Reznor OPT-FAN-CTRL is a replacement kit designed to easily upgrade discontinued fan control systems in duct furnaces and packaged systems equipped with a Thermocore® 1 heat exchanger. It includes a time delay wired relay assembly, mounting bracket, screws, fan control, fan control shield, and wire connectors. This kit allows for simple installation without the need for additional tools or expertise, ensuring proper and efficient operation of your heating system.

Reznor OPT-FAN-CTRL is a replacement kit designed to easily upgrade discontinued fan control systems in duct furnaces and packaged systems equipped with a Thermocore® 1 heat exchanger. It includes a time delay wired relay assembly, mounting bracket, screws, fan control, fan control shield, and wire connectors. This kit allows for simple installation without the need for additional tools or expertise, ensuring proper and efficient operation of your heating system.

Revision: OPT-FAN-CTRL (09-22) 209185-A
REPLACEMENT KIT (PN 209184) INSTALLATION
FOR DISCONTINUED FAN CONTROL
Supersedes: CP-Thermocore-1-FC (12-15) PN209185R6
ALL DUCT FURNACES AND PACKAGED SYSTEMS WITH
THERMOCORE® 1 HEAT EXCHANGER
⚠ DANGER ⚠
This replacement kit is to be installed by a qualified service agency in accordance with these
instructions and in compliance with all codes and requirements of authorities having jurisdiction.
Improper installation, adjustment, alteration, service, and/or maintenance can cause property
damage, injury, or death. The qualified agency performing this work assumes responsibility for
this installation.
The fan control used on heaters with a Thermocore® 1 heat exchanger has been discontinued by the manufacturer.
This kit is designed to replace the fan control and applies to all products using a Thermodisc #29T12-32517 fan
control (PN 10357).
Refer to the installation manual provided with the unit for important safety information.
Ensure that all components listed in Table 1 are available before beginning installation.
INSTALLATION
1. Turn OFF gas and disconnect electric power.
2. Remove control access panel, open electrical box cover (if provided), and locate existing fan control (see Figure 1).
DO NOT DESTROY. PLEASE READ CAREFULLY. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Table 1. Fan Control Replacement Kit (PN 209184) Components
Component Description PN (Quantity)
Time delay wired relay assembly SPST, includes relay PN 209164 (#12S20-305131) 209186 (1)
Bracket Mounting, relay 209167 (1)
Screw #10 × 3/8 96246 (1)
Fan control 125/90°F (#60T82-314585) 209166 (1)
Fan control shield Assembly 209169 (1)
Wire connector Twist-on, orange 16354 (2)
Figure 1. Obsolete Fan Control
3. Disconnect four wires from fan control. Save blue and red wires that connect to terminals 1 and 3 and discard
brown and black wires that connect to terminals A and B.
Limit
Control
2OPT-FAN-CTRL (09-22) 209185-A
INSTALLATION—CONTINUED
NOTE: Depending on model and unit size, the junction box may or may not have a heat shield.
4. If unit is equipped with junction box heat shield (see Figure 2), disconnect limit control (see Figure 1) wires.
Remove and discard heat shield and reconnect limit control wires.
Figure 2. Junction Box Heat Shield
5. Remove and save two screws that secure existing fan control (see Figure 1). Remove and discard control.
6. Install replacement fan control (see Figure 3):
a. Position replacement fan control in same location and slide fan control shield through hole in panel and insert
sensor side of fan control into shield.
b. Secure replacement fan control and fan control shield using two existing screws.
c. Connect blue and red wires to replacement fan control.
Figure 3. Replacement Fan Control and Fan Control Shield
7. Install time delay relay (see Figure 4):
a. Directly above fan control, remove and save two screws that secure patch plate to panel. Discard patch plate.
b. Position relay mounting bracket in same location. Orient bracket so that large tab is at top and small tab is at
bottom and align mounting holes.
c. Secure relay mounting bracket using two existing screws.
d. Secure time delay relay to mounting bracket using screw from kit.
Replacement
Fan Control
Fan
Control
Shield
3
OPT-FAN-CTRL (09-22) 209185-A
TIME
DELAY RELAY
(WIRES NOT SHOWN)
RELAY
MOUNTING
BRACKET
Figure 4. Time Delay Relay Assembly
8. Connect time delay relay wires in accordance with wiring diagram shown in Figure 5.
Figure 5. Wiring Diagram
9. Close electrical box cover (if provided) and install control access panel.
10. Turn ON electric and gas and check unit for proper operation.
1 3
FAN MOTOR OR
BL
BK BR
24V
LINE VOLT
DISCONNECT SWITCH
LINE/1 OR 3/60
GRD
G
31
R or BL
CONTACTS
R
FAN CONTROL
R
BLOWER RELAY
RELAY COIL
HH
TIME DELAY
24V
LINE VOLT
RELAY CONTACTS
BL
R or BL
R
TIME DELAY
13
R
1 3
CONTACTS
RELAY/CONTACTOR
BLOWER
FAN CONTROL
H
BK
H
BR
TIME DELAY
RELAY COIL
THERMOCORE I
FAN CONTROL
REPLACEMENT
KIT
DWG. #224201 REV. #2
BR
BR
REPLACEMENT
LIMIT
CONTROL
(SOME MODELS)
(NOTE 1)
(NOTE 2)
GAS VALVE
REPLACEMENT
GAS VALVE
(NOTE 1)
(NOTE 2)
NOTE 1 - SOME UNITS USE TERMINAL STRIPS RATHER THAN WIRE CONNECTORS.
NOTE 2 - INSTALL IN PLACE OF OLD FAN CONTROL HEATER.
NOTE 3 - LEAVE EXISTING LIMIT CONTROL INSTALLED AND WIRED ON UNIT.
NOTE 1 - SOME UNITS USE TERMINAL STRIPS RATHER THAN WIRE CONNECTORS.
NOTE 2 - INSTALL IN PLACE OF OLD FAN CONTROL HEATER.
NOTE 3 - LEAVE EXISTING LIMIT CONTROL INSTALLED AND WIRED ON UNIT.
RELAY CONTACTS
TIME DELAY
IF FAN CONTROL
IS IN 24V CONTROL
CIRCUIT:
IF FAN CONTROL IS
IN LINE VOLTAGE
CIRCUIT:
Specifications and illustrations subject to change without notice or incurring obligations.
Latest version of this manual is available at www.reznorhvac.com.
©2022 Nortek Global HVAC LLC, O’Fallon, MO. All rights reserved.
OPT-FAN-CTRL (09-22) 209185-A
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Reznor OPT-FAN-CTRL User manual

Type
User manual

Reznor OPT-FAN-CTRL is a replacement kit designed to easily upgrade discontinued fan control systems in duct furnaces and packaged systems equipped with a Thermocore® 1 heat exchanger. It includes a time delay wired relay assembly, mounting bracket, screws, fan control, fan control shield, and wire connectors. This kit allows for simple installation without the need for additional tools or expertise, ensuring proper and efficient operation of your heating system.