Support Vertiv User guide

Category
Uninterruptible power supplies (UPSs)
Type
User guide
Vertiv Liebert® EDGE
Installer/User Guide
| Lieber EDGE Installer/User Guide
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent
section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/ for additional assistance.
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
The products covered by this instruction manual are manufactured
and/or sold by Vertiv. This document is the property of Vertiv and
contains confidential and proprietary information owned by Vertiv.
Any copying, use or disclosure of it without the written permission
of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions regarding
usage of trademark names should be directed to the original
manufacturer.
Lieber EDGE Installer/User Guide
TABLE OF CONTENTS
1 Important Safety Instructions 1
2 EDGE Description 3
2.1 Available Models 3
2.2 Rear Panel Views 4
2.3 Front Panel 5
3 Installation 7
3.1 What’s Included 7
3.2 Unpacking and Inspection 7
3.3 Preparation for Installation 8
3.3.1 Installation Environment 8
3.3.2 Installation Clearances 8
3.4 Installing the UPS 8
3.4.1 Installation Environment 8
3.4.2 Installing a Mini Tower (MT) Model 11
3.5 Connecting Loads 11
3.6 USB Communication Connection 11
3.7 Emergency Power-off (EPO) Connection (Optional) 11
3.8 External Battery Cabinet Connection on 2U and 3U VRLA Models (Optional) 12
3.9 Network Communication Card Connection (Optional) 13
3.9.1 Connecting AC Input 13
4 Operations 15
4.1 Modes of Operation 15
4.1.1 Off Mode 15
4.1.2 On/Normal Mode 15
4.1.3 On/Automatic Voltage Regulation (AVR)/Boost1 Mode 15
4.1.4 On/Automatic Voltage Regulation (AVR)/Boost2 Mode 15
4.1.5 On/Automatic Voltage Regulation (AVR)/Buck Mode 15
4.1.6 On/Battery Mode 15
4.1.7 Fault Mode 15
4.1.8 Battery Self-test Mode 15
4.1.9 Controls 16
4.2 Startup wizard 17
4.2.1 Default Screen and Flow Screens 17
4.2.2 Main menu Screen 19
4.2.3 Status Screen 19
4.2.4 Settings Submenu 21
4.2.5 Control Screen 29
4.2.6 Log Screen 29
i
Lieber EDGE Installer/User Guide
4.2.7 About Screen 32
4.2.8 Maintenance screen 33
4.3 Editing Display and Operation Settings 35
4.3.1 Changing the Password 36
5 Maintenance and Battery Replacement 39
5.1 Precautions 39
5.2 Battery Charging 39
5.3 Replacing the UPS Batteries 39
6 Specifications 43
6.1 Battery Run Times 53
Appendices 61
Appendix A: Technical Support 61
ii
Lieber EDGE Installer/User Guide
1 Important Safety Instructions
IMPORTANT! This manual contains important safety instructions that must be followed during the
installation and maintenance of the UPS and batteries. Read this manual thoroughly and the safety and
regulatory information, available at https://www.vertiv.com/ComplianceRegulatoryInfo, before
attempting to install, connect to supply, or operate this UPS.
1 Important Safety Instructions 1
Lieber EDGE Installer/User Guide
1 Important Safety Instructions
2
This page intentionally left blank
Lieber EDGE Installer/User Guide
2 EDGE Description
The Lieber EDGE is a line-interactive UPS designed for IT applications such as network closets and
small data centers. It is available in 1U, 2U, 3U and MT(mini tower) form factors. It provides reliable power
protection for servers, critical nodes, network workstations, large network peripherals, network routers,
bridges, hubs and other electronic equipment. Matching battery cabinets are available to extend the on-
battery operating time for 2U and 3U VRLA models. The optional Liebert® Network Communication Card
makes advanced monitoring and control available.
2.1 Available Models
BATTERY TYPE MODEL FROM FACTOR MODEL NUMBER NOMINAL POWER RATING (230 V INPUT)
VRLA (Valve Regulated Lead Acid)
1U
EDGE-500IRT1U 500 VA / 450 W
EDGE-1000IRT1U 1000 VA / 900 W
EDGE-1500IRT1U 1500 VA / 1350 W
2U
EDGE-1500IRT2UXL 1500 VA / 1350 W
EDGE-2200IRT2UXL 2200 VA / 1980 W
EDGE-3000IRT2UXL 3000 VA / 2700 W
3U EDGE-3000IRT3UXL 3000 VA /2700 W
MT
EDGE-750IMT 750 VA / 675 W
EDGE-1000IMT 1000 VA / 900 W
EDGE-1500IMT 1500 VA / 1350 W
LI (Lithium Ion) 2U
EDGELI-1500IRT2U 1500 VA / 1350 W
EDGELI-2200IRT2U 2200 VA / 1980 W
EDGELI-3000IRT2U 3000 VA / 2700 W
Table 2.1 EDGE Models
2 EDGE Description 3
Lieber EDGE Installer/User Guide
2.2 Rear Panel Views
Figure 2.1 Rear Panel
ITEM DESCRIPTION ITEM DESCRIPTION
1 Input circuit breaker 6 Non-programmable receptacles
2 AC input 7 Emergency Power Off (EPO) connector
3 USB communication port 8 Output circuit breakers
4 IntelliSlot port 9 Ground Screw
5 Programmable receptacles 10 External Battery Cabinet (EBC) connector
2 EDGE Description
4
Lieber EDGE Installer/User Guide
2.3 Front Panel
NOTE: For detailed descriptions of the LCD display. See Controls.
Figure 2.2 Controls and Display
ITEM DESCRIPTION
1 ESC/MUTE button. SeeControls, for details.
2 DOWN/LEFT button. SeeControls, for details.
3 UP/RIGHT button. See Controls, for details.
4 ENTER/ button. See Controls, for details.
2 EDGE Description 5
Lieber EDGE Installer/User Guide
2 EDGE Description
6
This page intentionally left blank
Lieber EDGE Installer/User Guide
3 Installation
3.1 What’s Included
EDGE UPS
Quick install guide
Safety and regulatory statements
USB type A to B cable
Rail kit box (except MT models)
Left and right rail set
12 x Rail kit screws (M5 x 14mm) (2U/3U models)
10 x Rail kit screws (M5 x 14mm) (1U models)
4 x Tower feet (2U and 3U models only)
2 x UPS rack ears with 8 x rack ear screws (M4 x8mm) (except MT models)
2 x IEC C13 to C14 output cables
Input power cables (500-1500VA models)
Input power cable IEC Schuko to IEC C13
Input power cable BS1362 to IEC C13
Input power cable AUS to IEC C13
Input power cables (2200-3000VA models)
Input power cable IEC Schuko to IEC C19
Input power cable BS1362 to IEC C19
Input power cable AUS to IEC C19
3.2 Unpacking and Inspection
Unpack the UPS and conduct the following checks:
Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier
and your local dealer or your Vertiv representative immediately.
Check the accessories included in packaging list. If there is any discrepancy, contact your local
dealer or your Vertiv representative immediately.
3 Installation 7
Lieber EDGE Installer/User Guide
3.3 Preparation for Installation
3.3.1 Installation Environment
Unpack the UPS and conduct the following checks:
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off.
The installation environment should meet the specifications listed in Specifications.
Confirm UPS installation area is an area of unrestricted air-flow around the unit, away from
water, flammable liquids, gases, corrosives, and conductive contaminants. Avoid direct sunlight.
The utility power outlet should be nearby and easily accessible.
This UPS is not for use in an Information Technology Equipment (ITE) room as defined in the
standard for the Fire Protection of Information Technology Equipment ANSl/NFPA 75.
NOTE: Operating the UPS in temperatures above 2 C reduces battery life.
3.3.2 Installation Clearances
Maintain at least 100 mm clearance in the front and rear. Do not obstruct the air inlets on the front panel
and rear panel. Blocking the air inlets reduces ventilation and heat dissipation, shortening the service life
of the UPS.
3.4 Installing the UPS
3.4.1 Installation Environment
The 2U and 3U UPS and optional battery cabinets (not supported on LI models) may be installed in a
tower or rack configuration. Determine the configuration that meets your application needs, see Tower
Installation below , or Rack-mount Installation on page10 .
Tower Installation
When using the UPS in a tower configuration, see Figure 3.1 below . If you have an external battery, see
Figure 3.2 on the facing page on the below page.
Figure 3.1 Attaching stands to the UPS
3 Installation
8
Lieber EDGE Installer/User Guide
ITEM DESCRIPTION
1 Connect the two halves of the stand together.
2 Place the UPS in the stands.
3 Make sure that the stands are installed 70 mm from the edge of the unit.
Figure 3.2 Attaching stands to the UPS and external battery
ITEM DESCRIPTION
1Connect the two halves of the stand to the spacer, after installing the additional stand components shown in item 4, and
install the securing screws.
2 Place the UPS and external battery pack in the stands.
3 Make sure that the stands are installed 70 mm from the edge of the unit.
4 Insert the stand expansion components and install the securing screws.
3 Installation 9
Lieber EDGE Installer/User Guide
Rack-mount Installation
CAUTION: Do not use the mounting brackets to lift the unit. Only use the mounting brackets to
secure the UPS to the rack.
To install the UPS or EBC in a rack see Figure 3.3 below .
Figure 3.3 Installing the UPS in a rack
ITEM DESCRIPTION
1 Attach the rack ears with four rack ear screws to the front right and left sides of the UPS.
2
Install the rear member of the rail onto the rack with one rail kit screw on the top and one on the bottom. Loosely tighten the
screws (finger tight). Slide the front member of the rail to the front of the rack and secure the two bottom holes to the rack
with two rail kit screws. Tighten all screws. Repeat for the second rail.
3Place the UPS with assembled rack ears onto the rail supports. The batteries may be temporarily removed for easier
installation (see Replacing the UPS Batteries).
4
For 2U/3U models: attach two rail kit screws to each UPS rack ear and rail to secure the UPS to the rack.
For 1U models: attach one rail kit screw to each UPS rack ear and rail to secure the UPS to the rack.
5If using an optional external battery cabinet (EBC), follow steps 1-4. However, batteries cannot be removed from an EBC in
step 3.
3 Installation
10
Lieber EDGE Installer/User Guide
CAUTION: Do not use the rack ears to lift the unit. Only use the rack ears to secure the UPS to
the rack.
3.4.2 Installing a Mini Tower (MT) Model
Place the unit upright, on its feet without blocking air inlets.
3.5 Connecting Loads
The UPS has non-programmable and programmable outlets. Plug your critical equipment (such as
computer, monitors, etc.) into the non-programmable outlets and your less-critical equipment (such as
printers and other less-often used peripherals) into the programmable outlets.
3.6 USB Communication Connection
Basic monitoring of the EDGE and unattended controlled shutdown of your computer in case of a power
failure can be done using the Vertiv Power Assist software via the USB port. Visit
www.vertiv.com/powerassist for additional information.
3.7 Emergency Power-off (EPO) Connection (Optional)
To comply with national and local wiring codes and regulations, the EPO connector internally disconnects
all power sources to the connected equipment. The default operation is "active open" which means you
must remove the factory installed jumper and connect to external contacts that are normally closed, but
open during a power-off event. The logic may be reversed in the Settings. If you do not use the EPO
connector, leave the factory-installed jumper in place and the default EPO settings in the Settings.
3 Installation 11
Lieber EDGE Installer/User Guide
3.8 External Battery Cabinet Connection on 2U and 3U VRLA
Models (Optional)
External battery cabinets provide longer battery run-time for connected devices. Refer to Specifications,
and Battery Run Times, to select the appropriate model and quantity for your PSI5 model and
applications. You can connect up to 6 battery cabinets to the 2U EDGE and 3U models. LI, MT, and 1U
models do not support external battery cabinets.
To connect an external battery pack:
1. Connect one end of the external-battery cable to the UPS and one end to the battery cabinet
as shown in Figure 3.4 below .
2. If connecting more than one external battery, connect one end of the external battery cable to
the second connector on the battery cabinet, the connect the other end to the next battery
cabinet as shown in Figure 3.4 below .
NOTE: After install and initial start-up, set the number of installed battery cabinets in the UPS Settings.
Figure 3.4 Connecting External Batteries
ITEM DESCRIPTION
1 Connection to second connector on external battery cabinet for additional battery cabinets.
2 Connection from UPS to single/first external battery.
3 Connect to next external battery.
4 Connection to UPS.
3 Installation
12
Lieber EDGE Installer/User Guide
3.9 Network Communication Card Connection (Optional)
Advanced monitoring and simple control of the EDGE can be done with the use of a Vertiv Liebert
IntelliSlot Unity Communications card. Visit www.vertiv.com/intellislot for additional information.
To install the card:
1. Remove the two screws and protective cover on the rear-panel Network Communications Port.
2. Insert the card into the port and secure it with the screws. Refer to the documentation with the
card or at the link above for cable connection and operation.
3. Refer to the documentation with the card or at www.Vertiv.com for cable connection and
operation.
3.9.1 Connecting AC Input
Ensure that all the loads are first powered off. Connect to an input-power supply/wall outlet that is
properly protected by a circuit breaker in accordance with national and local electrical codes. The input
receptacle must be grounded. See Specifications, for input cord rating. Once the UPS is plugged into the
wall outlet, it begins charging the battery.
NOTE: While every precaution has been taken to ensure that the battery is in good condition, we
recommend allowing the UPS to be plugged into AC input and to charge the battery for at least 12
hours prior to providing full back-up time protection for any utility-power abnormality.
3 Installation 13
Lieber EDGE Installer/User Guide
3 Installation
14
This page intentionally left blank
Lieber EDGE Installer/User Guide
4 Operations
4.1 Modes of Operation
4.1.1 Off Mode
The UPS input is plugged into a stable, nominal source, but the outlets are turned off. The internal
batteries are charging.
4.1.2 On/Normal Mode
The UPS input is plugged into a stable, nominal source, and the outlets are turned on. The internal
batteries are charging.
4.1.3 On/Automatic Voltage Regulation (AVR)/Boost1 Mode
The UPS input is plugged in, but the voltage source is somewhat low (brown-out). The UPS automatically
corrects the low voltage and allows the outlets to be on with the normal, expected voltage. The internal
batteries are charging.
4.1.4 On/Automatic Voltage Regulation (AVR)/Boost2 Mode
The UPS input is plugged in, but the voltage source is abnormally low (brown-out). The UPS automatically
corrects the low voltage and allows the outlets to be on with the normal, expected voltage. The internal
batteries are charging.
4.1.5 On/Automatic Voltage Regulation (AVR)/Buck Mode
The UPS input is plugged in, but the voltage source is abnormally high. The UPS automatically corrects
the high voltage and allows the outlets to be on with the normal, expected voltage. The internal batteries
are charging.
4.1.6 On/Battery Mode
The UPS input is not plugged in, or the voltage source has become extremely low or high and unusable.
The UPS automatically switches to the internal battery to provide normal, usable voltage to the outlets.
4.1.7 Fault Mode
An error or fault condition has occurred. The outlets are shut off.
4.1.8 Battery Self-test Mode
The UPS enters a cycle of approximately 10 seconds during which it tests the internal battery. The outlets
are still temporarily powered by the internal battery. Self-test mode occurs at the following instances:
At start-up turning the UPS on.
Automatically every 8 weeks as a self-check.
When selecting the Replace battery option under Control > Start/Stop battery manual test
4 Operations 15
Lieber EDGE Installer/User Guide
4.1.9 Controls
Figure 4.1 Display and Buttons on the front panel
ITEM FUNCTION DESCRIPTION
1 ESC/MUTE
Mute the alarm: Press and hold this button for at least 2 seconds to mute an active alarm.
Esc Key: Press this button to exit from menu or cancel the setting.
2 DOWN/LEFT Press this button to select the lower or left item in the menu, next page in the screen, or decrease the
number in the setting.
3 UP/RIGHT Press this button to select the upper or right item in the menu, previous page in the screen, or increase
the number in setting.
4 ENTER /
Enter: Press this button to enter the main menu from the flow screen, or use this button to select an
item when not in the flow screen.
Turn on/off the UPS: Press this button for at least 2 seconds to turn the UPS on (with confirmation
dialog if not a cold start) when the UPS is off, or turn the UPS off (with confirmation dialog) when the
UPS is on.
Table 4.1 Control-button descriptions
NOTE: Press any button quickly to wake the display.
4 Operations
16
Lieber EDGE Installer/User Guide
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68