  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 210, 296, 310, A230 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210/296/310,applicationA230
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................12
2.3Mounting...........................................................13
2.4Placingthetemperaturesensors................................17
2.5Electricalconnections.............................................19
2.6InsertingtheECLApplicationKey..............................30
2.7Checklist............................................................37
2.8Navigation,ECLApplicationKeyA230.........................38
3.0Dailyuse.........................................................60
3.1Howtonavigate...................................................60
3.2Understandingthecontrollerdisplay..........................61
3.3Ageneraloverview:Whatdothesymbolsmean?...........64
3.4Monitoringtemperaturesandsystem
components........................................................65
3.5Influenceoverview................................................66
3.6Manualcontrol.....................................................67
3.7Schedule............................................................68
4.0Settingsoverview............................................69
5.0Settings...........................................................72
5.1IntroductiontoSettings..........................................72
5.2Flowtemperature..................................................73
5.3Roomlimit..........................................................78
5.4Returnlimit.........................................................81
5.5Flow/powerlimit.................................................87
5.6Windinfluence.....................................................92
5.7Optimization........................................................94
5.8Controlparameters..............................................100
5.9Compensation1.................................................105
5.10Compensation2.................................................107
5.11Application.......................................................109
5.12Heatcut-out......................................................118
5.13Alarm..............................................................121
5.14Alarmoverview..................................................126
5.15Twocirculationpumpsinsequence..........................127
6.0Commoncontrollersettings............................128
6.1IntroductiontoCommoncontrollersettings’..............128
6.2Time&Date.......................................................129
6.3Holiday............................................................130
6.4Inputoverview...................................................132
6.5Log.................................................................133
6.6Outputoverride..................................................134
6.7Keyfunctions.....................................................135
6.8System.............................................................137
7.0Miscellaneous................................................144
7.1ECA30/31setupprocedures.................................144
7.2Overridefunction................................................152
7.3Severalcontrollersinthesamesystem......................155
7.4Frequentlyaskedquestions....................................158
7.5Definitions........................................................162
7.6Type(ID6001),overview.......................................166
7.7Automatic/manualupdateoffirmware.....................167
7.8ParameterIDoverview..........................................168
©Danfoss|2019.07VI.LG.H5.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA230
(ordercodeno.087H3802).
TheECLApplicationKeyA230contains4subtypes,applicablein
ECLComfort210,296and310:
A230.1:Temperaturecontrolinheatinginstallations.Optional
compensationfromwind.
A230.2:Temperaturecontrolincoolinginstallations.Optional
externalsignal(0-10V)fortemperaturesetpoint.
A230.3:Temperaturecontrolinheatinginstallations.
Compensationforhighrelativehumidity.Optional
compensationfromwind.
A230.4:Temperaturecontrolinheatinginstallations.Optional
externalsignal(0-10V)fortemperaturesetpoint.Additional
temperatureandpressuremonitoringincluded.
TheA230applicationkeyalsocontainsaFloor(Screed)Drying
ProgramforthesubtypesA230.1,A230.3andA230.4.Seeseparate
documentation.(InEnglishandGermanlanguageonly).
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
Theapplicationdiagramsshowmandatorytemperaturesensors
withanunderscore;exampleS3
.
Thedescribedfunctionsarerealizedin:
ECLComfort210forbasicsolutions
ECLComfort296forbasicsolutions,inclusiveM-bus,Modbus
andEthernet(Internet)communication
ECLComfort310foradvancedsolutions,inclusiveM-bus,
ModbusandEthernet(Internet)communication.Theextension
moduleECA32canbeused,viaa0-10Voltoutput,to
controlamodulatedactuator,forexampleDanfosstypesAME.
FurthermoretheextensionmoduleECA32canbeusedfor
extendingthenumbersofinputsformonitoringviatheECL
Portal.EachinputcanbeconfiguredasPt1000,0-10Voltor
digital.
TheApplicationKeyA230complieswithECLComfort210/310
controllersasoffirmwareversion1.11.
TheApplicationKeyA230compliesalsowithECLComfort296
controllersasoffirmwareversion1.58.
Thefirmware(controllersoftware)versionisvisibleatstart-upof
thecontrollerandin‘Commoncontrollersettings’in‘System’ .
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedforremotemonitoringandsetting.Thebuilt-inroom
temperaturesensorcanbeutilized.
ECLPortal,Internetbasedconnection,allowsECL296,310and
310Btobemonitoredandcontrolledremotelyviastandard
Internetbrowsers(forexampleInternetExplorer,GoogleChrome
andSafari).
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
2|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Serviceandsupport>Downloads>
Tools>Heating>ECLTool.
TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
ECLComfort296isavailableas:
ECLComfort296,230volta.c.(087H3000)
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort296,230volt(087H3240)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com/
orhttp://store.danfoss.com.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
VI.LG.H5.02
©Danfoss|2019.07|3
OperatingGuideECLComfort210/296/310,applicationA230
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
4|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
1
2
174
-
Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.LG.H5.02
©Danfoss|2019.07|5
OperatingGuideECLComfort210/296/310,applicationA230
2.0Installation
2.1Beforeyoustart
TheapplicationA230isveryflexible.Thesearethebasicprinciples:
Heating(applicationA230.1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Bymeansofaweekschedule,theheatingcircuitcanbein
‘Comfort’or‘Savingmode.Theweekschedulecanhaveupto3
‘Comfort’periods/day.Avalueforthedesiredroomtemperature
canbesetineachofthemodes.
InSavingmodetheheatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot
betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent
oftheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
Ifthemeasuredroomtemperature(directlyconnectedtemperature
sensorESM-10(S2)orRemotecontrolunitECA30/31)doesnot
equalthedesiredroomtemperature,thedesiredflowtemperature
canbeadjusted.
Thecirculationpump,P1,isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.WhenthissubtypeisusedinanECLComfort296or310the
flow/energysignalcanalternativelycomeasanM-bussignal.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
Tocompensatefortheinfluenceofwind,awindspeedsensorcan
beconnected.Basedonthewindspeedsensorsignal(0-10V),the
controllercanbesettoincreasethedesiredflowtemperaturein
relationtoincreasedwindspeed.
Unusedinputs(fromS7andup)can,bymeansofanoverride
switchorrelaycontact,beusedforoverridingthescheduletoa
fixed'Comfort','Saving','Frostprotection'or'Constanttemperature'
mode.
Analarmcanbeactivatediftheactualflowtemperaturediffers
fromthedesiredflowtemperature.
TypicalA230.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296/
310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
(Optional)Roomtemperaturesensor/ECA30
S3
Flowtemperaturesensor
S4
(Optional)Supplyflowtemperaturesensor
(read-outonly)
S5
(Optional)Returntemperaturesensor
S7
(Optional)Flow/energymeter(pulsesignal)
S8
(Optional)Windspeedsignal(0-10V)
P1
Circulationpump
P2
(notillustrated)RelayoutputforSchedule2
M1
Motorizedcontrolvalve,3-pointcontrolled
Alternative1:Controlvalve,thermo-actuator
controlled(DanfosstypeABV)
Alternative2(ECL310withECA32):Motorized
controlvalve,0-10Voltcontrolled
A1
Alarm
TheA230.1applicationcanutilizeaconnectedflow/energymeter
tolimittheflow/power.
6|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
Cooling(applicationA230.2):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3issetinthe
ECLcontroller.Furthermore,theoutdoortemperature(S1)can
influencethedesiredflowtemperature.Thehighertheoutdoor
temperature,thelowerthedesiredflowtemperature.
Bymeansoftheweekschedule,thecoolingcircuitcanbein
‘Comfort’or‘Savingmode(twovaluesforthedesiredflow
temperature).
Theweekschedulealsocontrolstwovalues(‘Comfortand
‘Saving’)forthedesiredroomtemperature.Ifthemeasuredroom
temperaturedoesnotequalthedesiredroomtemperature,the
desiredflowtemperaturecanbeadjusted.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureishigherthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5tothecoolingsupplyshouldnotbetoo
low.Ifso,thedesiredflowtemperaturecanbeadjusted(typicallyto
ahighervalue),thusresultinginagradualclosingofthemotorized
controlvalve.
Thecirculationpump,P1,isONatcoolingdemand.
Anexternalsignalforthedesiredflowtemperaturecanbeapplied
asa0–10voltsignaltotheterminalsforS8.
Aconnectedfloworenergymeterbasedonpulses(S7)canlimit
thefloworenergytoasetmaximumvalue.
WhentheA230.2isusedinanECLComfort296/310theflow/
energysignalcanalternativelycomeasanM-bussignal.
Thestandbymodemaintainsaselectableflowtemperature,for
example30°C.
Unusedinputs(fromS7andup)can,bymeansofanoverride
switchorrelaycontact,beusedforoverridingthescheduletoa
fixed'Comfort'or'Saving'mode.
ThetemperaturesS4andS6areusedformonitoringpurposesonly.
Theschedulein"Commoncontrollersettings"controlstherelays
2and3.Thiscanbeutilizedforshiftingbetweentwocirculation
pumps.
Seetheinstallationguide,appl.A230.2,ex.dandrelatedelectrical
connections.
TypicalA230.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
/310
ElectroniccontrollerECLComfort210,296or310
S1
(Optional)Outdoortemperaturesensor
S2
(Optional)Roomtemperaturesensor/ECA30
S3
Flowtemperaturesensor,cooling
S4
(Optional)Supplyflowtemperaturesensor(read-out
only)
S5
(Optional)Returntemperaturesensor
S6
(Optional)Returntemperaturesensor(read-outonly)
S7
(Optional)Flow/energymeter(pulsesignal),not
illustrated
(S8)
(Optional)(Externalvoltage(0–10V)forexternal
settingofdesiredflowtemperature)
P1
Circulationpump
P2/P3
Schedule2
M1
Motorizedcontrolvalve,3-pointcontrolled
Alternative1:Controlvalve,thermo-actuator
controlled(DanfosstypeABV)
Alternative2(ECL310withECA32):Motorized
controlvalve,0-10Voltcontrolled
TheA230.2applicationcanutilizeaconnectedflow/energymeter
tolimittheflow/power.
VI.LG.H5.02
©Danfoss|2019.07|7
OperatingGuideECLComfort210/296/310,applicationA230
Heating(applicationA230.3):
ThissubtypeworkslikeA230.1,buttheflow-orenergylimitation,
basedonpulsesignalisnotimplemented.Ifflow-orenergy
limitationisneeded,theM-Busbasedsignalcanbeused(ECL
Comfort296or310).
Inaddition,A230.3canminimizetheriskofdew(condensation).
TheRH(RelativeHumidity)signalcanarrangeaminimumdesired
roomtemperatureforprotectionagainstdew(condensation).
Dewcanoccurwhenairwithhightemperatureandhumidity
comestocolderwalls,forexampleinchurches,castlesandother
thick-wallbuildings.
Theequation-
T.dew=(0.96xT.room)+(0.25xRH)-22.4
isusedforcalculationofthedewtemperature(T.dew).
T.roomisthemeasuredroomtemperature.RHistheRelative
Humidity,basedonmeasuredroomtemperatureandhumidity.
RoomtemperatureandRHcomeseitherfrom
theRemoteControlUnitECA31
or
aroomtemperaturesensorandanappliedRHsignal,0-10
Volt,toS7.
TherelationshipbetweenappliedvoltageandrelatedRHvalue
canbeset.
AnOffsetvalueforthecalculateddewtemperature(T.dew)canbe
addedforcompensationbetweenwallandroomtemperatures.
Favoritedisplay1canshowthefollowing:
RHvalue:76.3%
Roomtemperature:20.9°C
Desiredroomtemperature:19.5°C
Minimumdesiredroomtemperature,inclusive6Koffset:22.7°C
TypicalA230.3application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
/310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
(Optional)Roomtemperaturesensor/ECA31
S3
(Mandatory)Flowtemperaturesensor
S4
(Optional)Supplyflowtemperaturesensor(read-out
only)
S5
(Optional)Returntemperaturesensor
S7
(Optional)RHsignal(0-10V)
S8
(Optional)Windspeedsignal(0-10V)
P1
Circulationpump
P2
(notillustrated)RelayoutputforSchedule2
M1
Motorizedcontrolvalve,3-pointcontrolled
Alternative1:Controlvalve,thermo-actuator
controlled(DanfosstypeABV)
Alternative2(ECL310withECA32):Motorized
controlvalve,0-10Voltcontrolled
A1
Alarm
8|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
Heating(A230.4)
ThissubtypeworksassubtypeA230.1,butthewindinfluence
functionalityisnotimplemented.
Inaddition,A230.4canmonitorDHW(DomesticHotWater)
temperaturesS4andS6.
Anappliedvoltagesignal(0-10Volt)toS8canbeusedfor:
pressuremeasuring.ThevoltageisconvertedintheECL
controllertoapressure,measuredinbar
or
settingthedesiredflowtemperature.Thevoltageisconverted
intheECLcontrollertoatemperaturevalue.
TypicalA230.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210/296
/310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
(Optional)Roomtemperaturesensor/ECA30
S3
Flowtemperaturesensor,
S4
(Optional)DHWflowtemperaturesensor(read-out
only)
S5
(Optional)Returntemperaturesensor
S6
(Optional)DHWcirculationreturntemperature
sensor(read-outonly)
S7
(Optional)Flow/energymeter(pulsesignal)
S8
(Optional)0-10Voltsignalfrompressuresensor
Alternative:0-10Voltsignalforexternalsettingof
desiredflowtemperature
P1
Circulationpump,heating
M1
Motorizedcontrolvalve,3-pointcontrolled
Alternative1:Controlvalve,thermo-actuator
controlled(DanfosstypeABV)
Alternative2(ECL310withECA32):Motorized
controlvalve,0-10Voltcontrolled
A1
Alarm
VI.LG.H5.02
©Danfoss|2019.07|9
OperatingGuideECLComfort210/296/310,applicationA230
A230,ingeneral:
UptotwoRemoteControlUnits,ECA30/31,canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingorcoolingdemandcanbearranged.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.
SeveralECLcontrollers,internallyconnectedviaECL485bus,work
inMaster/Slaveconnection.InaMaster/Slavesystemmaximum
2ECA30/31canbepresent.
Anunusedinputcan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed:
(A230.A230.3andA230.4):
'Comfort','Saving' ,'Frostprotection'or'Constanttemperature'
mode
(A230.2):
'Comfort'or'Saving'mode
Heat-meters:
Upto5heat-meterscanbeconnectedtotheM-busterminals(ECL
296/310).
DatacanbetransferredtotheSCADAsystemviaModbusandTCP/
IPtotheECLPortal.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdata(ECLComfort296/310)canfurthermorebe
transferredtotheModbuscommunication.
Alarm
A230.1andA230.3:
AlarmA1(=relay4)canbeactivatedif:
theactualflowtemperaturediffersfromthedesiredflow
temperature.
atemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
A230.2:
Alarmrelay4isnotused,butatemperaturesensororits
connectionscanbemonitored.
(See:Commoncontrollersettings>System>Rawinputoverview).
A230.4:
AlarmA1(=relay4)canbeactivatedif:
theactualflowtemperaturediffersfromthedesiredflow
temperature.
theactualpressureisnotinsideanacceptablepressurerange
atemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
Offsetadjustment
Ameasuredtemperaturecanbeoffsetadjusted,ifneeded.
(Navigation:MENU>Commoncontroller>System>Sensoroffset)
Inputconfiguration
Inputs(asfromS7andup)whicharenotpartoftheapplicationcan
beconfiguredtobePt1000,0-10Volt,frequency(pulsecounter)
orDigitalinput.ThisfeaturemakesitpossibleinECL296/310to
communicateextrasignals,suchastemperatures,pressures,ON/
OFFconditions,viaModbusandECLPortal.
TheconfigurationisdonebymeansoftheECLTool(freesoftware
fordownload)ordirectlyinadedicatedmenuintheECLPortalor
theconnectionforModbus(BMS/SCADA).
10|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
A230,ingeneral(continued):
Applicationupload
Theapplicationuploadprocedureisthefollowingafterhaving
powereduptheECLComfortcontroller:
1.Inserttheapplicationkey
2.Selectlanguage
3.Selectsubtype(theInstallationGuideshowssubtypes)
4.SetTimeandDate
TheECLComfortcontrollerinstallstheapplication,initializesand
restarts.Outputrelaysareactivated/de-activated(click-sounds
fromthiscanbeheard).Thisalsomeansthat,forexample,
circulationpumpscanbeswitchedONandOFFshortly.
Commissioning
WhentheA230applicationhasbeenuploadedtheECLComfort
controllerstartsinManualmode.Thiscanbeusedtoverifycorrect
connectionsoftemperature,pressureandflowsensors.Also
verifyingthecontrolledcomponents(valveactuators,pumpsetc.)
forcorrectfunctionalitycanbedone.
Theapplicationkeyisdeliveredwithfactorysettings.
Dependingonsystemtype,itmightbenecessarytochangesome
factorysettingsindividuallyinordertooptimizethefunctionality.
Theapplicationkeymustbeinsertedinordertochangesettings.
Power-down/power-up
WhenthepowersupplytotheECLComfortcontrolleris
disconnected(power-down),theoutputrelaysgotode-activated
position.
Thismeansthat,forexample,circulationpumpscanbeswitched
ON.
SeetheelectricalconnectiondiagramsintheInstallationGuide.
Allrelaycontactsareshowninde-activatedsituation.Somerelay
contactsareclosed,somerelaycontactsareopen.
WhenthepowersupplytotheECLComfortcontrolleris
re-established(power-up),theoutputrelaysareactivated/
de-activated(click-soundsfromthiscanbeheard).Thisalsomeans
that,forexample,circulationpumpscanbeswitchedONandOFF
shortly.
Important:
Setthecorrectrunningtime"Mrun"oftheMotorizedControl
ValveM1.(Circuit1>MENU>Settings>Controlparameters
>Mrun).
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
VI.LG.H5.02
©Danfoss|2019.07|11
OperatingGuideECLComfort210/296/310,applicationA230
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
12|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
VI.LG.H5.02
©Danfoss|2019.07|13
OperatingGuideECLComfort210/296/310,applicationA230
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
14|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
VI.LG.H5.02
©Danfoss|2019.07|15
OperatingGuideECLComfort210/296/310,applicationA230
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
16|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturers
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturers
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
VI.LG.H5.02
©Danfoss|2019.07|17
OperatingGuideECLComfort210/296/310,applicationA230
Pt1000temperaturesensor(IEC751B,1000Ω/0°C)
Relationshipbetweentemperatureandohmicvalue:
18|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
Warning
ElectricconductorsonPCB(PrintedCircuitBoard)forsupplyvoltage,
relaycontactsandtriacoutputsdonothavemutualsafetydistanceof
minimum6mm.Theoutputsarenotallowedtobeusedasgalvanic
separated(voltfree)outputs.
Ifagalvanicseparatedoutputisneeded,anauxiliaryrelayis
recommended.
24Voltcontrolledunits,forexampleactuators,aretobecontrolledby
meansofECLComfort310,24Voltversion.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
VI.LG.H5.02
©Danfoss|2019.07|19
OperatingGuideECLComfort210/296/310,applicationA230
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Afor
inductiveload)
Triac(=electronic
relay)terminals
0,2A/230Va.c.
A230.2(cooling):2-pumpcontrol
ApplicationA230.2,ex.disanexampleforscheduledshiftbetween
twocirculationpumps.
ControlofP1isbasedonthecoolingdemandanddetermines
viaK1theON/OFFcontrolofthepumpsP2andP3.P2andP3
arerelatedtotheoutputoftheschedulein"Commoncontroller
settings".
TheelectricdiagramforA230.2,P2andP3showsanexamplefor
connection.
20|©Danfoss|2019.07
VI.LG.H5.02
OperatingGuideECLComfort210/296/310,applicationA230
/