13
3) Freeze Cycle: AMPS activated (water pan assembly completely closed). WV energizes.
74-sec. or 37-sec. timer starts. Comp and FM continue. Evaporator cooling.
Once 74-sec. or 37-sec. timer terminates, WV de-energizes and PM energizes.
a) AMU Diagnosis: AMU completes its rotation and AMPS is activated. If AM does
not rotate up, check for 115VAC at CB CN5 #1 (O) to neutral (W). If 115VAC is not
present, conrm ET is at 41°F (5°C) or higher. If ET achieved and AM does not
energize, replace CB. If 115VAC is present, check AM actuator cams A and B for
binding, actuator springs for proper connection, capacitor, and AM motor windings.
Repair or replace as needed. If AMPS does not indicate water pan assembly is fully
closed within 3 min. display shows "EE" and unit shuts down for 60 min. If error
recurs after icemaker resumes operation, display shows "EE" again and icemaker
shuts down. See "III.F. Error Codes."
b) Freeze Cycle Diagnosis: If Comp de-energizes once freeze begins, check
that appliance has not shut off on HPS ("on" display off). If so, check "1)b) HPS
Diagnosis" above. If"on" display is on, check for 115VAC at CB CN3 #9 (O) to
neutral (W). If 115VAC is not present, replace CB. Conrm Comp and FM continue.
Conrm that PM energizes after PM delay timer terminates and WV de-energizes
once 74-sec. or 37-sec. WV on timer terminates. Conrm evaporator is cooling.
If not, conrm HGV de-energized (not bypassing) and FM energizes, TXV
operating correctly, Comp is efficient, and refrigerant charge is correct. See "VIII.A.
Specication and Performance Data." Note: Refrigerant gauges should not be placed
on the icemaker until all other components have been conrmed.
c) Comp Diagnosis: If Comp is not energized, check for 115VAC at CB CN3 #9 (O).
If 115VAC is present, check for 115VAC at CR coil. If 115VAC is present, check CR
coil and contact continuity. Replace as needed. If CR is okay, check Comp start relay,
start capacitor, and motor winding continuity. If Comp is energized but evaporator
is not cooling, check for HGV leaking by or an inefficient Comp. See "VIII.A.
Specication and Performance Data."
d) FM: If Comp is energized but FM is not, check for 115VAC at CB CN3 #5 (BR) to
neutral. If 115VAC is not present, replace CB. If 115VAC is present, check capacitor,
motor winding, and fan blade for binding.
e) PM: After 74-sec. or 37-sec. timer terminates, conrm water is owing over
evaporator. If not, check for 115VAC at CB CN3 #1(BK) to neutral (W). If 115VAC is
not present, replace CB. If 115VAC is present and PM is de-energized, check PM
impeller for binding, capacitor, and motor winding continuity.
f) WV Diagnostics: WV energizes, 74-sec. or 37-sec. timer starts. Check that water
enters the water pan assembly. If not, check that the water supply line shut-off valve
is open and screens or external lters are clear. Check for 115VAC at CB CN3
#7 (V) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present
and WV does not energize, check for 115VAC at WV. If 115VAC is present, check
coil continuity. Ifopen, replace WV. 74-sec. or 37-sec. timer terminates. WV de-
energizes. If WV continues, check for 115VAC at CB CN3 #7 (V) to neutral (W). If
115VAC is present, and 74-sec. or 37-sec. timer has terminated, replaced CB. If WV
de-energizes and water continues to ll the reservoir, replace WV.