This guide is to prevent false alarms during a scheduled night shutdown for a salad bar or
similar case.
1. Add a new Schedule in Configuration>Control>Refrigeration>Schedules.
Add 1 to the existing number.
2. Set the type to Night Setback and match the hours to your shutdown schedule.
AK-CC 550A Prevent High Temp
Alarms During Night Shutdown
Programming Guide
danfoss.us
3. On the Controllers tab, add the relevant controllers.
4. Set the Night Offset so the cutout + night offset will be close to room temp. This will increase
the alarm setpoint and prevent false alarming during a scheduled nightly case shutdown.