ESP EMLED5WMBULK is a 5W LED IP65 MAINTAINED 3HR EMERGENCY BULKHEAD / EXIT SIGN. It is designed to comply with the recommended codes of practice for emergency lighting of premises and should be installed by a competent person in accordance with the relevant wiring regulations.

The luminaire has a rated input supply of AC 240V 50Hz and a rated output power of 28 P CS LED. It has an operating relative humidity of less than 90% and a battery specification of 3.6V 1800mAh 3Cell Ni-Cd, Stick. The battery temperature classification is 55°C continuous ambient temperature and the emergency duration is more than 3 hours. The change over time is less than 1 second.

ESP EMLED5WMBULK is a 5W LED IP65 MAINTAINED 3HR EMERGENCY BULKHEAD / EXIT SIGN. It is designed to comply with the recommended codes of practice for emergency lighting of premises and should be installed by a competent person in accordance with the relevant wiring regulations.

The luminaire has a rated input supply of AC 240V 50Hz and a rated output power of 28 P CS LED. It has an operating relative humidity of less than 90% and a battery specification of 3.6V 1800mAh 3Cell Ni-Cd, Stick. The battery temperature classification is 55°C continuous ambient temperature and the emergency duration is more than 3 hours. The change over time is less than 1 second.

EMLED5WMBULK
EMLED5WMBULKEX
5W LED IP65 MAINTAINED 3HR
EMERGENCY BULKHEAD / EXIT SIGN
Month Test
Sign Date Sign Date Sign Date Sign Date Sign Date
1 Functional
2 Functional
3 Functional
4 Functional
5 Functional
6 1 hour
7 Functional
8 Functional
9 Functional
10 Functional
11 Functional
12 3 Hour
1st year 2nd Year 3rd Year 4th Year 5th year
Unit 7 | Target Park | Shawbank Road | Lakeside | Redditch | B98 8YN | United Kingdom
T: +44 (0)1527 51 51 50 F: +44 (0)1527 51 51 43
E: sales@espuk.com
Luminaire Type/Ref: Date of Installation: Location:
TEST RECORD SHEET
W: www.espuk.com
www.espuk.com
GENERAL INFORMATION
Our products are designed to comply with the recommended
codes of practice for emergency lighting of
premises and be installed by competent person in accordance with the
relevant wiring regulations.
LUMINAIRE INFORMATION
Rated input supply: AC 240V 50Hz
Rated output power: 28 P CS LED
Operating relative humidity: Less than 90%
Battery Specification : 3.6V 1800mAh 3Cell Ni-Cd, Stick
Battery Temperature Classification: 55°C continuous ambient temperature
Emergency Duration: More than 3 Hours.
Change over time: Less than 1 second.
The Ta rating of this fitting is minimum 0 and maximum 40°
MONITORING
Green indicator lamp (LED) normally continuously ‘on’. Indicator lamp goes
out if A.C. supply or charger fails.
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed
Recommended routine test procedure in accordance with BS 5266
Daily check - check that the status GREEN LED indicator is illuminated
Monthly functional test - simulate a mains supply failure for approx. 30 secs by operation of key switch or
switching off a circuit breaker. Ensure normal supply is restored after test and the indicator status LED
is illuminated
Twice yearly conduct a one hour duration test - simulate a mains supply failure for one hour continuous test
by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and the
indicator status LED is illuminated
Annual full three hour duration test - conduct a three hour continuous duration test. Simulate a mains supply
failure for three hour continuous test by operation of key switch or switching off circuit breaker.
Ensure normal supply is restored after test and the indicator status LED is illuminated
If the luminaire fails any of the above tests, please contact a
GENERAL
ould be recycled in the
correct manner when it reaches the end of its life. Check local authorities for where facilities
exist. Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents
WARRANTY
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end user for
future reference and maintenance.
These instructions should be used to aid installation of the following product:
EMLED5
SAFETY
Installation of this luminaire should only be carried out by a
competent person to the current IEE Wiring Regulations (BS 7671)
Please isolate mains prior to installation/maintenance
Check the total load on the circuit (including when this lumina
exceed the rating of the circuit cable, fuse or circuit breaker
Please note the IP (Ingress of Protection) rating of this luminaire when deciding
the location for installation. This luminaire is suitable for indoor and outdoor use.
This product is Class II double insulated
This product is non-dimmable
A deep (150mm) clear diffuser is also available to provide double-sided signage if required.
It makes the product achieve a viewing distance of 28 meters.
This product is IP65 rated
INSTALLATION
Provide power to the required point of installation. Suitable IP rated junctions boxes
should be used where required
ng not to infringe with
any joists, gas or water pipes or electrical cables
feed the mains input through
Use a suitable IP rated 20mm compression gland
For non-maintained operation please wire up connector block as shown in Fig 3
For maintained operation (luminaire always on) please see Fig 4
For switchable maintained operation see Fig 5
Connect the battery via the plug and
socket on the PCB
Switch on the power supply and ensure
the LED indicator is illuminated Green
• Remove two screws
to remove diffuser
• Pull apart tabs (see Fig 2) to
gain access to the connections
Fig 1 Fig 2
Fig 3
Fig 4
Fig 5
Insert link
cable
Remove screws Pull apart tabs
Please contact your supplier.
d=30
EMERGENCY FUNCTION
Battery Specification - Ni-Cd 3.6V 1800mAh
A second / permanent live (marked ‘L’) should be provided to the fitting.
This will allow the fitting to sense when there is a mains power failure and activate emergency mode.
The light will operate at a reduced output in emergency mode.
Failure to provide a permanent live will cause the batteries to power the fitting when it is switched off.
This is not recommended as it will reduce the lifetime of the batteries.
Following a full discharge, a 16 hour charge will be necessary to fully re-charge the batteries.
On first operation a 24 hour charge will be required to fully charge the batteries.
The battery is charging when the green charge indicator LED is illuminated. This LED should remain lit
after the fitting is switched off.
It is advised that routine testing of emergency luminaires is undertaken and logged in order to ensure
that they are operating correctly.
Should luminaire fail to deliver a full 3hr emergency duration/illumination, a replacement battery
should be sought of the same specification. Please contact ESP for replacement battery option
with luminaire model number and batch code.
Photometrics files available from ESP Technical Support Team on request
electrician. See overleaf for test record sheet
  • Page 1 1
  • Page 2 2

ESP EMLED5WMBULK User manual

Type
User manual

ESP EMLED5WMBULK is a 5W LED IP65 MAINTAINED 3HR EMERGENCY BULKHEAD / EXIT SIGN. It is designed to comply with the recommended codes of practice for emergency lighting of premises and should be installed by a competent person in accordance with the relevant wiring regulations.

The luminaire has a rated input supply of AC 240V 50Hz and a rated output power of 28 P CS LED. It has an operating relative humidity of less than 90% and a battery specification of 3.6V 1800mAh 3Cell Ni-Cd, Stick. The battery temperature classification is 55°C continuous ambient temperature and the emergency duration is more than 3 hours. The change over time is less than 1 second.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI