THEBEN LUNA 122 top2 RC EL Operating instructions

Type
Operating instructions

THEBEN LUNA 122 top2 RC EL is a digital twilight switch designed for lighting control in various applications. It features precise lux value setting for both switch-on and switch-off, allowing for customized light activation based on ambient brightness. The device enables programming of switching times in standard and special programs, providing flexibility for different scenarios. With its delay function, it prevents unwanted switching due to brief light fluctuations. Additionally, it offers manual or permanent switching options for temporary overrides.

THEBEN LUNA 122 top2 RC EL is a digital twilight switch designed for lighting control in various applications. It features precise lux value setting for both switch-on and switch-off, allowing for customized light activation based on ambient brightness. The device enables programming of switching times in standard and special programs, providing flexibility for different scenarios. With its delay function, it prevents unwanted switching due to brief light fluctuations. Additionally, it offers manual or permanent switching options for temporary overrides.

1
LUNA 121 top2 RC
1210100/ 1210200
LUNA 122 top2 RC
1220100/ 1220200
307031
Digital twilight
switch
EN
1. Basic safety information 4
2. Proper use 4
Disposal 4
3. Installation and connection 5
Mounting the time switch 5
Connecting the cable 7
Disconnecting the cable 7
Connection/installation of
light sensor 8
4. Device description 10
2
Display & buttons 10
Operating instructions 11
Overview of navigation menu 12
Initial operation 13
5. Settings and functions 14
Set lux values 14
Set delay 15
Program switching time in
standard program 16
Program switching time in
special program 1 17
Delete switching program 19
Set Easter rule 19
Allocate sensors 20
Activating PIN code 20
Setting manual or permanent
switching 21
3
Set external input 22
Hour counter 23
Using the OBELISK top2
memory card 24
Resetting the twilight switch 25
6. Technical data 26
7. Contact 27
4
1. Basic safety information
Danger of death through electric shock or fire!
Installation should only be carried out by a
qualied electrician!
WARNING
The device is designed for installation on DIN top hat
rails (in accordance with EN 60715)
!OBELISK top2 memory card: Avoid mechanical overload
and contamination during storage/transportation
2. Proper use
The digital twilight switch is used for lighting equipment
(streets), external stairways, display windows, entrances etc.
Only for use in closed, dry rooms
!Do not use on safety devices, e.g. escape route doors, re
safety equipment etc.
Disposal
Dispose of device in environmentally sound manner
5
3. Installation and connection
Mounting the time switch
Danger of death through electric shock or fire!
Installation should only be carried out by a
qualied electrician!
WARNING
click
6
45° cable
Plug-in
screwless termi-
nal NC contact
OBELISK top2
memory card
(9070404)
Test tap
Load line connection
Mount on DIN top hat rails (as dened in EN 60715)
Switched voltage-free
Ensure device cannot be switched on
Check absence of voltage
Earth and bypass
Cover or shield any adjacent live components
7
Connecting the cable
Wiring diagrams LUNA 121 top2 RC / LUNA 122
top2 RC
C1
1 2 3
N
L
L
L N
Ext1
max. 100 m
Data
RC DCF
+
Lux
max. 100 m
C2
C1
1 2 3
4 5 6
N
L
L
L N
Ext1
max. 100 m
max. 100 m
Ext2
Data
RC DCF
+
Lux
max. 100 m
Strip cable to 8 mm (max. 9)
Insert cable in the open DuoFix® plug-in terminal at 45°
L2 cables per terminal position possible
To open the DuoFix® plug-in terminal, press screwdriver
downwards
Disconnecting the cable
Use the screwdriver to push the load line connection
opener downwards
8
Connection/installation of light sensor
!Take length of connection cable into account: max. 100 m
(2 x 1.5 mm2), max. 50 m (2 x 0.75 mm2)
!Avoid running sensor wiring parallel to mains power
cables
Ensure correct polarity. Disconnect power source
Mounting light sensor 907 0 415
Mounting light sensor: 0.5-2.5 mm2, strip cable by 10 mm
(max. 11 mm)
max .o4mm
Installing light sensor 907 0 456
Installing light sensor: 0.25-1.5 mm2, strip cable by 8 mm
(max. 9 mm)
9
8-9 mm
max. 10 mm
Ø 5-10 mm
<9 mm Ø 20 mm
ca. 63 mm
IP 66
IP 40
10
4. Device description
Display & buttons
MENU OK
OKMENU
0 6 12 18 24
Programmed
switching times
Date display
Channel status
C1, C2
ON = On
OFF = Off
Time display
Days of the week
from 1 to 7
Display of the active buttons
with the relevant function
Activate display
Open menu
Cancel menu
ESC
(leave menu)
Save
selection
Confirm
selection
Options
are displayed
Sunrise/sunset
display
DCF antenna display
11
Operating instructions
YES
Confirmation
Press
OK
NO
Modify/
Change
Press
t u
1. Read text line
text/symbol represents
query
2. Make a decision
12
Overview of navigation menu
LIGHT
MENU
MANUAL
PROGRAM TIME/DATE
OPTIONS END
CHANNEL C1 SENSORS
PERM ON
PERM OFF
OVERRI ON
TIMER
OPERATING
HOUR
EXT INPUT
HOLIDAY
CHANNEL C1
STANDARD
EXTRA 1
EXTRA 2
END
LCD
ILLUMINATION
LANGUAGE
PIN
FACTORY
SETTINGS
INFO
END
CHANNEL C1
LUX VALUES
DELAY TIME
END
TIME
SET DATE
SU--WI
WEEK DAY
FORM DATE
FORM TIME
EASTER RULE
END
END
u u u u
uu u
19 10 15
C1 OFF C2 OFF
9:40 46
13
Initial operation
DEUTSCH
ENGLISH
ESPANOL
FRANCAIS
FORM DATE
YEAR
MONTH
DAY
FORM TIME
HOUR
MINUTE
SU-WI EUROPE
u
28 02 15
C1 ON C2 OFF
9:4046
...
Set language, date, time as well as summer/winter time
(SU-WI)
Press any button and display follows on screen (see gure)
LIf all settings are performed, the screen alternately shows
the automatic display and READING
LIf a sensor is connected, the measured lux value appears
on screen (only during mains operation).
14
5. Settings and functions
Set lux values
LIGHT CHANNEL
C1
LUX VALUE LUX ON
Switch light off
in the mornings
Switch light on
in the evening
LUX OFF
MONDAY MONDAY
MONDAY
15 lx
MONDAY
15 lx
SAVE COPY
COPY
ADD TUESDAY
ADD TUESDAY
DELAY TIME
END
MENU
...
u
u
u
u
u
SAVE
LThe device has been preset at 15 lx for the switch on/
switch off level
Press MENU
Select LIGHT and press OK to conrm
Select CHANNEL C1 or C2, conrm with OK
Select LUX VALUE and press OK to conrm
Select LUX ON and press OK to conrm
MONDAY is displayed, conrm with OK
Set LUX VALUE, conrm with OK
Select COPY or SAVE, conrm with OK
To save press u and press OK to conrm
To copy press OK
15
Typical brightness values
Daylight (bright) 80.000 lx
Ofce accommodation 500 lx
Hallways and stairs 100–150 lx
Street lighting 15 lx
Full moon ca. 0,3 lx
Set delay
LIGHT CHANNEL
C1
LUX VALUES
DELAY TIME ON DELAY
OFF DELAY
MINUTE
MINUTE
SECONDS
SECONDS
END
MENU
u
u
u
LAn on/off delay of 1 minute is preset to avoid faulty ope-
ration caused by lightning, car headlights etc. When the
delay ends the channel status will ash ON/OFF.
Press MENU
Select LIGHT and press OK to conrm
Select CHANNEL C1 or C2, conrm with OK
Select DELAY TIME, conrm with OK
Select ON DELAY, conrm with OK
MODIFY HOUR, use the + or – buttons to change hour and
minute and conrm with OK.
16
Program switching time in standard
program
PROGRAM
MENU
CHANNEL
C1
STANDARD
EXTRA 1
EXTRA 2
END
u
ª
ª
u
or
Switching
time for
one day
MEM FREE 84
NEW
NIGHT BREAK LIGHT ON
HOUR
MINUTE
MONDAY
DURATION
UNTIL
SAVE
COPY
ADD TUESDAY
SAVE
Copy switching to other days of
the week. The day of the week
always relates to a start time
Start time
u
u
LA switching time always consists of a start time and an
end time
LThere are 84 memory cells available
17
Example: Switch on sports hall lighting from Mon–Fri, 7:30 to
12:00 hrs
Press MENU
Select PROGRAM and press OK to conrm
Select CHANNEL C1 or C2, conrm with OK
Select STANDARD, conrm with OK
Select NEW, conrm with OK
Select NIGHT BREAK or LIGHT ON, conrm with OK
Set required turn-on time (Mo–Fr, 7:30), conrm with OK
Set DURATION UNTIL, conrm with OK
Select COPY, conrm with OK
ADD TUESDAY is displayed, conrm by pressing OK and also
conrm the days We, Th, Fr by pressing OK.
Continue with u until SAVE is displayed.
Conrm by pressing OK.
Repeat all steps for the turn-off time, however instead of
selecting ON with u select OFF and enter 12:00 for hour and
minute.
Program switching time in special program 1
Special programs 1 and 2 are simple annual programs that a
higherpriority than the standard program
The following can be entered in the special program:
LUX ON/LUX OFF
one night switch off/day switch on with length without
naming day of the week
as many date entries as required
Special program in the holidays from Mon-Sun, e.g. 1.8.–17.8.
with alternative night switch off and lux values
18
LUX ON
LUX OFF
PROGRAM
MENU
CHANNEL
C1
STANDARD
EXTRA 1
EXTRA 2
END
u
u
u
u u u
MEM FREE 84
NIGHT BREAK
DURATION
UNTIL
LIGHT ON
DURATION
UNTIL
NEW DATE
FIX DATE
BEFORE/
AFTER EASTER
EVERY YEAR START YEAR
END YEAR
CHECK DATE
MODIFY DATE
DELETE DATE
START MONTH
START DAY
START HOUR
...
...
19
Delete switching program
CHANNEL C1
MENU
u
u
u
SINGLE
DELETE ALL
PROGRAM
NEW
CHECK
MODIFY
DELETE
STANDARD
EXTRA 1
EXTRA 2
END
Press MENU
Select PROGRAM and conrm with OK
Select CHANNEL C1 or C2, conrm with OK
Select STANDARD; EXTRA 1 or EXTRA 2, conrm with OK
Select DELETE, conrm with OK
Select SINGLE or DELETE ALL, conrm with OK
Set Easter rule
LThe EASTER RULE can be set using menu item TIME/DATE
Easter holiday dates in Germany
Public holiday days before/after Easter Sunday
Monday before
Lent
– 48
Good Friday – 2
Easter Monday + 1
Ascension + 39
Whit Monday + 50
Corpus Christi + 60
20
Allocate sensors
LThe SENSORS are allocated in the menu under OPTIONS
OPTIONS
MENU
SENSORS
OPERATING
HOURS METER
EXTERNAL
OUTPUT
LCD
ILLUMINATION
CHANNEL C1
1 SENSOR
RECOGNISED
NO
SENSOR
1 ACTIVE
SENSOR
SENSOR 1
READING
SENSOR 1
ACTIVE DEACTIVATE
u u
u
u
u
u
...
*red LED ashes
on the sensor
*
Press MENU (see g.)
Connection options:
1 LUNA + max. 4 light sensors
1 LUNA + max. 3 light sensors + 1 DCF antenna
max. 10 LUNA
Σ max. 16 devices (LUNA + light sensors)
LPresetting: all connected sensors are active for all chan-
nels. The sensor that sends the lowest lux value is active
Activating PIN code
The PIN code is set in OPTIONS via the menu.
LIf you have forgotten your PIN, call the Theben Hotline.
LHave the serial number ready
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27

THEBEN LUNA 122 top2 RC EL Operating instructions

Type
Operating instructions

THEBEN LUNA 122 top2 RC EL is a digital twilight switch designed for lighting control in various applications. It features precise lux value setting for both switch-on and switch-off, allowing for customized light activation based on ambient brightness. The device enables programming of switching times in standard and special programs, providing flexibility for different scenarios. With its delay function, it prevents unwanted switching due to brief light fluctuations. Additionally, it offers manual or permanent switching options for temporary overrides.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI