Danfoss Floor drying, ECL 210, 296 310 Operating instructions

Type
Operating instructions
InstallationGuide
ECLComfort210/296/310,Floor(Screed)DryingProgram
1.0TableofContents
1.0TableofContents.............................................1
1.1Importantsafetyandproductinformation....................2
2.0Installation......................................................5
2.1Description,ingeneral............................................5
3.0Settings...........................................................7
3.1Parametersanddescriptions....................................7
4.0ECLTool..........................................................13
4.1DataloggingforreportwithECLTool..........................13
4.2Shortget-goinginstruction......................................14
5.0Miscellaneous..................................................15
5.1ParameterIDoverview............................................15
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK1
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeys
whichhavetheoordryingprogramimplemented.Theapplication
Keymusthaveversion2.42orhigher.TheECLComfortcontroller
softwaremusthaveversion1.56orhigher.
Thedescribedfunctionsarerelatedtotheoordryingprocessonly.
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
SeealsotherelatedInstallationGuide(nditon
http://heating.danfoss.com)fordescriptionofthefunctions.
TheApplicationKeyscomplywithECLComfort210/296/310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
2
DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Automaticupdateofcontrollersoftware:
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11).Thefollowinganimationwill
beshownwhenthesoftwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisInstallationGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK3
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
2.0Installation
2.1Description,ingeneral
ApplicationkeysfortheECLComfort210/296/310series,which
controlheatingcircuits,offeraoordryingprogram,alsocalled
screeddryingprogram.
Theoordryingprogramisusedafteranewoorheatingcircuit
hasbeenplacedandfresh-from-factoryconcretecoverstheoor
heatingpipes.Theoordryingprogramcanalsobeused,when
theself-levelingscreedhasbeendistributed.
Theoordryingprogramcanbestartedimmediatelyinorderto
dry-outtheconcrete/screedaccordingtoasettime/temperature
plan.
Navigationtothemenufor'Floordrying':
Commoncontroller>MENU>Floordrying:
Functionalheating:
Theowtemperatureiscontrolled
accordingtoasettime/temperatureplan
inordertodry-outtheconcrete/screed.
Curingheating:
Theowtemperatureiscontrolled
accordingtoasettime/temperatureplan
inordertocuretheconcrete/screed.The
curingmustbedonebeforemountingof,
forexample,tiles.
Functionalandcuringheatingcanworkasoneprocessor
separated.
Thetime/temperatureplanissetandiscommonforselected
circuits.
87H1658 .10
Da nfos s
T
# 1 #
°C
# 2 #
X1
X3
X5 X6 X7 X8
10
60
X2
X4
T
=
Time
#1#
=
Functionalheating
#2#
=
Curingheating
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK
5
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Whentheoordryingprocessisnished,adatalogcanberead
fromtheECLComfortcontrollerbymeansofthe"ECLTool".The
datalogcanbeusedfordocumentingtheprocess.
Thefavoritedisplaywithtemperatureinformationoftheheating
circuit(s)can,asanexample,looklikethis:
Floordryingprocessnotactive:
Floordryingprocessactive:
Theprogressbarislledupfromleftside,accordingtotime
elapsedsinceprocessstart.Theelapsedtimeandtotalprocess
timeisalsoindicatedinhours.
Returntemperaturerelatedindicationsarenotpresent,asthe
returntemperaturelimitationiscancelledduringtheoordrying
process.
Floordryingprocessbeingactivecanalsobeseen:
Circuitx>MENU>Inuenceoverview>Des.owT:
Beforestartoftheoordryingprocess:
Thecontrolparametersmustbesetcorrectly(Circuitx>MENU
>Settings>Controlparameters).SeetheInstallationGuide
fortheapplicationinquestion.
TheTime&Datemustbesetcorrectly(Commoncontroller
>MENU>Time&Date).SeetheInstallationGuideforthe
applicationinquestion.TheTime&Datesettingsareusedin
thelogfacilities.
ThemodeselectoroftheECLComfortcontrollermustnotbein
Manualmodewhentheoordryingprocessisinprogress.
6DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
3.0Settings
3.1Parametersanddescriptions
Parametertablescontainparametername,IDanddescriptions.
Parameters’settingrangeandfactorysettingsarelistedinthe
section"ParameterIDoverview"attheendofthisInstallation
Guide.
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK7
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
DesiredowT(Desiredowtemperature)
Read-
out
Read-outofthedesiredowtemperature.
---:
Theoordryingprocessisnotactive
Value:
Theoordryingprocessisactive
Pushthedialto:
select/deselectcircuit(s)foroordrying
enter/changethegraphofthe"Functionalheating"or"Curing
heating"process
Thedesiredowtemperaturecanbesetat:
X1,X2,X3andX4(Functionalheating)
X5,X6,X7andX8(Curingheating)
Selectionofcircuit(s)foroordrying:
Circuitnumberselected
Circuitnumbernotselected
Examplesofgraph:
TimesforX1,X2,X3andX4arethesame(0h)
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is20°C
DesiredtemperatureatX3is20°C
DesiredtemperatureatX4is20°C
TimesforX1,X2,X3andX4aredifferent,asshown.
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is50°C
DesiredtemperatureatX3is50°C
DesiredtemperatureatX4is20°C
Important:Thedesiredowtemperaturevalues,setatX4andX8are
usedascontrollingtemperatures:
aftertheoordryingprocess,iftheapplicationisnottobestarted
afterapowerfailure
Applicationwithoneheatingcircuit:
Iftheoordryingprocessisinoperationandthecircuit,byaccident,is
changednottobeselected,theoordryingprocessmustberestarted.
Applicationwithtwoorthreeheatingcircuits:
Iftheoordryingprocessisinoperationfortwoorthreecircuitsand
oneofthecircuits,byaccident,ischangednottobeselected,theoor
dryingprocesscontinues.Justselectthecircuitinquestionagain.
8DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Prog.execution(Programexecution)
10512
Startorstoptheoordryingprocess.
Pressandholdthedialfor5secondsinordertostartorstoptheprocess.
OFF:
Theoordryingprocessisnotactive
ON:
Theoordryingprocessisactive
IftheECLComfortcontrollerissettomanualmode,theoordrying
processcanbestarted,butwillnotbeactive.
If"Prog.execution"issettoONandreturnstoOFFafter5seconds,
noneofthecircuitsinthegraph(DesiredowT)havebeenselected
foroordrying.
Iftheparameter"Appl.continue"(ID10912)issettoSTOP ,the"Prog.
execution"remainsONafterelapseoftheoordryingprocess.
Max.pwr.failure(Max.powerfailureperiodacceptance)
10514
Settingthemax.acceptedtimeforpowerfailure.
IftheECLComfortcontrolleriswithoutpowerformorethanthesettime,the
alarmwillbeactivatedwhenthecontrollerispoweredup.
Value:Settheacceptedtime
Thealarmcanbereset(MENU>Alarm>Alarmoverview)
Torestarttheoordryingprocess:
Iftheparameter"Afterpowerfail."(ID10913)issettoSTOP ,the
"Prog.execution"mustbesettoOFFandthentoON.
Afterapowerfailure,thealarmisindicated/activated.
Iftheparameter"Afterpowerfail. "(ID10913)issettoSTOP ,thedesired
owtemperatureismaintainedatthevalue,setinX1.
RampX5-X6(TemperaturerampingfromtimeX5toX6)
RampX7-X8(TemperaturerampingfromtimeX7toX8)
10903
10904
Settingthenumberofstepsforthechangeofthedesiredowtemperature
inselectedperiod.
OFF:
Thestepwisechangeisdisabled
Value:
Theperiodisdividedinthenumberofsteps
Example:
"X5"timeissetto100
"X5"temperatureissetto25°C
"X6"timeissetto150
"X6"temperatureissetto35°C
"RampX5-X6"issetto5
Result:
PeriodbetweenX5andX6is50hours.Temperaturechangeis10K.
Theprocesswillbe:
Starttemperature:25°C,after10hoursthetemperaturechanges
to27°C.Afterfurther10hoursthetemperaturechangesto29°C
andsoon.
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK9
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Appl.continue(Applicationcontinue)
10912
SelectionhowtheECLComfortcontrollermustcontinueafterhaving
nishedtheoordryingprocess.
OFF:
Thedesiredowtemperaturewillbethevaluesetat
"X8"time
ON:
Thecontrollercontinueswiththeselectedapplication
andthesetmodeofthefunctionselector
Whenusingonly"Functionalheating"andnodemandforcontrolafter
theoordryingprocess,itisimportanttosetthedesiredtemperature
atX8.
(Commoncontroller>MENU>Floordrying>Curingheating>
"DesiredowT">Graph'srightpoint).
Afterpowerfail.(Afterpowerfailure)
10913
SelectionhowtheECLComfortcontrollermustcontinueafterapower
failure(powerhasbeenawayformorethanacceptedtime,setin"Max.
pwr.failure",ID10514).
Ifpowerfailurehappensin"Functionalheating"process,theoordryingcan
berestartedaccordingtotimeandtemperaturesettingforX1orstopped.If
stopped,thedesiredowtemperatureismaintainedatthevalue,setforX1.
Ifpowerfailurehappensin"Curingheating"process,theoordryingcanbe
restartedaccordingtotimeandtemperaturesettingforX4.Ifstoppedthe
desiredowtemperatureismaintainedatthevalue,setforX1.
STOP:
Thecontrollerstopstheoordryingprocessand
maintainsthetemperature,setatX1
START:
Thecontrollerstartstheoordryingprocessfrom
settingsinX1orX4
Torestarttheoordryingprocess:
Iftheparameter"Afterpowerfail."(ID10913)issettoSTOP ,the
"Prog.execution"mustbesettoOFFandthentoON.
Afterapowerfailure,thealarmisindicated.
Thealarmcanbereset.
10DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
X1(Starttimeforperiod1)
X2(Starttimeforperiod2)
X3(Starttimeforperiod3)
X4(Starttimeforperiod4)
10930
10931
10932
10933
Thetimethatmustelapsefromprocessstartforcontrollingthesetow
temperatureinthefunctionalheatingperiod.
Values:Setthetimes
Example1:
X1
=
50hours
X2
=
50hours
X3
=
200hours
X4
=
200hours
Result:
Thedesiredowtemperature,whichwillbemaintainedfrom
processstart,isthevalue,whichisindicated/setatX1in"Desired
owT".
50hoursafterprocessstart,thedesiredowtemperature,whichis
indicated/setatX2in"DesiredowT",willbemaintained.
200hoursafterprocessstart,thedesiredowtemperature,which
isindicated/setatX3in"DesiredowT",willbemaintained.
200hoursafterprocessstart,thedesiredowtemperature,which
isindicated/setatX4in"DesiredowT",willbemaintained.
Example2:
X1
=
50hours
X2
=
100hours
X3
=
150hours
X4
=
200hours
Result:
Thedesiredowtemperature,whichwillbemaintainedfrom
processstart,isthevalue,whichisindicated/setatX1in"Desired
owT".
50hoursafterprocessstart,thedesiredowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX2in
"DesiredowT".
150hoursafterprocessstart,thedesiredowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX3in
"DesiredowT".
200hoursafterprocessstart,thedesiredowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX4in
"DesiredowT".
Ifthefunctionalheatingperiodshouldnotbeused,X4canbeset0
h(zerohours).
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK11
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
X5(Starttimeforperiod5)
X6(Starttimeforperiod6)
X7(Starttimeforperiod7)
X8(Starttimeforperiod8)
10934
10935
10936
10937
ThetimethatmustelapsefromtimeX4forcontrollingthesetow
temperatureinthecuringheatingperiod.
Values:Setthetimes
Ifthetemperaturevalues,setatX4andX5,aredifferent,the
desiredowtemperaturechangesgraduallyfromtheX4value
totheX5value.
WhenX5issettoatimevalue,thedesiredowtemperaturestarts
withthevalue,setatX4.
Ifthecuringheatingperiodshouldnotbeused,X8canbeset0h
(zerohours).
12
DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
4.0ECLTool
4.1DataloggingforreportwithECLTool
BymeansoftheECLTooladatalogcanbereadfromtheECL
Comfortcontrollerinordertodocumenttheprocess.
Thelogmakesastampeach15minutes.Max.logtimeis40days.
Whenthelogmemoryisfull,theloggingstops.Astartoftheoor
dryingmightdeletetheexistinglogintheECLcontroller.
TheECLToolisfoundhere:http://heating.danfoss.com
ChooseTools&Software,selectDownload.DownloadtheUSB
driverandECLToolinstaller.
Theexe-lealsocontainsanECLToolinstructioninPDFleformat.
WhenrunningtheECLTool,besuretheversionis1.9.8.1orhigher.
ConnectioncablebetweenPCandECLComfortcontrollerisan
USBcable,havingUSB-Aplug(forPC)atoneendandUSB-Bplug
(fortheECLComfortcontroller)attheotherend.
Versioninformation,example:
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK13
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
4.2Shortget-goinginstruction
AfterhavingestablishedconnectionbetweenthePCandthe
ECLcontroller,the"Loadstandardparameters(recommended)"
isselected.
Allparametersandsettingsarelistedingroups.
Atthebottomoftheviewagraphbuttonis
present.Thenameis"Readlogs".
Byselectingthereadlogsbutton,adefaultgraphisshown.
Atthebottomofthedefaultgraphviewsomebuttonsarepresent:
Help.
OpensECLToolinstructioninPDFformat.
Print
ReadECLlogfromECLandshowgraph
ReadextendedlogfromECLandshowgraph.
ThisispossiblewithECLComfortcontrollershaving
rmware1.56orhigher.
Selectthelogbutton;agraphshowstheloggingsofthelisted
items.
Alewiththeindicatednameiscreatedandsaved.
IfchoosingYesforopeninginanexternalprogram(forexample
Excel),theprogramopenswiththedata.
Thegraphcanbezoomed/draggedinordertogetadesired
pictureforthereport.
Aright-clickonthegraphallowscopyfacilities.
Selectthebutton"Copygraphtoreportpage"inordertoinclude
thecurrentlyshowngraphinthereport.
Theprintbuttonwillstartthereportprinting.
14DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
5.0Miscellaneous
5.1ParameterIDoverview
IDParameterName
Settingrange
Factory
UnitOwnsettings
10512
Prog.execution
OFF;ONOFF
10514
Max.pwr.failure
5...300030
Min
10903
RampX5-X6
OFF,1...20
5
10904
RampX7-X8
OFF,1...20
5
10912
Appl.continue
OFF;ONOFF
10913
Afterpowerfail.
STOP/STARTSTOP
10930
X1
0-12000
h
10931
X2
0-12000
h
10932
X3
0-12000
h
10933
X4
0-12000
h
10934
X5
0-12000
h
10935
X6
0-1200360
h
10936
X7
0-1200720
h
10937
X8
0-12001080
h
Functionalheating
Factorysettings
DesiredowT:0.20(0=time;20=desiredowtemperature)
Curingheating
Factorysettings
DesiredowT:0.25(0=time;25=desiredowtemperature)
-||-
360.50(360=time;50=desiredowtemperature)
-||-
720.50(720=time;50=desiredowtemperature)
-||-
1080.25(1080=time;25=desiredowtemperature)
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK
15
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
*087H9262*
*VIJMP102*
ProducedbyDanfossA/S©11/2015
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16