  • Hello! I am an AI chatbot trained to assist you with the Danfoss Floor drying, ECL 210, 296 310 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210/296/310,Floor(Screed)Drying
Program
1.0TableofContents
1.0TableofContents.............................................1
1.1Importantsafetyandproductinformation....................2
2.0Installation......................................................5
2.1Description,ingeneral............................................5
3.0Settings...........................................................7
3.1Parametersanddescriptions....................................7
4.0ECLTool..........................................................13
4.1DataloggingforreportwithECLTool..........................13
4.2Shortget-goinginstruction......................................14
5.0Miscellaneous..................................................15
5.1ParameterIDoverview............................................15
©Danfoss|2017.08VI.JM.P2.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyswhich
havethefloordryingprogramimplemented.TheapplicationKey
musthaveversion2.42orhigher.TheECLComfortcontroller
softwaremusthaveversion1.56orhigher.
Thedescribedfunctionsarerelatedtothefloordryingprocessonly.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
SeealsotherelatedInstallationGuide(finditon
http://heating.danfoss.com)fordescriptionofthefunctions.
TheApplicationKeyscomplywithECLComfort210/296/310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
2|©Danfoss|2017.08
VI.JM.P2.02
ECLComfort210/296/310,Floor(Screed)DryingProgram
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
VI.JM.P2.02
©Danfoss|2017.08|3
ECLComfort210/296/310,Floor(Screed)DryingProgram
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2017.08
VI.JM.P2.02
ECLComfort210/296/310,Floor(Screed)DryingProgram
2.0Installation
2.1Description,ingeneral
ApplicationkeysfortheECLComfort210/296/310series,which
controlheatingcircuits,offerafloordryingprogram,alsocalled
screeddryingprogram.
Thefloordryingprogramisusedafteranewfloorheatingcircuit
hasbeenplacedandfresh-from-factoryconcretecoversthefloor
heatingpipes.Thefloordryingprogramcanalsobeused,when
theself-levelingscreedhasbeendistributed.
Thefloordryingprogramcanbestartedimmediatelyinorderto
dry-outtheconcrete/screedaccordingtoasettime/temperature
plan.
Navigationtothemenufor'Floordrying':
Commoncontroller>MENU>Floordrying:
Functionalheating:
Theflowtemperatureiscontrolled
accordingtoasettime/temperatureplan
inordertodry-outtheconcrete/screed.
Curingheating:
Theflowtemperatureiscontrolled
accordingtoasettime/temperatureplan
inordertocuretheconcrete/screed.The
curingmustbedonebeforemountingof,
forexample,tiles.
Functionalandcuringheatingcanworkasoneprocessor
separated.
Thetime/temperatureplanissetandiscommonforselected
circuits.
T
=
Time
#1#
=
Functionalheating
#2#
=
Curingheating
VI.JM.P2.02
©Danfoss|2017.08|5
ECLComfort210/296/310,Floor(Screed)DryingProgram
Whenthefloordryingprocessisfinished,adatalogcanberead
fromtheECLComfortcontrollerbymeansofthe"ECLTool".The
datalogcanbeusedfordocumentingtheprocess.
Thefavoritedisplaywithtemperatureinformationoftheheating
circuit(s)can,asanexample,looklikethis:
Floordryingprocessnotactive:
Floordryingprocessactive:
Theprogressbarisfilledupfromleftside,accordingtotime
elapsedsinceprocessstart.Theelapsedtimeandtotalprocess
timeisalsoindicatedinhours.
Returntemperaturerelatedindicationsarenotpresent,asthe
returntemperaturelimitationiscancelledduringthefloordrying
process.
Floordryingprocessbeingactivecanalsobeseen:
Circuitx>MENU>Influenceoverview>Des.flowT:
Beforestartofthefloordryingprocess:
Thecontrolparametersmustbesetcorrectly(Circuitx>MENU
>Settings>Controlparameters).SeetheOperatingGuidefor
theapplicationinquestion.
TheTime&Datemustbesetcorrectly(Commoncontroller
>MENU>Time&Date).SeetheOperatingGuideforthe
applicationinquestion.TheTime&Datesettingsareusedin
thelogfacilities.
ThemodeselectoroftheECLComfortcontrollermustnotbein
Manualmodewhenthefloordryingprocessisinprogress.
6|©Danfoss|2017.08
VI.JM.P2.02
ECLComfort210/296/310,Floor(Screed)DryingProgram
3.0Settings
3.1Parametersanddescriptions
Parametertablescontainparametername,IDanddescriptions.
Parameters’settingrangeandfactorysettingsarelistedinthe
section"ParameterIDoverview"attheendofthisOperatingGuide.
VI.JM.P2.02
©Danfoss|2017.08|7
ECLComfort210/296/310,Floor(Screed)DryingProgram
DesiredflowT(Desiredflowtemperature)
Read-
out
Read-outofthedesiredflowtemperature.
---:
Thefloordryingprocessisnotactive
Value:
Thefloordryingprocessisactive
Pushthedialto:
select/deselectcircuit(s)forfloordrying
enter/changethegraphofthe"Functionalheating"or"Curing
heating"process
Thedesiredflowtemperaturecanbesetat:
X1,X2,X3andX4(Functionalheating)
X5,X6,X7andX8(Curingheating)
Selectionofcircuit(s)forfloordrying:
Circuitnumberselected
Circuitnumbernotselected
Examplesofgraph:
TimesforX1,X2,X3andX4arethesame(0h)
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is20°C
DesiredtemperatureatX3is20°C
DesiredtemperatureatX4is20°C
TimesforX1,X2,X3andX4aredifferent,asshown.
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is50°C
DesiredtemperatureatX3is50°C
DesiredtemperatureatX4is20°C
Important:Thedesiredflowtemperaturevalues,setatX4andX8are
usedascontrollingtemperatures:
afterthefloordryingprocess,iftheapplicationisnottobestarted
afterapowerfailure
Applicationwithoneheatingcircuit:
Ifthefloordryingprocessisinoperationandthecircuit,byaccident,is
changednottobeselected,thefloordryingprocessmustberestarted.
Applicationwithtwoorthreeheatingcircuits:
Ifthefloordryingprocessisinoperationfortwoorthreecircuitsand
oneofthecircuits,byaccident,ischangednottobeselected,thefloor
dryingprocesscontinues.Justselectthecircuitinquestionagain.
8|©Danfoss|2017.08
VI.JM.P2.02
ECLComfort210/296/310,Floor(Screed)DryingProgram
Prog.execution(Programexecution)
10512
Startorstopthefloordryingprocess.
Pressandholdthedialfor5secondsinordertostartorstopthe
process.
OFF:
Thefloordryingprocessisnotactive
ON:
Thefloordryingprocessisactive
IftheECLComfortcontrollerissettomanualmode,thefloordrying
processcanbestarted,butwillnotbeactive.
If"Prog.execution"issettoONandreturnstoOFFafter5seconds,
noneofthecircuitsinthegraph(DesiredflowT)havebeenselected
forfloordrying.
Iftheparameter"Appl.continue"(ID10912)issettoSTOP ,the"Prog.
execution"remainsONafterelapseofthefloordryingprocess.
Max.pwr.failure(Max.powerfailureperiod
acceptance)
10514
Settingthemax.acceptedtimeforpowerfailure.
IftheECLComfortcontrolleriswithoutpowerformorethantheset
time,thealarmwillbeactivatedwhenthecontrollerispoweredup.
Value:Settheacceptedtime
Thealarmcanbereset(MENU>Alarm>Alarmoverview)
Torestartthefloordryingprocess:
Iftheparameter"Afterpowerfail."(ID10913)issettoSTOP ,the
"Prog.execution"mustbesettoOFFandthentoON.
Afterapowerfailure,thealarmisindicated/activated.
Iftheparameter"Afterpowerfail."(ID10913)issettoSTOP,thedesired
flowtemperatureismaintainedatthevalue,setinX1.
VI.JM.P2.02
©Danfoss|2017.08|9
ECLComfort210/296/310,Floor(Screed)DryingProgram
RampX5-X6(TemperaturerampingfromtimeX5
toX6)
RampX7-X8(TemperaturerampingfromtimeX7
toX8)
10903
10904
Settingthenumberofstepsforthechangeofthedesiredflow
temperatureinselectedperiod.
OFF:
Thestepwisechangeisdisabled
Value:
Theperiodisdividedinthenumberofsteps
Example:
"X5"timeissetto100
"X5"temperatureissetto25°C
"X6"timeissetto150
"X6"temperatureissetto35°C
"RampX5-X6"issetto5
Result:
PeriodbetweenX5andX6is50hours.Temperaturechangeis10K.
Theprocesswillbe:
Starttemperature:25°C,after10hoursthetemperaturechanges
to27°C.Afterfurther10hoursthetemperaturechangesto29°C
andsoon.
Appl.continue(Applicationcontinue)
10912
SelectionhowtheECLComfortcontrollermustcontinueafter
havingfinishedthefloordryingprocess.
OFF:
Thedesiredflowtemperaturewillbethevaluesetat
"X8"time
ON:
Thecontrollercontinueswiththeselectedapplication
andthesetmodeofthefunctionselector
Whenusingonly"Functionalheating"andnodemandforcontrolafter
thefloordryingprocess,itisimportanttosetthedesiredtemperature
atX8.
(Commoncontroller>MENU>Floordrying>Curingheating>
"DesiredflowT">Graph'srightpoint).
Afterpowerfail.(Afterpowerfailure)
10913
SelectionhowtheECLComfortcontrollermustcontinueaftera
powerfailure(powerhasbeenawayformorethanacceptedtime,
setin"Max.pwr.failure",ID10514).
Ifpowerfailurehappensin"Functionalheating"process,thefloor
dryingcanberestartedaccordingtotimeandtemperaturesetting
forX1orstopped.Ifstopped,thedesiredflowtemperatureis
maintainedatthevalue,setforX1.
Ifpowerfailurehappensin"Curingheating"process,thefloor
dryingcanberestartedaccordingtotimeandtemperaturesetting
forX4.Ifstoppedthedesiredflowtemperatureismaintainedat
thevalue,setforX1.
STOP:
Thecontrollerstopsthefloordryingprocessand
maintainsthetemperature,setatX1
START:
Thecontrollerstartsthefloordryingprocessfrom
settingsinX1orX4
Torestartthefloordryingprocess:
Iftheparameter"Afterpowerfail."(ID10913)issettoSTOP ,the
"Prog.execution"mustbesettoOFFandthentoON.
Afterapowerfailure,thealarmisindicated.
Thealarmcanbereset.
10|©Danfoss|2017.08
VI.JM.P2.02
ECLComfort210/296/310,Floor(Screed)DryingProgram
X1(Starttimeforperiod1)
X2(Starttimeforperiod2)
X3(Starttimeforperiod3)
X4(Starttimeforperiod4)
10930
10931
10932
10933
Thetimethatmustelapsefromprocessstartforcontrollingtheset
flowtemperatureinthefunctionalheatingperiod.
Values:Setthetimes
Example1:
X1
=
50hours
X2
=
50hours
X3
=
200hours
X4
=
200hours
Result:
Thedesiredflowtemperature,whichwillbemaintainedfrom
processstart,isthevalue,whichisindicated/setatX1in"Desired
flowT".
50hoursafterprocessstart,thedesiredflowtemperature,whichis
indicated/setatX2in"DesiredflowT",willbemaintained.
200hoursafterprocessstart,thedesiredflowtemperature,which
isindicated/setatX3in"DesiredflowT",willbemaintained.
200hoursafterprocessstart,thedesiredflowtemperature,which
isindicated/setatX4in"DesiredflowT",willbemaintained.
Example2:
X1
=
50hours
X2
=
100hours
X3
=
150hours
X4
=
200hours
Result:
Thedesiredflowtemperature,whichwillbemaintainedfrom
processstart,isthevalue,whichisindicated/setatX1in"Desired
flowT".
50hoursafterprocessstart,thedesiredflowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX2in
"DesiredflowT".
150hoursafterprocessstart,thedesiredflowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX3in
"DesiredflowT".
200hoursafterprocessstart,thedesiredflowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX4in
"DesiredflowT".
Ifthefunctionalheatingperiodshouldnotbeused,X4canbeset0
h(zerohours).
VI.JM.P2.02
©Danfoss|2017.08|11
ECLComfort210/296/310,Floor(Screed)DryingProgram
X5(Starttimeforperiod5)
X6(Starttimeforperiod6)
X7(Starttimeforperiod7)
X8(Starttimeforperiod8)
10934
10935
10936
10937
ThetimethatmustelapsefromtimeX4forcontrollingthesetflow
temperatureinthecuringheatingperiod.
Values:Setthetimes
Ifthetemperaturevalues,setatX4andX5,aredifferent,the
desiredflowtemperaturechangesgraduallyfromtheX4value
totheX5value.
WhenX5issettoatimevalue,thedesiredflowtemperaturestarts
withthevalue,setatX4.
Ifthecuringheatingperiodshouldnotbeused,X8canbeset0h
(zerohours).
12|©Danfoss|2017.08
VI.JM.P2.02
ECLComfort210/296/310,Floor(Screed)DryingProgram
4.0ECLTool
4.1DataloggingforreportwithECLTool
BymeansoftheECLTooladatalogcanbereadfromtheECL
Comfortcontrollerinordertodocumenttheprocess.
Thelogmakesastampeach15minutes.Max.logtimeis40days.
Whenthelogmemoryisfull,theloggingstops.Astartofthefloor
dryingmightdeletetheexistinglogintheECLcontroller.
TheECLToolisfoundhere:http://heating.danfoss.com
ChooseTools&Software,selectDownload.DownloadtheUSB
driverandECLToolinstaller.
Theexe-filealsocontainsanECLToolinstructioninPDFfileformat.
WhenrunningtheECLTool,besuretheversionis1.9.8.1orhigher.
ConnectioncablebetweenPCandECLComfortcontrollerisan
USBcable,havingUSB-Aplug(forPC)atoneendandUSB-Bplug
(fortheECLComfortcontroller)attheotherend.
Versioninformation,example:
VI.JM.P2.02
©Danfoss|2017.08|13
ECLComfort210/296/310,Floor(Screed)DryingProgram
4.2Shortget-goinginstruction
AfterhavingestablishedconnectionbetweenthePCandthe
ECLcontroller,the"Loadstandardparameters(recommended)"
isselected.
Allparametersandsettingsarelistedingroups.
Atthebottomoftheviewagraphbuttonis
present.Thenameis"Readlogs" .
Byselectingthereadlogsbutton,adefaultgraphisshown.
Atthebottomofthedefaultgraphviewsomebuttonsarepresent:
Help.
OpensECLToolinstructioninPDFformat.
Print
ReadECLlogfromECLandshowgraph
ReadextendedlogfromECLandshowgraph.
ThisispossiblewithECLComfortcontrollershaving
firmware1.56orhigher.
Selectthelogbutton;agraphshowstheloggingsofthelisted
items.
Afilewiththeindicatednameiscreatedandsaved.
IfchoosingYesforopeninginanexternalprogram(forexample
Excel),theprogramopenswiththedata.
Thegraphcanbezoomed/draggedinordertogetadesired
pictureforthereport.
Aright-clickonthegraphallowscopyfacilities.
Selectthebutton"Copygraphtoreportpage"inordertoinclude
thecurrentlyshowngraphinthereport.
Theprintbuttonwillstartthereportprinting.
14|©Danfoss|2017.08
VI.JM.P2.02
ECLComfort210/296/310,Floor(Screed)DryingProgram
5.0Miscellaneous
5.1ParameterIDoverview
IDParameterName
Settingrange
Factory
UnitOwnsettings
10512
Prog.execution
OFF;ONOFF
10514
Max.pwr.failure
5...300030
Min
10903
RampX5-X6
OFF,1...20
5
10904
RampX7-X8
OFF,1...20
5
10912
Appl.continue
OFF;ONOFF
10913
Afterpowerfail.
STOP/STARTSTOP
10930
X1
0-12000
h
10931
X2
0-12000
h
10932
X3
0-12000
h
10933
X4
0-12000
h
10934
X5
0-12000
h
10935
X6
0-1200360
h
10936
X7
0-1200720
h
10937
X8
0-12001080
h
Functionalheating
Factorysettings
DesiredflowT:0.20(0=time;20=desiredflowtemperature)
Curingheating
Factorysettings
DesiredflowT:0.25(0=time;25=desiredflowtemperature)
-||-
360.50(360=time;50=desiredflowtemperature)
-||-
720.50(720=time;50=desiredflowtemperature)
-||-
1080.25(1080=time;25=desiredflowtemperature)
VI.JM.P2.02
©Danfoss|2017.08|15
ECLComfort210/296/310,Floor(Screed)DryingProgram
*087H9262*
*VIJMP202*
16|©Danfoss|2017.08