This document is the exclusive property of Bouyer, it must not be disclosed or reproduced without the written consent of Bouyer.
This document is not legally binding. We reserve the right to modify descriptions and specifications without prior notice.
VACIE range
Vulca Voice
Installation instructions
Ref: 596384
Date: 16/11/2015
Version: 1
Remark: the connection must IMPERATIVELY be made on the terminals of the input marked
CIE1. The CIE2 input is not operational for the link with the CIE.
The table below summarises the different configurations enabling the activation of the "Voice
Alarm" condition as well as the monitoring of the VACIE link by the CIE:
Monitoring voltage whose level and
polarity depend on the CIE
Monitoring of the presence of the end-of-line resistor Rfl
(defined by the CIE manufacturer)
The value of Rfl depends directly on the reference of the CIE connected.
Remark concerning General Fault information:
In the connection diagram above, this information is available on the terminal block marked
CIE1 between points 3 and 4; it is also available between points 3 and 4 of the terminal
marked CIE2.
4.3.5. Auxiliary Input
The system has one Auxiliary input, stereo type, asymmetric, 0dBu.
4.3.5.1. Cable length and type
The cross section of the cable must be at least 0.28mm2 and the connection distance must
be less than 3 m.
4.3.5.2. Connection
The connection is made on the 9U enclosure, on the top of the enclosure by means of 2
RCA sockets (1 red and 1 white).
There is no particular specification for the type of cable to be used.
If there are interfering signals present (noise, hum), connect the non-safety source to the
earth.
4.3.6. Animation Inputs
The system has one Animation input, mono type, symmetrical, -30dBu/0dBu.
4.3.6.1. Cable length and type
The cross section of the cable must be at least 0.28 mm2 and the connection distance must
be less than 3 m.
4.3.6.2. Connection
The -30 dBu sensitivity enables the connection of the GZ2802 product via a 6.35mm
socket; if a GZ2802 is connected, it may be necessary to earth the GZ2802 frame to avoid
problems with a low frequency hum. -30dbu/0dbu is selected via a configuration item in
the menu accessible in the HMI.
The connection is made: