FIELD CONTROLS CV-4VR & CV-5VR Sidewall Power Venter Kit Installation guide

Type
Installation guide
2630 AIRPORT ROAD · KINSTON, NC 28504
Phone: 252-522-303 Fax: 252-522-0214
www.fieldcontrols.com
SIDEWALL POWER VENTER KIT
Model: CV- 4VR, -5VR Vent Riser Models
*Patented
TYPICAL VENTING SYSTEM COMPONENTS
1 CV-VR Series Power Venter 1 - CK Series Control Kit (sold separately)
OPTIONAL SYSTEM COMPONENTS
FOR MOST MULTIPLE HEATING EQUIPMENT SYSTEMS
One CK Series Control Kit for each appliance. Except for a 24V gas furnace or boiler and a 30mV water
heater multiple venting system, use the CK-90 Series Control Kit.
CONTENTS
Available Control Kits............................................... 2 Maintenance..................................................... 10
Installation Instructions ............................................ 2 General Inspection ........................................... 10
Wiring ...................................................................... 9 Repair Parts ..................................................... 11
Air Flow Adjustments .............................................. 9 System Information .......................................... 11
GENERAL SYSTEM INFORMATION
This sidewall power venting kit is designed for installations requiring additional ground clearance for high snow
levels and/or low elevation of vent penetration through the wall, and is designed for operation with natural gas, LP
gas and #2 fuel oil appliances. It also features a combustion air inlet for connection to the burner, which may be
used if desired
1. The thermostat (wall thermostat or aquastat) calls for heat and energizes a relay which activates the power
venter. After the venter motor has come up to speed, the pressure switch closes. This closes the circuit to the
burner and allows the burner to fire.
2. For millivolt controlled water heaters using the CK-20 Series Control Kit, the gas valve pressure switch
activates the power venter at the same time as the burner fires.
3. After the heating requirement has been satisfied, the thermostat circuit will open and de-activate the burner
and power venter circuit.
4. For venting systems equipped with a post purge device, the power venter operates for a period of time after
the burner has shut off to purge remaining flue gases.
This device MUST be installed by a qualified agency* in accordance with the manufacturer’s
installation instructions.
The definition of a qualified agency is: any individual, firm, corporation or company which either in
person or through a representative is engaged in, and is responsible for, the installation and operation of
oil appliances, who is experienced in such work, familiar with all the precautions required, and has
complied with all the requirements of the authority having jurisdiction.
DO NOT DESTROY
THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT
CK series control kit sold
separately
Page 2
CONTROL KITS
CK-20F/HWK: For operation with 30 or 750 millivolt gas-fired water heaters, gas-fired space heaters and gas-fired pool or
spa heaters with an internally mounted thermostat. Includes a fixed post purge.
CK-21: For operation with gas-fired instantaneous water heaters with a pressure tap port in the burner manifold.
CK-40F/41F: For operation with gas-fired furnaces, boilers, unit heaters and water heaters operating with a 24 VAC gas
valve. For systems not equipped with factory mounted spillage switches, use the CK-41F which includes
two GSK-3 spill switches. Includes a fixed post purge.
CK-43/43F: For draft induced 24 VAC gas valve systems. Includes a 4" MG-1 draft control and electronic post purge.
The CK-43F includes a fixed post purge.
CK-61: For operation with oil-fired systems. Has electronic post purge.
CK-62: For operation with oil-fired systems. Has thermally activated post purge.
CK-63: For operation with oil-fired systems. Has electronic post purge. For operating venter with or without burner
motor.
CK-81: For operation with 750 millivolt operated boilers, furnaces, water heaters, pool or spa heaters and gas-fired
fireplaces when operating with remote mounted thermostat. Operated off a 24 VAC thermostat. For
operation off of a 120 VAC thermostat or wall switch, use the CK-80.
CK-91/91F: For gas fired draft induced 24 VAC gas valve systems and a 30 millivolt operated water heater. Includes a
4" MG-1 draft control and an electronic post purge. The CK-91F includes a fixed post purge.
CK-92*/92F: For operation with gas-fired furnaces, boilers, unit heaters and water heaters operating with a 24 VAC gas
valve and a 30 millivolt operated water heater. Includes an electronic post purge. The CK-92F includes a
fixed post purge.
INSTALLATION SAFETY INSTRUCTIONS
CAUTION: This device must be installed by a qualified installer in accordance with the manufacturer's installation
instructions. Appliances should have a minimum of 75% combustion efficiency or have a maximum measured flue gas
temperature of 650°F US/575°F CA at the inlet of the power venter.
1. The power venting system must be installed by a qualified installer. "Qualified Installer" shall mean an individual who
has been properly trained or a licensed installer. The installer must write or imprint his name, phone number and date of
installation on the installation tag. The tag should be attached to the power venting system control kit box or power
venter unit. Recording burner and venting system initial operational information is strongly recommended as a guide for
service or burner tune-up. Enter this on the back page of this manual.
2. Safety inspection of a venting system should be performed before and after installing a power venting system on an
existing or new appliance. Procedures to follow are those recommended by the National Flue Gas Code A.N.S.I.Z223.1,
or refer to the General Installation Inspection section of this manual.
3. Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed wiring or
plumbing inside walls.
4. Single wall vent pipe (refer to Diagram B) may be used to join an appliance to the venting system, but if proper
clearances cannot be maintained from combustible materials, Class B Vent Pipe should be used for gas appliances
and Class L Type Vent Pipe for oil appliances. Refer to national or local codes for guidelines.
5. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
6. This equipment is designed to overcome minor negative pressure conditions. To ensure extreme negative pressure
does not exist, follow the General Installation Inspection section of this manual.
7. Heating appliances equipped with draft hoods, such as boilers or furnaces, LP gas appliances and Natural gas
appliances SHOULD have a secondary spillage switch installed. On appliances without draft hoods, it is recommended
that a secondary safety switch such as a WMO-1, GSK, FTS, or TSP-1 be used. Gas-fired 30 millivolt power systems
MUST be equipped with a spillage switch.
8. Air flow adjustment MUST be made to ensure appliance efficiency. This should be done at the appliance exhaust outlet
with a velocity meter, draft gauge or by "match test procedure". A match test is in accordance with National Fuel Gas
Code A.N.S.I.Z223.1, Section 8.6.
9. On oil-fired and gas-fired heating appliances not equipped with a draft hood, a barometric draft control MUST be
installed to regulate proper air flow and fluctuations in the system's air flow during operation. Fluctuations may come
from wind loads on the outlet of the power venter, house de-pressurization during windy days and the different house
ventilation requirements between summer and winter operation. For gas appliances, use a Field Controls Type MG-1
Barometric Draft Control. For oil appliances use a Field Controls Type M or RC Barometric Draft Control. Gas-fired draft
induced systems should have a single-acting barometric draft control installed.
Page 3
INSTALLATION OF CV-*VR POWER VENTER (See Table 1)
Table 1
UNIT SIZING CHART
OIL
GAS
MAXIMUM EQUIVALENT FEET OF
VENT PIPE
MAX*
OIL
GPH
INPUT
MAX**
BTU/HR.
IMPUT
AT MAX BTU/HR
INPUT
AT 60% OF MAX
BTU/HR INPUT
VENTING WITH
VENT PIPE
SIZE
MODEL
1.10
170,000
18
83
4"
CV-4VR
48
100
5"
100
100
6"
100
100
7"
1.85
290,000
-
25
4"
CV-5VR
32
81
5"
76
100
6"
100
100
7"
*Rating at 100 psi. Sizing based on appliance maximum input rate not actual firing rate. **Do not exceed maximum BTU/HR input rating or maximum oil GPH
input. For multiple venting system applications, add the input for each appliance. Category I gas-fired draft induced systems require a CV-4 or larger. Category
III gas-fired draft induced systems require a CV-5 or larger.
PROCEDURE FOR CALCULATING TOTAL EQUIVALENT PIPE LENGTH IN FEET
1. Calculate the total equivalent feet for each type of fitting used in the venting system from the chart below.
2. Calculate the total amount of feet for the straight lengths of vent pipe.
3. Add the equivalent feet for the fitting with the total amount of feet of straight lengths. This will approximate the total
equivalent feet of the vent system.
Table 2
EQUIVALENT LENGTH (FEET) OF VENT PIPE FOR VENT PIPE FITTING
VENT PIPE DIAMETER
VENT PIPE FITTINGS
3”
4”
5”
6”
7”
8”
9”
10”
TEE
19
25
31
38
44
50
56
63
90° ELBOW
5
7
9
11
12
14
16
18
45° ELBOW
3
4
4
5
6
7
8
9
SUDDEN REDUCER
OR INCREASER
FOR 3 *RATIOS (d/D)
d/D
1/4
8
11
14
17
19
22
25
28
1/2
5
7
8
10
12
13
15
17
3/4
2
3
3
4
4
5
6
6
*Reducer or increaser ratio (d/D) small diameter divided reducer ratio
is d/D = 4/8 = 1/2. To estimate the equivalent foot length for the
fitting, use the smaller pipe diameter for the equivalent length figure.
Example 4" to 8" reducer; the reducer ratio is 1/2 and the smaller pipe
diameter is 4". So, from the chart, the equivalent feet would be 7 feet.
(See Figure 1)
Example: System Pipe Size = 4"
Step 1 Two 4" 90° elbows @ 7 feet each = 14 ft.
Step 2 Ten 2 foot lengths of 4" pipe = 20 ft.
Step 3 Total equivalent feet = 14 ft. + 20 ft. = 34 ft.
Figure 1
Page 4
INSTALLATION
CAUTION: Failure to install, maintain and/or operate the power venting system in accordance with manufacturer's
instructions will result in conditions which may produce bodily injury and/or property damage.
1. Remove power venter from box and inspect unit for damage. If the carton has been crushed or mutilated, check unit
very carefully for damage. Rotate blower wheel to insure that the motor and blower wheel rotate freely. DO NOT install
if any damage is apparent. Refer to unit sizing chart to check proper venting sizing.
2. Location of the termination of the venting system should be installed in accordance with the National Fuel Gas Code
A.N.S.I.Z223.1, manufacturer's recommendations and/or local codes which are applicable. See requirements below or
refer to installation location, Diagram A, for typical locations.
a. The exit termination of mechanical draft systems shall not be less than 7' above grade when located adjacent to
public walkways.
b. A venting system shall terminate at least 3' above any forced air inlet located within 10'.
c. The venting system of other than a direct vent appliance shall terminate at least 4' below, 4' horizontally from or 1'
above any door, window or gravity air inlet into the building.
d. The vent termination of a direct vent appliance with an input of 50,000 BTU's per hour or less, shall be located at
least 9" from any opening through which vented gases could enter the building. With an input over 50,000 BTU's per
hour, a 12" termination clearance shall be required.
e. The vent termination point shall not be installed closer than 3' from an inside corner of an L-shaped structure.
f. The vent termination should not be mounted directly above, or within 3' horizontally from an oil tank vent or gas
meter.
g. The bottom of the exterior portion of the vent terminal (excluding the riser section) shall be located at least 12"
above the surrounding finished grade or well/sill structure (see Well Installation Illustration).
3. Determine the venting system termination location (See Diagram A) and prepare the installation area: If the vent
penetration through the wall must be near or below the surrounding grade, provision must be made to protect the riser
section from standing water that could reach the level of the bottom of the riser section, such as a well structure with
adequate drainage and protection from water runoff. If a well structure is employed, adequate clearance from the walls
of the well to the riser section is required to allow for installation, inspection and cleaning of debris. It is recommended
that a sill structure and grating be employed to help prevent water and debris entry into the well (see Well Installation
Illustration). Refer to local building codes governing such structures.
4. Prepare the CV-VR series power venter for installation:
a. Extend the inner pipe of the tailpiece assembly (see Install 1, on pg 6), and using the supplied silicone sealant,
apply a bead of sealant around the end of the inner pipe of the tailpiece assembly.
b. Insert the tailpiece inner pipe into the riser inlet collar fully, and tighten the hose clamp to secure the inner pipe into
the collar (see Install 2, on pg 6).
c. Slide the tailpiece outer pipe up to the back of the riser section, and attach the outer pipe flange to the back of the
riser section using the four supplied sheet metal screws (see Install 3, on pg 6). Note: do not use the self-drilling
screws, which are for installation of the backing plates (see “Two-Piece Backing Plate Installation” section).
Well Installation
Page 5
Figure 2
Figure 3
d. Uncoil about 2 feet of the ¼” aluminum CK kit tubing (supplied with CK kit), and attach the straightened end to the
pressure port fitting on the back of the riser, using the supplied compression gland and nut (See Install 4).
5. Cut a square hole for the tailpiece through the wall to the minimum dimensions given in Table 5, “Installation Hole
Dimensions” (note that the tailpiece is offset from the actual termination).
6. Apply a bead of the supplied silicone sealant to the back of the top and sides of the riser section mounting flange, and
mount the power venter on the wall, making sure to pass the flexible conduit and pressure tubing through the wall, and
keeping the outer pipe centered in the hole (see Figure 2). Fasten the power venter to the outside wall with stainless
steel or galvanized lag screws (not included) or other appropriate fasteners. Flash and seal the edges of the power
venter mounting plate to the wall with exterior sealant as necessary to prevent water entry behind the riser. DO NOT
enclose the spaced plates on the power venter body. This will result in reduced cooling of the power venter body.
Wood or vinyl siding should be cut so that the unit mounts directly on the wallboard to provide a stable support. If the
siding is greater than 1/2" thick use a spacer plate or board behind the power venter mounting plate. (See Figure 2)
7. Two-Piece Backing Plate Installation:
a. Position the Upper Backing Plate Half on the inside wall by placing the plate half on the inside wall and up to the
venter body, locating the air pressure sensing tube through the small slot in the plate half and the flexible conduit
through the larger slot, as shown in Figure 4. Install an appropriate fastener in the upper right corner hole in the
plate half. Note: if the wall is thicker than 11”, it may be necessary to enlarge the pressure sensing tube slot to
allow clearance for the tube union fitting.
Diagram A
Page 6
b. Bend the two tabs of the Lower Backing Plate Half outward (See Figure 5) and position it on the inside wall as
shown in Figure 6 and install appropriate fasteners through the upper left and lower right corner holes in both plate
halves.
c. Install an appropriate fastener in the lower left corner hole.
d. Extend and rotate the tailpiece’s extendable combustion air tee to the desired position, and install the two self -
drilling screws (included) through the two tabs on the lower backing plate and into the body of the power venter, to
lock the air tee in the desired position (See Diagram 7) and complete the backing plate installation.
8. Air Tee Collar Installation: If the venter is to be used to provide combustion air to an
appliance (See Figure 8):
a. Remove the factory-installed air tee cover plate.
b. Install the combustion air tee collar: insert the collar tabs into the slots on the
air tee adjacent to the opening, and position the slotted tabs onto the mounting
studs.
NOTE: The air tee must be extended to give at least 14-1/4” from end of the air tee to
back of riser mounting flange to allow proper installation of the air tee collar.
c. Reaching into the collar, bend both collar tabs inward towards the opening into
a U-shape, to pull the collar towards the tee and stabilize the joint.
d. Re-install the lock-washer nuts onto the mounting studs and carefully tighten,
use care not to over-tighten.
WARNING: If the venter does not supply combustion air to an appliance, the factory-
installed air tee cover plate must be in place on the venter. Fire hazard and/or
infiltration of vented gases may occur if the cover plate is not in place on the venter.
WARNING: The combustion air feature must be connected to one appliance only.
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
INSTALL 1
INSTALL 2
INSTALL 3
INSTALL 4
Page 7
Figure 9
VENTING SYSTEM CONNECTIONS
Venting system should be installed and supported in
accordance with the National Flue Gas Code
A.N.S.I.Z223.1, or in accordance with any local
codes. A vent pipe connector shall be supported for
the design and weight of the material employed, to
maintain clearances, prevent physical damage and
separation of joints. A vent pipe increaser or
reducer may be required for connecting the power
venter to the vent system. If needed, place the
reducer close to the power venter. Smaller vent
pipe sizes than a chimney-vented system may be
used for the vent system.
If mounting venting system near combustible
materials, refer to Diagram B for allowable venting
system installation clearances. Clearances are
based on an installation using single wall galvanized
steel vent pipe. For metal thickness of galvanized
steel pipe connectors, refer to NFPA 211 or NFPA
54 Standards for guidelines. If manufactured double
wall vent pipe is required or used for the installation,
clearance should be based on the vent pipes rated
clearance. Always check local code requirements
for code restrictions.
Route the vent pipe from the appliance to the power venter using a minimum number of elbows as possible. The horizontal
section of the vent pipe should have a slight upward slope from the appliance to the power venter. For clearances to
combustible materials, multiple appliance venting and other installation requirements, refer to the National Fuel Gas Code
A.N.S.I.Z223.1, and/or any applicable local codes or appliance manufacturer's installation instructions.
COMBUSTION AIR SYSTEM CONNECTIONS
1. For appliances constructed with a combustion air inlet connection that do not come equipped with means of either (a)
providing the burner with an alternate source of combustion air in the event of blockage, or (b) safely preventing
combustion in the event of a blockage: install a Field Controls Vacuum Relief Valve, model VRV (sold separately), in
the combustion air piping from the air tee collar to the appliance inlet connection, following the installation instructions
included with the VRV (See Figure 9). This will allow combustion air to be drawn from within the structure (or a safe
shutdown) if the venter inlet becomes blocked.
2. For oil appliances without a combustion air inlet connection, install a Field Controls Airboot, series CAS-2, with the
model appropriate for the particular burner model (see the Field Controls Contractor Reference Guide for instructions
on specifying the Airboot model). A VRV is included with the Airboot and need not be purchased separately.
Diagram B
Page 8
COMBUSTION AIR DUCT WORK INSTALLATION
1. A maximum of 30 linear feet of 4” duct pipe and two (2) 90° elbows at maximum firing rate may be used (44 equivalent
feet). Subtract 7 feet from the maximum linear feet for every additional 90° elbow added.
Longer pipe lengths require the use of a larger pipe between the VRV and the intake hood. It also
requires the use of a vent pipe increaser at the VRV and a reducer at the intake hood. (See Table 3)
Table 3
Pipe
Diameter
Maximum Equivalent
Pipe Feet (between Air boot™
and duct termination)
Elbow*
Equivalent
Feet
Reducer or
Increaser
Equivalent Feet
4”
44’
7’
-
5”
60’
9’
(4” to 5”) 3’
6”
90’
11’
(4” to 6”) 6’
*Note: Subtract the elbow or reducer equivalent feet from the maximum
equivalent feet to get maximum linear feet of pipe.
2. Route the duct work from the VRV tee to the inlet vent termination with as minimum a number of elbows as possible.
3. Secure and support the duct work for the design and weight of the material used, to prevent physical damage and
separation of joints. For guidelines refer to recognized national building codes or according to any local codes.
4. To reduce uncontrolled air leakage into the duct, tape all joints and seams using standard duct tape.
NOTE: Try to run a minimum of 12 feet of duct to help temper the outside air being brought into burner.
INSTALLATION USING SINGLE WALL VENT PIPE (SEE TABLE 4)
Table 4
CV-4VR & 5VR INSTALLATION CLEARANCES TO COMBUSTIBLES
Max. Inlet Temperature
Through-wall Clearance
Vent Pipe Clearances
Double Pipe
System
Single Pipe
System
400°F or Less
½” min
½” min
3” min
400°F-650°F (US)
400°F-575°F (Can)
½” min
1” min
4” min
½” min with
sheet metal liner
3” min with sheet
metal liner
*CAUTION: Air Tee Cover Plate must be in position on Air Tee when not providing combustion air.
NOTE: Vent pipe joints should be secured with at least (3) three sheet metal screws.
Table 5
Model
Hole Dimensions
CV-4VR
Min. 7-1/8” Square
CV-5VR
Min. 8-1/8” Square
Page 9
Figure 11
Figure 12
Figure 13
CLASS B AND CLASS L DOUBLE WALL VENT PIPE INSTALLATION
(Follow vent pipe manufacturer's listed or recommended clearances from combustible material)
1. Using a hand crimper or a like device, crimp the inner pipe of the CV power venter approximately 1" long. (See
Figure 7)
2. Attach the vent pipe over the crimped end of the CV power venter inner pipe.
3. Secure the vent pipe to the CV power venter inner pipe with at least (3) three #8 sheet metal screws. Pre-drilling the
holes through both pipes will allow easier fastening.
WIRING
NOTE: Refer to appropriate control kit for proper installation instructions.
Wire the power venter motor and controls in accordance with the National Electric Code and applicable local codes. UNIT
MUST BE GROUNDED. Check ground circuit to make certain that the unit has been properly grounded. The wiring should
be protected by an over-current circuit device rated at 15 amperes. CAUTION MUST be taken to ensure that the wiring does
not come in contact with any heat source. All line voltage and safety control circuits, between the power venter and the
appliance, MUST be wired in accordance with the National Electrical Code for Class 1 wiring or equivalent.
AIR FLOW ADJUSTMENTS
In order to obtain proper system draft, the power venter has an airflow adjustment damper built in.
When used in a system with a barometric draft control, this damper should be used to make
coarse draft adjustments while the barometric should be used for finer adjustments. Loosen the
locking screw on the air flow adjustment damper on the outer pipe of the power venter. (See
Figure 8) Adjust the damper to the full open position. Follow appliance manufacturer's procedures
for starting the heating appliance. Then adjust the thermostat to call for "Heat". After the system
has operated for several minutes to stabilize flue gas temperatures, check for negative draft or up-
draft at the heating appliance outlet or air flow into the draft hood. Use a draft gauge, velocity
meter or match test procedure. Adjust the adjustment damper closed to obtain the minimum air
flow required to maintain draft. Then increase air flow slightly (10% over minimum air flow rate) to
ensure proper venting. For oil-fired or gas-fired power burners, adjust draft to proper over-fired
draft.
If proper draft has been established, tighten the adjustment locking screw. For gas-fired systems, shut off thermostat and
check for residual heat spilling from draft hood. If this occurs, a post purge timer may be required. If so, use a Field Controls
PPC-5 Electronic Post Purge or a Control Kit which includes one. Before installing, refer to the General Installation
Inspection to check for negative pressure problems in the building. If sufficient combustion air for the burner is not provided,
a flow reversal during the off cycle could occur within the venting system. This may cause combustion problems as well as
condensation that could block the air pressure sensing tube. It may also contribute to premature motor failure. Combustion,
and/or make-up air, should be supplied from outside the structure and the air inlet should be on the same wall as the power
venter discharge, if the combustion air feature of the power venter is not used. For example, tightly constructed homes and
homes retro-fitted from electric heated systems are more likely to experience combustion and/or make-up air problems. For
further information consult "The Field Report-Effects of insufficient combustion air on draft and heating systems". Refer to
the appropriate control kit installation instructions for pressure switch adjustment procedure and system checkout
procedures before operating continuously. NOTE: After proper venting has been established, it is recommended that a
combustion test on gas and oil units, a check for CO levels on gas units, and a smoke test on oil systems be performed to
ensure maximum burner efficiency. Oil burner air adjustments should be set at a zero to a trace smoke at the highest or
recommended CO
2
% setting set by heating equipment manufacturer.
Page 10
GENERAL INSTALLATION INSPECTION
Recommended procedures for safety inspection of an appliance in accordance with the National Fuel Gas Code
A.N.S.I.Z223.1. The following procedure will help evaluate the venting system. It is intended as a guide to aid in determining
that the venting system is properly installed and is in a safe condition for continuous use. This procedure should be
recognized as a generalized procedure which cannot anticipate all situations. Accordingly, in some cases, deviation from
this procedure may be necessary to determine safe operation of the equipment. If it is determined that a condition exists
which could result in unsafe operation, the appliance should be shut off and the owner advised of the unsafe condition.
Corrections must be made before the appliance is put into continuous operation. The following steps should be followed in
making a safety inspection.
1. Visually inspect the venting system for proper size and determine that there is no flue gas spillage, blockage, restriction,
leakage, corrosion or other deficiency which could cause an unsafe operation.
2. Insofar as practical, close all building doors, fireplace dampers, windows and all doors in area in which the appliance is
located. Turn on clothes dryers, any exhaust fans, such as range hoods and bathroom exhausters so they operate at
maximum speed. Do not operate a summer exhaust fan. If, after completing Steps 3 through 7 it is believed sufficient
combustion air is not available, refer to the National Flue Gas Code A.N.S.I.Z223.1, or any applicable local codes for
guidance.
3. Place in operation the appliance being inspected. Follow the lighting instructions and adjust thermostat so appliance will
operate continuously.
4. Determine that the pilot or burner is operating properly and that the main burner ignition operates satisfactorily, by
interrupting and re-establishing the electrical power of the appliance in any convenient manner. Test the pilot or burner
safety device to determine if it is operating properly by extinguishing the pilot or disconnecting the flame safety circuit and
pressure switch sensing tube from the pressure switch.
5. Visually determine that the main burner is burning properly; i.e., no floating, lifting or flashbacks. When performing smoke
test on oil-fired systems, the burner should operate at a zero to a trace smoke. This can indicate reduced available
combustion air to burner.
6. If appliances are equipped with high and low flame control or flame modulation, check for proper main burner operation
at low flame.
7. Test for spillage at draft hood or barometric draft control opening and burner inlet air location after 5 minutes of main
burner operation. Use a draft gauge, flame of a match or candle, smoke from a cigarette, cigar or pipe. If spillage occurs,
adequate air is not available. Shut off heating appliance thermostat and check for spillage around the draft hood, barometric
draft control or burner inlet air location after power venter has stopped operation. If a flow reversal is noticed, house de-
pressurization is occurring and make up air is required. For oil-fired systems, this may be noticed by oil fume smell after post
purge cycle.
8. Turn on all fuel burning appliances within the same room so that they will operate at their maximum input. Then repeat
Steps 5 through 7.
9. Return doors, windows, exhaust fans, fireplace dampers and any other fuel-burning appliances to their previous condition
of use.
MAINTENANCE
1. Motor: Inspect the motor once a year - motor should rotate freely. To prolong the life of the motor, it must be lubricated
with six drops of SWG Superlube, Part # 46226200, annually.
2. Wheel: Inspect the power venter wheel annually to clear any soot, ash or coating, which inhibits either rotation or air
flow. Remove all foreign materials before operating.
3. Vent System: Inspect all vent connections annually for looseness, for evidence of corrosion and for flue gas leakage.
Replace, seal or tighten pipe connections if necessary. Check the power venter choke plate to insure it is secured in
place. Check the barometric draft control, if installed, to insure the gate swings freely.
4. System Safety Devices: With the heating system operating, disconnect the pressure sensing tube from the pressure
switch on the CK Kit. This will stop the burner operation. Re-connecting the tube will relight the burner. For 30 millivolt
operating systems, disconnect one lead of the spill switch circuit from the thermocouple junction block. This will shut off
the pilot and the burner. Re-connection will allow relighting the pilot.
Page 11
Figure 14
Figure 15
Figure 16
REPLACEMENT PARTS
Should the motor or blower wheel need replacing, the following replacement items are available. The Repair Motor
Assembly contains the Motor and Blower Wheel factory assemble to a mounting bracket.
PART NUMBERS
MODEL
REPAIR MOTOR ASSEMBLY
BLOWER WHEEL
CV-4VR
46234800
46310400
CV-5VR
46234900
46213800
REMOVAL AND INSTALLATION OF THE CV SERIES POWER VENTER MOTOR
ASSEMBLY
REMOVAL
1. Remove the motor enclosure cover by loosening the four screws. (See Figure 14)
2. Disconnect the conduit connector from the motor conduit box by loosening the screw
on the side of the connector. Pull the wires and wire nuts out of conduit box hole and
remove the wire nuts. NOTE: Wiring disconnection may not be necessary for
inspection and/or cleaning only. (See Figure 15)
3. Remove the three or four nuts securing the motor assembly, and pull the motor
assembly straight off of the unit. (See Figure 16)
4. Clean off any build-up inside the blower wheel housing and the blower wheel.
CAUTION: Avoid applying excess pressure on the blower wheel when cleaning
off any build-up of material. This will cause an imbalance of the blower wheel,
which will result in excessive vibration and premature motor failure.
INSTALLATION
1. Align the holes in the circular cover plate with the holes in the motor mount
bracket on the motor assembly. (See Figure 16)
2. Slide the motor assembly onto the protruding threaded studs on the power
venter body with the exhaust chute pointing downward, and replace the four nuts
securely to the threaded studs. (See Figure 16)
3. Re-attach wires and wire nuts to the motor wiring and reinstall the conduit
connector, firmly tightening the screw on the side of the connector.
4. Install the motor cover with the side louvers pointing downward.
CV Repair
Motor Assembly
Page 12
INITIAL BURNER AND VENTING SYSTEM OPERATIONAL INFORMATION
List the following for each operating appliance on the sidewall venting system, as a guide for tune-up or service information
annually.
DATE:
FOR GAS FIRED EQUIPMENT
Heating Appliance BTU/HR Input
Gas Valve Operation Pressure
Vent System Draft Above Draft Hood or
Before Barometric Draft Control
CO
2
Measurement
CO Measurement
Equipment Outlet Flue Gas Temperature
FOR OIL FIRED EQUIPMENT
Oil Burner Nozzle Size
Oil Burner Operating Pressure
Pump Operating Vacuum Pressure
Smoke Number
Over-fire Draft
Equipment Outlet Flue Gas Temperature
CO
2
Measurement
Warranty
For warranty information about this or any Field Controls product, visit:
www.fieldcontrols.com/warranty
P/N 46568400 09/08
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

FIELD CONTROLS CV-4VR & CV-5VR Sidewall Power Venter Kit Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI