Danfoss 084B8120, 084B8020, 084B8024, 084B8030, 084B8032, 084B8036, 084B8070, 084B8073, 084B8128, 084B8130, 084B8162 User guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss 084B8120 User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
© Danfoss | DCS (mrb) | 2019.06
AU308671350171
1
This guide is to prevent false alarms during a scheduled night shutdown for a salad bar or
similar case.
1. Add a new Schedule in Configuration>Control>Refrigeration>Schedules.
Add 1 to the existing number.
2. Set the type to Night Setback and match the hours to your shutdown schedule.
AK-CC 550A Prevent High Temp
Alarms During Night Shutdown
Programming Guide
danfoss.us
3. On the Controllers tab, add the relevant controllers.
4. Set the Night Offset so the cutout + night offset will be close to room temp. This will increase
the alarm setpoint and prevent false alarming during a scheduled nightly case shutdown.
© Danfoss | DCS (mrb) | 2019.06
AU308671350171
2
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
/