ESP EM2WMEXSIGN User manual

Type
User manual
www.espuk.com
EM2W NM & M EXIT SIGN
EMERGENCY LIGHTING LUMINAIRE
INSTRUCTIONS AND TEST PROCEDURES
Month Test Sign Date Sign Date Sign Date Sign Date Sign Date
1 Functional
2 Functional
3 Functional
4 Functional
5 Functional
6 1 hour
7 Functional
8 Functional
9 Functional
10 Functional
11 Functional
12
1 Hour
3 Hour
1st year 2nd Year 3rd Year 4th Year 5th year
Unit 7 | Target Park | Shawbank Road | Lakeside | Redditch | B98 8YN | United Kingdom
T: +44 (0)1527 51 51 50 F: +44 (0)1527 51 51 43
TECHNICAL PARAMETER
Batteries installed or replaced: Nicd 4.8V 600mAH
Supply Voltage: 220-240V/50/60Hz
Charging Current: 85-90mAH
Charging Duration: 24 Hours
Batteries Protection: Overcharge and full discharge
Discharge Duration: more than 3 Hours
Lamp Source: High Power White LED
Max Intensity: 6100Mcd
Operation Indicator: Charge LED
Proration Rating: IP20
Operation Temperature: 0 - 60 Degrees C
Humidity: up to 95% Relative Humidity
Dimensions: 380 x 195 x 51mm
Weight: 1350g
Luminaire Type/Ref: Date of Installation: Location:
EM2W NM & M EXIT SIGN INSTRUCTIONS.indd 2-3 27/03/2014 09:16:44
INDICATION LED STATUE
Charge Green LED (RIGHT): ON: Power supply an full charge
OFF: Power supply fails
TEST BUTTON
Press the test button next to the Led indicator.
That would be AC supply switch to the DC supply.
IMPORTANT
Ensure the mains supply is isolated before undertaking any electrical
installation of product. Disconnect luminaires from the supply when
carrying out megger testing. Installation should be carried out by a qualied
electrician in accordance with the relevant IEE Wiring Regulations.
INSTALLATION
In order for the luminaire to become operational, the battery and the mains
power supply must be connected. An internal terminal block is used to
connect the luminaire to the mains power supply. To obtain access to this
terminal block and to the battery remove the cover of the main body by
unscrewing the two retaining screws, the connection socket arrangement
ensuring correct polarity. Determine the length of wire suspension required
and if necessary will permit the wire to be adjusted accordingly. When
required length is achieved re-lock mechanism, To avoid excess wire inside
the unit, wire can be cut to desired length and re-terminated on the pcb
thus ensuring no wire comes into contact with any other connections on the
pcb. Failure to ensure no excess wire inside the unit causing subsequent
damage will invalidate the warranty. Unit can then be re-assembled and
secured with the 2 retaining screws previously removed.
MOUNTING OF LUMINAIRE
This lamp can be wall mounted and ceiling mounted.
RECOMMENDED ROUTINE TEST PROCEDURE
The following test is designed to ensure the continued protection of your
premises and occupants. Because of the possibility of a failure of the
normal lighting supply occurring shortly after a period of testing, all tests
should whenever possible, be undertaken at times of least risk, e.g during
daylight hours.
ONCE A DAY
Visual inspection of battery charge led.
ONCE A MONTH
Each unit should be energised from its battery for about 30 seconds by
simulation of a failure of the normal lighting supply, to ensure the lamp
operates in the emergency condition.
TWICE A YEAR
Each unit should be energized from its battery for a continuous period of at
least one hour. Inspect the uorescent tube and if the ends are blackened
replace. It is recommended that for maintained luminaires the tubes are
replaced at intervals of no more than 1 year in order to retain the design
photometric characteristics.
AFTER THREE YEARS & EACH SUBSEQUENT YEAR
All units with specied durations in excess of 1 hour should be energised
for their full rating period.
TECHNICAL PARAMETER
Supply Voltage: 220-240V/50/60Hz
Bat
te
ries installed or replaced: Ni-cd 4.8V 600mah
Charging current:85-90mah
Charging duration: 24 hours
Discharging duration: more than 3 hours
Batteries protection: Overcharge and full discharge
Lamp source: High power white LED
Max Intensity: 6100mcd
Operation Indicator: Charge LED
Proration rating: IP20
Operation Temperature: 0 - 60 degrees C
Humidity: Up to 95% relative humidity
Dimensiions: 380 x 195 x 51 mm
Weight: 1350g
Indication LED Statue:
Charge Green LED (RIGHT):
ON: Power supply and full charge
Off: Power supply fails
Important:
Ensure the mains supply is isolated before undertaking any
electrical installation of product. Disconnect luminaries from
the supply when carrying out megger testing. Installation
should be carried out by a qualified electrician in accordance
with the relevant IEE Wiring Regulations.
Installation
In order for the luminaire to become operational, the battery
and the mains power supply must be connected. An internal
terminal block is usd to connect the luminaire to the mains
power supply. To obtain assess to this terminal block and to
the battery remove the cover of the main body by unscrewing
the two retining screws, The connection socket arrangement
ensuring correct polarity. Determine the length of wire
suspension required and if necessary will permit the wire to
be adjusted according ly. W
hen required length is achieved
re-lock mechanism. To avoid excess wire inside the unit, wire
can be cut to desired length and re-terminated on the pcb thus
ensuring no wire comes into contact with any other connections
on the pcb. Failure to ensure no e xcess wire inside the unit
causing subsequent damage will invalidate the warranty. Unit
can then be re-assembled and secured with the 2 retaining
screws previously removed.
N
L
terminal block
Connection
230V AC
N
L
Mounting of Luminaire
This lamp can be wall mounted and ceiling mounted.
Test button
Press the test button next to the Led indicator.
That would be AC supply switch to the DC supply.