  • Hello! I am an AI chatbot trained to assist you with the Danfoss Floor drying, ECL 210, 296 310 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
InstallationGuide
ECLComfort210/296/310,Floor(Screed)DryingProgram
1.0TableofContents
1.0TableofContents.............................................1
1.1Importantsafetyandproductinformation....................2
2.0Installation......................................................5
2.1Description,ingeneral............................................5
3.0Settings...........................................................7
3.1Parametersanddescriptions....................................7
4.0ECLTool..........................................................13
4.1DataloggingforreportwithECLTool..........................13
4.2Shortget-goinginstruction......................................14
5.0Miscellaneous..................................................15
5.1ParameterIDoverview............................................15
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK1
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeys
whichhavetheoordryingprogramimplemented.Theapplication
Keymusthaveversion2.42orhigher.TheECLComfortcontroller
softwaremusthaveversion1.56orhigher.
Thedescribedfunctionsarerelatedtotheoordryingprocessonly.
SeetheMountingGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
SeealsotherelatedInstallationGuide(nditon
http://heating.danfoss.com)fordescriptionofthefunctions.
TheApplicationKeyscomplywithECLComfort210/296/310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
AdditionaldocumentationforECLComfort210,296and310,
modulesandaccessoriesisavailableonhttp://heating.danfoss.com.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
2
DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Automaticupdateofcontrollersoftware:
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11).Thefollowinganimationwill
beshownwhenthesoftwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisInstallationGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK3
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
2.0Installation
2.1Description,ingeneral
ApplicationkeysfortheECLComfort210/296/310series,which
controlheatingcircuits,offeraoordryingprogram,alsocalled
screeddryingprogram.
Theoordryingprogramisusedafteranewoorheatingcircuit
hasbeenplacedandfresh-from-factoryconcretecoverstheoor
heatingpipes.Theoordryingprogramcanalsobeused,when
theself-levelingscreedhasbeendistributed.
Theoordryingprogramcanbestartedimmediatelyinorderto
dry-outtheconcrete/screedaccordingtoasettime/temperature
plan.
Navigationtothemenufor'Floordrying':
Commoncontroller>MENU>Floordrying:
Functionalheating:
Theowtemperatureiscontrolled
accordingtoasettime/temperatureplan
inordertodry-outtheconcrete/screed.
Curingheating:
Theowtemperatureiscontrolled
accordingtoasettime/temperatureplan
inordertocuretheconcrete/screed.The
curingmustbedonebeforemountingof,
forexample,tiles.
Functionalandcuringheatingcanworkasoneprocessor
separated.
Thetime/temperatureplanissetandiscommonforselected
circuits.
87H1658 .10
Da nfos s
T
# 1 #
°C
# 2 #
X1
X3
X5 X6 X7 X8
10
60
X2
X4
T
=
Time
#1#
=
Functionalheating
#2#
=
Curingheating
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK
5
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Whentheoordryingprocessisnished,adatalogcanberead
fromtheECLComfortcontrollerbymeansofthe"ECLTool".The
datalogcanbeusedfordocumentingtheprocess.
Thefavoritedisplaywithtemperatureinformationoftheheating
circuit(s)can,asanexample,looklikethis:
Floordryingprocessnotactive:
Floordryingprocessactive:
Theprogressbarislledupfromleftside,accordingtotime
elapsedsinceprocessstart.Theelapsedtimeandtotalprocess
timeisalsoindicatedinhours.
Returntemperaturerelatedindicationsarenotpresent,asthe
returntemperaturelimitationiscancelledduringtheoordrying
process.
Floordryingprocessbeingactivecanalsobeseen:
Circuitx>MENU>Inuenceoverview>Des.owT:
Beforestartoftheoordryingprocess:
Thecontrolparametersmustbesetcorrectly(Circuitx>MENU
>Settings>Controlparameters).SeetheInstallationGuide
fortheapplicationinquestion.
TheTime&Datemustbesetcorrectly(Commoncontroller
>MENU>Time&Date).SeetheInstallationGuideforthe
applicationinquestion.TheTime&Datesettingsareusedin
thelogfacilities.
ThemodeselectoroftheECLComfortcontrollermustnotbein
Manualmodewhentheoordryingprocessisinprogress.
6DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
3.0Settings
3.1Parametersanddescriptions
Parametertablescontainparametername,IDanddescriptions.
Parameters’settingrangeandfactorysettingsarelistedinthe
section"ParameterIDoverview"attheendofthisInstallation
Guide.
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK7
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
DesiredowT(Desiredowtemperature)
Read-
out
Read-outofthedesiredowtemperature.
---:
Theoordryingprocessisnotactive
Value:
Theoordryingprocessisactive
Pushthedialto:
select/deselectcircuit(s)foroordrying
enter/changethegraphofthe"Functionalheating"or"Curing
heating"process
Thedesiredowtemperaturecanbesetat:
X1,X2,X3andX4(Functionalheating)
X5,X6,X7andX8(Curingheating)
Selectionofcircuit(s)foroordrying:
Circuitnumberselected
Circuitnumbernotselected
Examplesofgraph:
TimesforX1,X2,X3andX4arethesame(0h)
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is20°C
DesiredtemperatureatX3is20°C
DesiredtemperatureatX4is20°C
TimesforX1,X2,X3andX4aredifferent,asshown.
DesiredtemperatureatX1is20°C
DesiredtemperatureatX2is50°C
DesiredtemperatureatX3is50°C
DesiredtemperatureatX4is20°C
Important:Thedesiredowtemperaturevalues,setatX4andX8are
usedascontrollingtemperatures:
aftertheoordryingprocess,iftheapplicationisnottobestarted
afterapowerfailure
Applicationwithoneheatingcircuit:
Iftheoordryingprocessisinoperationandthecircuit,byaccident,is
changednottobeselected,theoordryingprocessmustberestarted.
Applicationwithtwoorthreeheatingcircuits:
Iftheoordryingprocessisinoperationfortwoorthreecircuitsand
oneofthecircuits,byaccident,ischangednottobeselected,theoor
dryingprocesscontinues.Justselectthecircuitinquestionagain.
8DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Prog.execution(Programexecution)
10512
Startorstoptheoordryingprocess.
Pressandholdthedialfor5secondsinordertostartorstoptheprocess.
OFF:
Theoordryingprocessisnotactive
ON:
Theoordryingprocessisactive
IftheECLComfortcontrollerissettomanualmode,theoordrying
processcanbestarted,butwillnotbeactive.
If"Prog.execution"issettoONandreturnstoOFFafter5seconds,
noneofthecircuitsinthegraph(DesiredowT)havebeenselected
foroordrying.
Iftheparameter"Appl.continue"(ID10912)issettoSTOP ,the"Prog.
execution"remainsONafterelapseoftheoordryingprocess.
Max.pwr.failure(Max.powerfailureperiodacceptance)
10514
Settingthemax.acceptedtimeforpowerfailure.
IftheECLComfortcontrolleriswithoutpowerformorethanthesettime,the
alarmwillbeactivatedwhenthecontrollerispoweredup.
Value:Settheacceptedtime
Thealarmcanbereset(MENU>Alarm>Alarmoverview)
Torestarttheoordryingprocess:
Iftheparameter"Afterpowerfail."(ID10913)issettoSTOP ,the
"Prog.execution"mustbesettoOFFandthentoON.
Afterapowerfailure,thealarmisindicated/activated.
Iftheparameter"Afterpowerfail. "(ID10913)issettoSTOP ,thedesired
owtemperatureismaintainedatthevalue,setinX1.
RampX5-X6(TemperaturerampingfromtimeX5toX6)
RampX7-X8(TemperaturerampingfromtimeX7toX8)
10903
10904
Settingthenumberofstepsforthechangeofthedesiredowtemperature
inselectedperiod.
OFF:
Thestepwisechangeisdisabled
Value:
Theperiodisdividedinthenumberofsteps
Example:
"X5"timeissetto100
"X5"temperatureissetto25°C
"X6"timeissetto150
"X6"temperatureissetto35°C
"RampX5-X6"issetto5
Result:
PeriodbetweenX5andX6is50hours.Temperaturechangeis10K.
Theprocesswillbe:
Starttemperature:25°C,after10hoursthetemperaturechanges
to27°C.Afterfurther10hoursthetemperaturechangesto29°C
andsoon.
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK9
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
Appl.continue(Applicationcontinue)
10912
SelectionhowtheECLComfortcontrollermustcontinueafterhaving
nishedtheoordryingprocess.
OFF:
Thedesiredowtemperaturewillbethevaluesetat
"X8"time
ON:
Thecontrollercontinueswiththeselectedapplication
andthesetmodeofthefunctionselector
Whenusingonly"Functionalheating"andnodemandforcontrolafter
theoordryingprocess,itisimportanttosetthedesiredtemperature
atX8.
(Commoncontroller>MENU>Floordrying>Curingheating>
"DesiredowT">Graph'srightpoint).
Afterpowerfail.(Afterpowerfailure)
10913
SelectionhowtheECLComfortcontrollermustcontinueafterapower
failure(powerhasbeenawayformorethanacceptedtime,setin"Max.
pwr.failure",ID10514).
Ifpowerfailurehappensin"Functionalheating"process,theoordryingcan
berestartedaccordingtotimeandtemperaturesettingforX1orstopped.If
stopped,thedesiredowtemperatureismaintainedatthevalue,setforX1.
Ifpowerfailurehappensin"Curingheating"process,theoordryingcanbe
restartedaccordingtotimeandtemperaturesettingforX4.Ifstoppedthe
desiredowtemperatureismaintainedatthevalue,setforX1.
STOP:
Thecontrollerstopstheoordryingprocessand
maintainsthetemperature,setatX1
START:
Thecontrollerstartstheoordryingprocessfrom
settingsinX1orX4
Torestarttheoordryingprocess:
Iftheparameter"Afterpowerfail."(ID10913)issettoSTOP ,the
"Prog.execution"mustbesettoOFFandthentoON.
Afterapowerfailure,thealarmisindicated.
Thealarmcanbereset.
10DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
X1(Starttimeforperiod1)
X2(Starttimeforperiod2)
X3(Starttimeforperiod3)
X4(Starttimeforperiod4)
10930
10931
10932
10933
Thetimethatmustelapsefromprocessstartforcontrollingthesetow
temperatureinthefunctionalheatingperiod.
Values:Setthetimes
Example1:
X1
=
50hours
X2
=
50hours
X3
=
200hours
X4
=
200hours
Result:
Thedesiredowtemperature,whichwillbemaintainedfrom
processstart,isthevalue,whichisindicated/setatX1in"Desired
owT".
50hoursafterprocessstart,thedesiredowtemperature,whichis
indicated/setatX2in"DesiredowT",willbemaintained.
200hoursafterprocessstart,thedesiredowtemperature,which
isindicated/setatX3in"DesiredowT",willbemaintained.
200hoursafterprocessstart,thedesiredowtemperature,which
isindicated/setatX4in"DesiredowT",willbemaintained.
Example2:
X1
=
50hours
X2
=
100hours
X3
=
150hours
X4
=
200hours
Result:
Thedesiredowtemperature,whichwillbemaintainedfrom
processstart,isthevalue,whichisindicated/setatX1in"Desired
owT".
50hoursafterprocessstart,thedesiredowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX2in
"DesiredowT".
150hoursafterprocessstart,thedesiredowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX3in
"DesiredowT".
200hoursafterprocessstart,thedesiredowtemperaturewill
graduallyrise/falltothevalue,whichisindicated/setatX4in
"DesiredowT".
Ifthefunctionalheatingperiodshouldnotbeused,X4canbeset0
h(zerohours).
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK11
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
X5(Starttimeforperiod5)
X6(Starttimeforperiod6)
X7(Starttimeforperiod7)
X8(Starttimeforperiod8)
10934
10935
10936
10937
ThetimethatmustelapsefromtimeX4forcontrollingthesetow
temperatureinthecuringheatingperiod.
Values:Setthetimes
Ifthetemperaturevalues,setatX4andX5,aredifferent,the
desiredowtemperaturechangesgraduallyfromtheX4value
totheX5value.
WhenX5issettoatimevalue,thedesiredowtemperaturestarts
withthevalue,setatX4.
Ifthecuringheatingperiodshouldnotbeused,X8canbeset0h
(zerohours).
12
DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
4.0ECLTool
4.1DataloggingforreportwithECLTool
BymeansoftheECLTooladatalogcanbereadfromtheECL
Comfortcontrollerinordertodocumenttheprocess.
Thelogmakesastampeach15minutes.Max.logtimeis40days.
Whenthelogmemoryisfull,theloggingstops.Astartoftheoor
dryingmightdeletetheexistinglogintheECLcontroller.
TheECLToolisfoundhere:http://heating.danfoss.com
ChooseTools&Software,selectDownload.DownloadtheUSB
driverandECLToolinstaller.
Theexe-lealsocontainsanECLToolinstructioninPDFleformat.
WhenrunningtheECLTool,besuretheversionis1.9.8.1orhigher.
ConnectioncablebetweenPCandECLComfortcontrollerisan
USBcable,havingUSB-Aplug(forPC)atoneendandUSB-Bplug
(fortheECLComfortcontroller)attheotherend.
Versioninformation,example:
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK13
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
4.2Shortget-goinginstruction
AfterhavingestablishedconnectionbetweenthePCandthe
ECLcontroller,the"Loadstandardparameters(recommended)"
isselected.
Allparametersandsettingsarelistedingroups.
Atthebottomoftheviewagraphbuttonis
present.Thenameis"Readlogs".
Byselectingthereadlogsbutton,adefaultgraphisshown.
Atthebottomofthedefaultgraphviewsomebuttonsarepresent:
Help.
OpensECLToolinstructioninPDFformat.
Print
ReadECLlogfromECLandshowgraph
ReadextendedlogfromECLandshowgraph.
ThisispossiblewithECLComfortcontrollershaving
rmware1.56orhigher.
Selectthelogbutton;agraphshowstheloggingsofthelisted
items.
Alewiththeindicatednameiscreatedandsaved.
IfchoosingYesforopeninginanexternalprogram(forexample
Excel),theprogramopenswiththedata.
Thegraphcanbezoomed/draggedinordertogetadesired
pictureforthereport.
Aright-clickonthegraphallowscopyfacilities.
Selectthebutton"Copygraphtoreportpage"inordertoinclude
thecurrentlyshowngraphinthereport.
Theprintbuttonwillstartthereportprinting.
14DEN-SMT/DK
VI.JM.P1.02
DanfossDistrictEnergy
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
5.0Miscellaneous
5.1ParameterIDoverview
IDParameterName
Settingrange
Factory
UnitOwnsettings
10512
Prog.execution
OFF;ONOFF
10514
Max.pwr.failure
5...300030
Min
10903
RampX5-X6
OFF,1...20
5
10904
RampX7-X8
OFF,1...20
5
10912
Appl.continue
OFF;ONOFF
10913
Afterpowerfail.
STOP/STARTSTOP
10930
X1
0-12000
h
10931
X2
0-12000
h
10932
X3
0-12000
h
10933
X4
0-12000
h
10934
X5
0-12000
h
10935
X6
0-1200360
h
10936
X7
0-1200720
h
10937
X8
0-12001080
h
Functionalheating
Factorysettings
DesiredowT:0.20(0=time;20=desiredowtemperature)
Curingheating
Factorysettings
DesiredowT:0.25(0=time;25=desiredowtemperature)
-||-
360.50(360=time;50=desiredowtemperature)
-||-
720.50(720=time;50=desiredowtemperature)
-||-
1080.25(1080=time;25=desiredowtemperature)
DanfossDistrictEnergy
VI.JM.P1.02
DEN-SMT/DK
15
InstallationGuideECLComfort210/296/310,Floor(Screed)DryingProgram
*087H9262*
*VIJMP102*
ProducedbyDanfossA/S©11/2015
/