TECHNIBEL 387107060 User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

TECHNICAL DATA
& SERVICE MANUAL
OUTDOOR UNIT: GRV180C5TA-
GRV180C5TAB-
GRV180L5TA-
GRV180L5TAB-
GRV220C5TA-
SPLIT SYSTEM AIR CONDITIONER
0.8180.268.1 09/2004
Model No. Product Code No.
GRV220C5TA- 387107062
387107068GRV180C5TAB-
Model No. Product Code No.
GRV180C5TA- 387107059
GRV180L5TA- 387107060
387107069GRV180L5TAB-
IMPORTANT!
Please read before installation
This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important to install or
service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state and national electrical codes.
Pay close attention to all warning and caution notices given in
this manual.
•The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.
SPECIAL PRECAUTIONS
During installation, connect before the refrigerant system and
then the wiring one; proceed in the reverse orden when removing
the units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.
Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked, to ensure the grounding.
Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause
accidental injury and death.
Ground the unit following local electrical codes.
The Yellow/Green wire cannot be used for any connection
different from the ground connection.
Connect all wiring tightly. Loose wiring may cause overheating
at connection points and a possible fire hazard.
Do not allow wiring to touch the refrigerant tubing, compressor,
or any moving parts of the fan.
Do not use multi-core cable when wiring the power supply and
control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.
When installing...
... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.
... In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
When connecting refrigerant tubing
Keep all tubing runs as short as possible.
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of the flare
and union tubes before connecting them; screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.
Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.
When servicing
Turn the power OFF at the main power board before opening
the unit to check or repair electrical parts and wiring.
Keep your fingers and clothing away from any moving parts.
Clean up the site after the work, remembering to check that no
metal scraps or bits of wiring have been left inside the unit being
serviced.
Ventilate the room during the installation or testng the refrigeration
system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
2
Page
1. OPERATING RANGE 4
2. SPECIFICATIONS 5
2-1 Unit specifications 5
2-2 Major Component specifications 10
2-3 Other Component specifications 15
3. DIMENSIONAL DATA 17
4. REFRIGERANT FLOW DIAGRAM 19
5. PERFORMANCE DATA 22
5-1 Performance Charts 22
5-2 Cooling Capacity 27
6. ELECTRICAL DATA 32
6-1 Electrical characteristics 32
6-2 Electric Wiring Diagram 37
6-3 System Wiring Diagram 39
Table of Contents
3
1. OPERATING RANGE
(
*) SCL MODEL : -15°C D.B.
Temperature Indoor Air Intake Temp.
O
utdoor Air Intake Temp.
43°C D.B.
Cooling Maximum
Minimum
(
*)19°C D.B.
32°C D.B. / 23°C W.B.
19°C D.B. / 14°C W.B.
4
2. SPECIFICATIONS
2-1 Unit Specifications
GRV180C5TA-
Power source
Voltage rating
Performance * MCAV180C5VA-
Capacity kW
BTU/h
Air circulation (High) m³/h
Moisture removal (High) Liters/h
Electrical Rating
Available voltage range V
Running amperes A
Power input W
Power factor %
C.O.P. W/W
Compressor locked rotor amperes A
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment g
Refrigerant control
Operation Sound Hi dB-A
Refrigerant tubing connections
Max. allowable tubing length at shipment m
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Dimensions & Weight
Unit dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
2200
7,5
0,29
230V
994
413
52
57
6,35 (1/4")
830
2,3
Cooling
10,00
760
198 ~ 264
2
20 - 240V ~ 50Hz
Cooling
5,00
17063
713
1(Hi)
630
R
otary (Hermetic)
R
407C / 1760
12,7(1/2")
Flare type
305
47
96
2,3
46
C
apillary tube
5
GRV180C5TAB-
Power source
Voltage rating
Performance * MCAV180C5VA-
Capacity kW
BTU/h
Air circulation (High) m³/h
Moisture removal (High) Liters/h
Electrical Rating
Available voltage range V
Running amperes A
Power input W
Power factor %
C.O.P. W/W
Compressor locked rotor amperes A
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment g
Refrigerant control
Operation Sound Hi dB-A
Refrigerant tubing connections
Max. allowable tubing length at shipment m
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Dimensions & Weight
Unit dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
*For other INDOOR UNITS' MODELS, please refer to catalogue
2
20 - 240V ~ 50Hz
230V
Cooling
5,00
17063
760
2,3
Cooling
198 ~ 264
10,50
2250
93
2,2
52
1(Hi)
R
otary (Hermetic)
R
407C / 1660
C
apillary tube
50
Flare type
7,5
6,35 (1/4")
12,7(1/2")
630
830
305
713
994
413
52
57
0,29
6
GRV180L5TA-
Power source
Voltage rating
Performance * MCAV180C5VA-
Capacity kW
BTU/h
Air circulation (High) m³/h
Moisture removal (High) Liters/h
Electrical Rating
Available voltage range V
Running amperes A
Power input W
Power factor %
C.O.P. W/W
Compressor locked rotor amperes A
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment g
Refrigerant control
Operation Sound Hi dB-A
Refrigerant tubing connections
Max. allowable tubing length at shipment m
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Dimensions & Weight
Unit dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
12,7(1/2")
630
Flare type
7,5
R
otary (Hermetic)
R
407C / 1670
C
apillary tube
6,35 (1/4")
47
0,29
830
305
713
994
413
2
20 - 240V ~ 50Hz
230V
52
57
2,3
10,00
2200
760
198 ~ 264
1(Hi)
96
2,3
46
Cooling
Cooling
5,00
17063
7
GRV180L5TAB-
Power source
Voltage rating
Performance * MCAV180C5VA-
Capacity kW
BTU/h
Air circulation (High) m³/h
Moisture removal (High) Liters/h
Electrical Rating
Available voltage range V
Running amperes A
Power input W
Power factor %
C.O.P. W/W
Compressor locked rotor amperes A
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment g
Refrigerant control
Operation Sound Hi dB-A
Refrigerant tubing connections
Max. allowable tubing length at shipment m
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Dimensions & Weight
Unit dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
*For other INDOOR UNITS' MODELS, please refer to catalogue
2
20 - 240V ~ 50Hz
230V
Cooling
5,00
17063
760
2,3
Cooling
198 ~ 264
10,50
2250
93
2,2
52
1(Hi)
R
otary (Hermetic)
R
407C / 1660
C
apillary tube
50
Flare type
7,5
6,35 (1/4")
12,7(1/2")
630
830
305
713
994
413
52
57
0,29
8
GRV220C5TA-
Power source
Voltage rating
Performance * MCAV220C5VA-
Capacity kW
BTU/h
Air circulation (High) m³/h
Moisture removal (High) Liters/h
Electrical Rating
Available voltage range V
Running amperes A
Power input W
Power factor %
C.O.P. W/W
Compressor locked rotor amperes A
Features
Fan speed
Compressor
Refrigerant / Amount charged at shipment g
Refrigerant control
Operation Sound Hi dB-A
Refrigerant tubing connections
Max. allowable tubing length at shipment m
Refrigerant Narrow tube mm(in.)
tube diameter Wide tube mm(in.)
Dimensions & Weight
Unit dimensions Height mm
Width mm
Depth mm
Package dimensions Height mm
Width mm
Depth mm
Weight Net kg
Shipping kg
Shipping volume
m
3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Remarks:
Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 7°C D.B. / 6°C W.B.
2
20 - 240V ~ 50Hz
230V
C
ooling
198 ~ 264
830
C
ooling
R
407C / 2400
C
apillary tube
1(Hi)
R
otary (Hermetic)
Flare type
7,5
6,35 (1/4")
1
5,88 (5/8")
835
850
305
913
1000
400
67,0
76,0
0,37
50
5,90
20134
3,3
13,00
2750
92
2,1
70
9
2-2 Major Component Specifications
Outdoor Unit: GRV180C5TA-
Compressor
Type
Compressor model
Nominal output W
Compressor oil…Amount cc.
Coil resistance (Ambient temp. 25°C)
Safety devices Type
Overload relay
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output W
Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil
Rows
Fin pitch mm
Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Operating amp.(Ambient temp.25°C) -
R
otary (Hermetic)
C-S: 3,422
8
0807045B C-2RN170H5W
1700
FV68S…800
C-R: 1,353
nternal protector
Propeller
S
MEN 5192672 OR / KFG6S-51SA5P - 1
40
400
-
A
utomatic opening
A
utomatic reclosining
2
A
luminium plate fin / Copper tube
440
W
HT-PNK: 218,7 / 201
1…. Ø 400
6…910 / 6…908
43 / 40
B
RN-WHT: 83,4 / 98,5
A
crylic baked-on enamel finish
I
nternal thermal protector
130 ± 5
2
1,8
0,508
83 ± 15
10
Outdoor Unit: GRV180C5TAB-
Compressor
Type
Compressor model
Nominal output W
Compressor oil…Amount cc.
Coil resistance (Ambient temp. 20°C)
Safety devices Type
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output W
Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil
Rows
Fin pitch mm
Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
R
otary (Hermetic)
4
JS350EAA( JSM671 - 48 )
1700
R
B68A or FREOL ALPHA68M 700
C-R: 0,957
C-S: 3,617
45
400
nternal protector
A
utomatic opening
A
utomatic reclosining
Propeller
1…. Ø 400
S
MEN 5192672 OR / KFG6S-51SA5P - 1
6…910 / 6…908
43 / 40
B
RN-WHT: 83,4 / 98,5
W
HT-PNK: 218,7 / 201
I
nternal thermal protector
130 ± 5
83 ± 15
2
440
A
crylic baked-on enamel finish
A
luminium plate fin / Copper tube
2
1,8
0,508
11
Outdoor Unit: GRV180L5TA-
Compressor
Type
Compressor model
Nominal output W
Compressor oil…Amount cc.
Coil resistance (Ambient temp. 25°C)
Safety devices Type
Overload relay
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output W
Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil
Rows
Fin pitch mm
Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Crank case heater
Operating amp.(Ambient temp.25°C)
240 V - 30 W
A
utomatic reclosining
-
A
utomatic opening
40
400
-
R
otary (Hermetic)
8
0807045B C-2RN170H5W
1700
FV68S…800
C-R: 1,353
C-S: 3,422
nternal protector
130 ± 5
Propeller
1…. Ø 400
S
MEN 5192672 OR / KFG6S-51SA5P - 1
43 / 40
B
RN-WHT: 83,4 / 98,5
W
HT-PNK: 218,7 / 201
I
nternal thermal protector
6…910 / 6…908
83 ± 15
2
440
A
crylic baked-on enamel finish
A
luminium plate fin / Copper tube
2
1,8
0,508
12
Outdoor Unit: GRV180L5TAB-
Controller PCB
Compressor
Type
Compressor model
Nominal output W
Compressor oil…Amount cc.
Coil resistance (Ambient temp. 20°C)
Safety devices Type
Overload relay
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output W
Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil
Rows
Fin pitch mm
Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
R
otary (Hermetic)
4
JS350EAA( JSM671 - 48 )
1700
R
B68A or FREOL ALPHA68M 700
C-R: 0,957
C-S: 3,617
nternal protector
-
A
utomatic opening
A
utomatic reclosining
Operating amp.(Ambient temp.25°C) -
45
400
Crank case heater 240 V - 30 W
Propeller
1…. Ø 400
S
MEN 5192672 OR / KFG6S-51SA5P - 1
6…910 / 6…908
43 / 40
B
RN-WHT: 83,4 / 98,5
W
HT-PNK: 218,7 / 201
I
nternal thermal protector
J
ohnson Control
A
crylic baked-on enamel finish
A
luminium plate fin / Copper tube
2
1,8
0,508
130 ± 5
83 ± 15
2
440
13
Outdoor Unit: GRV220C5TA-
Compressor
Type
Compressor model
Nominal output W
Compressor oil…Amount cc.
Coil resistance (Ambient temp. 25°C)
Safety devices Type
Overload relay
Operating Temp. Open °C
Close °C
Run capacitor µF
VAC
Fan & Fan Motor
Type
Q'ty ……. Dia.
Fan motor model…Q'ty
No. Of poles…rpm (230 V, High)
Nominal output W
Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
Heat Exch. Coil
Coil
Rows
Fin pitch mm
Face area
m
2
External Finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
R
otary (Hermetic)
8
0244035 C-RN220H5A
2200
FV68S…1350
C-R: 0,777
C-S: 2,408
nternal protector External protector
-
OL-D24
A
utomatic opening 150 ± 5
A
utomatic reclosining 63 ± 10
Operating amp.(Ambient temp.25°C)
-
Tripin6to16sec.at59A
40
400
Crank case heater 240 V - 30 W
Propeller
1…. Ø 460
K
FC6S-51B5P OR / KFG6S-51SA5P - 1
6…860 / 6…856
50 / 62,6
B
RN-WHT: 95,9 / 98,1
W
HT-YEL: 55,4 / 56,7
Y
EL-PNK:7,2/7,4
I
nternal thermal protector
130 ± 5
83 ± 15
5,0
0.610
A
crylic baked-on enamel finish
440
A
luminium plate fin / Copper tube
2
2
14
2-3 Other Component Specifications
Outdoor Unit: GRV180C5TA-
GRV180C5TAB-
GRV180L5TA-
GRV180L5TAB-
Power Relay
Type
Coil Rating
Coil resistance (at 23°C)
k
Contact Rating
Pressure Transducer ( *Johnson Control)
Type
Range Bar
Factory Setting Bar
1
4to24
2
0
(
*Only for GRV180L5TAB)
2
1 ± 15%
A
C 220 V , 25 A
P
35 AC
G
7L-2A-TUB
A
C 200-240 V ~ 50/60 Hz
15
Outdoor Unit: GRV220C5TA-
Thermostat (Fan Speed Control 23S)
Type
Switching Temp. °C high LOW 28.5 ± 1
°C low HIGH 31 ± 1
Magnetic Contactor (MG)
Type
Coil Rating
A
C 220-240 V ~ 50 HAC 220-240 V ~ 50 Hz
Coil resistance (at 20°C)
Contact Rating (Main)
A
C 220 V , 20 A AC 240 V , 20 A
H
E-20FT31B or CLK-20J-S20A
1
.050 ± 15% (at 25°C) 1116 (at 20°C)
YTB-S383
16
3. DIMENSIONAL DATA Outdoor Unit: GRV180C5TA-
GRV180C5TAB-
GRV180L5TA-
GRV180L5TAB-
Air discharge
Air intake
538 146
307
337
4 ø12 holes
830
19
630
305
61
95
Wide tube service valve
ø12.7 (1/2")
Narrow tube service valve
ø6.35 (1/4")
Unit : mm
17
Outdoor Unit: GRV220C5TA-
Wide tube service valve ø15.88 (5/8")
Narrow tube service valve ø6.35 (1/4")
Check port ø6.35 (1/4")
86
88
155
57
7386
229
285
835
620130 100 55
20
20
325
850
250250
560
6 ø3.1 holes
Air intake
Air discharge
Unit : mm
18
4. REFRIGERANT FLOW DIAGRAM
Indoor Unit: Outdoor Unit: GRV180C5TA-
Indoor Unit: Outdoor Unit: GRV180C5TAB-
19
Indoor Unit: Outdoor Unit: GRV180L5TA-
Indoor Unit: Outdoor Unit: GRV180L5TAB-
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

TECHNIBEL 387107060 User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI