5
I-F&B-PV (09-20) 97967-A
Figure 3. Flue Restrictor and Flue Adapter Assembly Installation
5. Remove existing flue collar assembly:
a. For unit sizes 025, 050, 075, 100, 130, 165, and 200: remove and discard factory-installed flue collar assembly
(if heater was manufactured before OCT 1989, it has fixed vertical vent outlet so there is nothing to remove).
b. For unit size 125: if heater is already installed, remove and discard flue collar plate with 7-inch collar. If heater
has not been installed, proceed to step 6.
c. For unit sizes 250, 300, and 400: if heater is already installed, remove and discard flue collar assembly and
cover plate. If heater has not been installed, proceed to step 6.
6. Install flue adapter assembly:
a. For unit sizes 025, 050, 075, 100, 130, 165, and 200: install flue adapter assembly in accordance with Table 3.
b. For unit size 125: if heater is already installed, replace flue collar assembly removed in step 5a with flue
adapter assembly using sheet metal screws in existing holes. If heater has not been installed, install flue
adapter assembly in accordance with Table 3.
c. For unit sizes 250, 300, and 400: install flue adapter assembly as follows. If heater has not been installed,
install flue adapter assembly in accordance with Table 3.
(1) Center flue adapter assembly (with flue restrictor installed in step 4) on top of heater. Align flue adapter
assembly holes (see Figure 3) and mark three new screw holes on top of heater.
(2) Remove flue adapter assembly and drill holes marked in step 6c(1) using 1/8-inch drill bit.
(3) Secure flue adapter assembly to heater using five sheet metal screws.
FLUE ADAPTER ASSEMBLY
FLUE ADAPTER ASSEMBLY HOLES
FLUE RESTRICTOR HOLES
UNIT SIZE
125 FLUE
RESTRICTOR
HOLES
DETAIL A
Table 3. Flue Adapter Assembly Installation
Unit Size
025, 050, 075, 100, 130, 165, 200 125 250, 300, 400
1. Center flue adapter assembly (with flue
restrictor installed) on top of heater over flue
outlet support.
NOTE: The flue collar assembly with the
7-inch oval flue collar provided with the
heater is not used.
NOTE: None of the flue outlet pieces
shipped with the heater are used.
2. Align flue adapter assembly holes (see
Figure 3) and mark three new screw holes on
top of heater.
1. Assemble flue outlet using flue collar
support and flat cover provided with heater
and flue adapter assembly (with flue restrictor
installed).*
1. Remove two center screws (one of each
side) that secure flue outlet pieces in place for
shipping. Discard all three pieces and parts
bag.
3. Remove flue adapter assembly and drill
holes marked in step 2 using 1/8-inch drill bit.
2. Attach flue collar support as instructed.
2. Center flue adapter assembly (with flue
restrictor installed) on top of heater.
4. Secure flue adapter assembly to heater
using five sheet metal screws.
3. Secure flue outlet assembled in step 1 to
heater and attach flat cover plate.
3. Align flue adapter assembly holes (see
Figure 3) and mark three new screw holes on
top of heater.
4. Remove flue adapter assembly and drill
holes marked in step 3 using 1/8-inch drill bit.
5. Secure flue adapter assembly to heater
using five sheet metal screws.
*Refer to the instructions in the heater installation manual or in form I-F/B-HV125 in the standard vent outlet hardware bag (manuals are also
found online at www.reznorhvac.com).