the port
volume. Discuss the need with your customer and advise them your plan for the media
ports is the consideration before purchasing the Ethernet module.
Note: The JetNet 5628G/5828G main board can support high temperature environment.
There is no limitation to connect up to 3 x JNM5-8TX modules. Should you want connect
the Fiber modules, please check the environment temperature first. The heat from the
fiber interface is much higher than copper, using wide-temperature SFP transceiver is
recommended. Korenix requests less than 12 Fiber connections within one JetNet
5628G/5828G box when install in high temperature environment, especially no- air
condition environment. Should you need more fiber connections in one field station,
please separate them to 2 or more JetNet 5628G/5828G box.
2.7 Mounting Fast Ethernet Module
2.7.1 Power down the switch or Turn off the front power switch of the 5628G/5828G
series.
2.7.2 Unlock the front plate of the slot and plug the Fast Ethernet Module into the
socket.
2.7.3 Turn the captive screw to lock the module.
2.7.4 After locked the modules,
turn on the switch.
Note: Each time when you
plug or exchange module,
be noticed that you
should turn off the power
first.
12
2.8 Wiring Fast Ethernet Ports
JetNet 5628G/5828G includes maximum 24 RJ-45 Fast Ethernet ports. The fast Ethernet
ports support 10Base-T and 100Base-TX, full or half duplex modes. All the fast Ethernet
ports will auto-detect the signal from connected devices to negotiate the link speed and
duplex mode. Auto MDI/MDIX allows users to connect another switch, hub or workstation
without changing straight through or crossover cables.
Note that crossover cables simply cross-connect the transmit lines at each end to the
received lines at the opposite end.
Straight-through Cabling Schematic
Cross-over Cabling Schematic
Note that Ethernet cables use pins 1, 2, 3, and 6 of an 8-pin RJ-45 connector. The signals
of these pins are converted by the automatic MDI-X function, as shown in the table below:
Pin MDI-X
Signals
MDI Signals
1
RD+
TD+
2
RD-
TD-
3
TD+
RD+
6
TD-
RD-
Connect one side of an Ethernet cable into any switch port and connect the other side to
your attached device. The LNK LED will light up when the cable is correctly connected.
Refer to the LED Indicators section for descriptions of each LED indicator. Always make
sure that the cables between the switches and attached devices (e.g. switch, hub, or
workstation) are less than 100 meters (328 feet).
The wiring cable types are as below.
10Base-T: 2-pair UTP/STP Cat. 3, 4, 5 cable, EIA/TIA-568 100-ohm (100m)
100 Base-TX: 2-pair UTP/STP Cat. 5 cable, EIA/TIA-568 100-ohm (100m)
1000 Base-TX: 4-pair UTP/STP Cat. 5 cable, EIA/TIA-568 100-ohm (100m)
2.9 Wiring Fiber Ports
100Base-FX-SC Fiber
The automatic MDI/MDI-X crossover function does not apply to fiber connections, as
these must be crossed over manually. To connect the fiber port on one switch to the fiber
port of another switch, simply cross-connect the transmit channel at each end to the
receive channel at the opposite end as illustrated in the figure below.
13
JNM5-2SFP/4MSC and JNM5-2SFP/4SSC provides four 100Base-FX ports with SC type
connectors (in multi-mode and single mode versions). Single-mode types have greater
distance capability than multi-mode types, but single mode cable is generally more
expensive.
A fiber segment using single-mode cable must use 9/125 or 10/125 micrometer
single-mode fiber cables. For single-mode, the connection distance can be up to 30 km.
A fiber segment using multi-mode must use 50 or 62.5/125 micrometer multi-mode fiber
cables. For multi-mode, the connection distance can be up to 2 km.
Small Form-factor Pluggable (SFP)
The SFP ports accept standard MINI GBIC SFP transceiver. But, to ensure system
reliability, Korenix recommends using the Korenix certificated Gigabit SFP
Transceiver. The web UI will show Unknown vendor type when choosing the SFP which
is not certificated by Korenix. The certificated SFP transceiver includes 100Base-FX
single/multi mode, 100/Gigabit BIDI/WDM, 1000Base-SX/LX single/multi mode ranger
from 550m to 80KM.
14
The way to connect the SFP transceiver is to Plug in SFP fiber transceiver fist. Cross-connect the
transmit channel at each end to the receive channel at the opposite end as
illustrated in the figure below. The SPF cage is 2x1 design, check the
direction/angle of the fiber transceiver and fiber cable when inserted.
Note: This is a Class 1 Laser/LED product. Don’t stare at the
Laser/LED Beam.
2.10 Wiring Gigabit Combo Ports
JetNet 5628G/5828G includes 4 RJ-45 Gigabit Ethernet ports. The speed of the gigabit
Ethernet port supports 10Base-T, 100Base-TX and 1000Base-TX. JetNet 5628G/5828G
also equips 4 gigabit SFP ports combo with gigabit Ethernet ports. The speed of the
gigabit SFP port supports 1000Full Duplex. The available gigabit SFP supports Gigabit
Single-mode, Multi-mode, BIDI/WDM single-mode and DDM SFP transceivers. (The
100Base-FX is not supported in gigabit combo ports.)
While connect both RJ-45 and SFP at a time, the SFP will be chosen as the active media.
2.11 Wiring RS-232 Console Cable
Korenix JetNet 5628G/5828G attaches one RS-232 DB-9 to DB-9 cable in the box.
Connect the DB-9 connector to the COM port of your PC, open Terminal tool and set up
serial settings to 9600, N,8,1. (Baud Rate: 9600 / Parity: None / Data Bit: 8 / Stop Bit: 1)
Then you can access CLI interface by console able.
Note: If you lost the cable, please contact with your sales or follow the pin assignment to
buy a new one. The Pin assignment spec is listed in the appendix.
2.12 Rack Mounting Installation
The Rack Mount Kit is attached inside the package.
15
2.1.1 Attach the brackets to the device by using the screws provided in the Rack
Mount kit.
2.2.2 Mount the device in the 19 rack by using four rack-mounting screws provided by
the rack manufacturer.
When installing multiple switches, mount them in the rack one below the other. Its
requested to reserve 0.5U-1U free space for multiple switches installing. This is
important to disperse the heat generated by the switch.
Notice when installing:
Temperature: Check if the rack environment temperature conforms to the specified operating
temperature range.
Mechanical Loading: Do no place any equipment on top of the switch
Grounding: Rack-mounted equipment should be properly grounded.
Fiber Port limitation: Maximum 12 Fiber ports are allowed to install under the highest
temperature. Wide-Temperature SFP transceiver is always suggested.
16
2.13 Safety Warming
2.2.1 The Equipment intended for installation in a Restricted Access
Location.
2.2.2 The warning test is provided in user manual. Below is the information:
For tilslutning af de ovrige ledere, se medfolgende installationsvejledning.
Laite on liitettava suojamaadoitus-koskettimilla varustettuun pistorasiaan
Apparatet ma tilkoples jordet stikkontakt
Apparaten skall anslutas till jordat uttag
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194

Korenix JetNet 5628G Series User manual

Category
Network switches
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI