Powertronix 20kVA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

Manual Registration
Prelim Page i3x3 UPS Preliminary Pages
Issue 2 - November 2001
Manual Registration
S THIS MANUAL IS A CONTROLLED DOCUMENT AND WILL BE PERIODICALLY UPĆ
DATED.
S IN ORDER TO ENSURE THAT YOU RECEIVE ANY AMMENDMENT PLEASE REGĆ
ISTER THIS MANUAL WITH THE TECHNICAL SUPPORT DEPARTMENT BY REĆ
TURNING A COPY OF THIS FORM TO:
Manual Registration
Number
Name of Registered Holder
Address of
Holder
Company
Name/Building
Street/Road
Area/region
Town/City
County/State
Post/Zip Code
Country
Telephone Number
FAX Number
E Mail Address
Amendment Record
Amendment Record
Service Manual
Manual Serial
Number:
Please enter the Manual Serial Nº
for future record
Issue
Issue
Date
Amendment Amended By Date
1
Initial issue
ć ć
Service Manual
Amendment Record
Prelim Page iii 3x3 UPS Preliminary Pages
This Service manual contains information concerning the installation operation and service of the folĆ
lowing UPS
EQUIPMENT PART NUMBER
With battery Without battery
10 kVA UPS
15 kVA UPS
20 kVA UPS
30 kVA UPS
UTILITY
SUPPLY
WARNING
PLEASE
NOTE
Service Manual
Limitations of Use
Prelim Page iv 3x3 UPS Preliminary Pages
Issue 2 - November 2001
Limitations of Use
ELECTROMAGNETIC COMPATABILITY
The equipment covered by this manual complies with the requirements of the EMC DirecĆ
tive 89/336/EEC and the published technical standards. Continued compliance requires
installation in accordance with these instructions and use of manufacturer approved accesĆ
sories only.
WARNINGThe UPS is a Class A product.
When used in a domestic environment a unit may cause radio interference,
If this is the case the user may be required to take additional measures
WARNING HIGH EARTH LEAKAGE CURRENT.
Earth connection is essential before connecting the utility supply.
This equipment must be earthed in accordance with local electrical codes.
WARNING This UPS does not incorporate automatic backĆfeed protection. A warning label must be
fitted to all external primary power isolators stating:
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS CIRCUIT.
The UPS should not be supplied from electrical power systems of the `IT'
(Impédance à Terre) type.
(IEC 364 Ć ELECTRICAL INSTALLATION OF BUILDINGS)
Note: Where use on `IT' systems is required an optional input isolation transformer should
be fitted.
CAUTION This equipment is fitted with RFI suppression filters
Earth leakage exceeds 3.5mA but is less than 300mA.
Transient and steadyĆstate earth leakage currents, which occur when starting the equipĆ
ment, should be taken into account when selecting instantaneous RCCB or RCCD devices.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCCD.
These products are intended for Commercial/Industrial use only, and are not suitable for
use in any life support applications.
Service Manual
Important Instructions for safe use
Prelim Page v 3x3 UPS Preliminary Pages
Important Instructions for safe use
GENERALThe UPS must be approved engineer before it is put into serĆ
vice. Failure to observe this condition will invalidate any implied warranty.
In common with other types of high power equipment, dangerous voltages are present with
the UPS and battery enclosure. The risk of contact with these voltages is minimised as the
live component parts are housed behind a hinged lockable door.
Further internal safety screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner, followĆ
ing the recommended operating procedures.
All equipment maintenance and servicing procedures involving internal access, should be
carried out by trained personnel.
The UPS is for indoor use only. It must be protected from rain or excessive moisture and
installed in a clean environment, free from flammable liquids, gasses, or corrosive subĆ
stances. Do not put drinks, plants, or any other containers holding liquids, on top of the unit.
BATTERIES Battery manufacturers supply details of the necessary precautions to be observed when
working on, or in the vicinity of, a large bank of battery cells. These precautions should be
followed at all times.
Particular attention should be paid to the recommendations concerning local environĆ
mental conditions and the provision of protective clothing, first aid and fireĆfighting facilities.
TEST EQUIPMENT
When the battery is under charge it is earthĆreferenced about its midĆpoint e.g. if the battery
is being charged at 460V the battery extremities will be =230V and Ć230V with respect to
neutral (earth). When using mains powered test equipment such as oscilloscopes in the
UPS high voltage area, always use a differential mode of operation to avoid the need to disĆ
connect the oscilloscope frame earth.
PERSONNEL
When working inside the UPS (trained personnel only) is recommended that protection be
worn to prevent eye damage, should an electric arc be struck by mishandling or severe
electrical fault.
Some of the power components are very heavy. If their removal is necessary ensure that
sufficient manpower is available, otherwise use adequate mechanical handling equipment.
When working in the general area of the UPS where high voltages are present, a second
person should be standingĆby to assist and summon help in case of accident.
Service Manual
Personnel Categorisation
Prelim Page vi3x3 UPS Preliminary Pages
Issue 2 - November 2001
Personnel Categorisation
The following definitions are given to categorise the scope, and use of this service
manual:
Operator/User
This service manual is outside the scope for use by personnel who have received instrucĆ
tion on the correct operation of the UPS controls; limited to operation of the unit circuit
breakers and the Front Control Panel; operator/users are not permitted to remove any panĆ
els which are retained by screws.
Competent Personnel
The Troubleshooting section, and Service procedures contained in this manual are norĆ
mally outside the scope of personnel categorised competent; though they may be aware
of the dangers appropriate to working with hazardous voltages. A Competent engineer is
deemed to have sufficient technical skills/training to make electrical connections, install
batteries, close and open circuit breakers/fuses etc. (i.e. a qualified electrician) he is not
categorised as service personnel.
Service Personnel
This
etraining and are password authorised.
Service manual is designed for use by engineers who have received the relevant
Important Symbols
The warning triangle shown above indicate personal safety instructions.
Follow these instructions carefully to avoid injury.
Service Manual
Specification
Prelim Page vii UPS Preliminary Pages
Issue 2 - November 2001
Specification
10kVA 15kVA 20kVA 30kVA
Input Data
Nominal Input Voltage 400V 3 phase, neutral and earth
Input Voltage Range 300 ć 480Vac (330 ć 480Vac full charging capability)
Nominal Input Frequency 50/60Hz
Input Frequency Range 40 ć 70Hz
Maximum Input Current at Nominal Input Voltage 18.5A 25.3A 31.7A 45.0A
Input Current Harmonic Distortion (THD) <30% (without filter)
Input Power Factor 0.95 (over specified load and voltage ranges)
Output Data
Nominal Output Voltage 380, 400 or 415Vac selectable
Output Voltage Adjustment Range 360 ć 415Vac
Output Voltage Stability
Static Balanced Load
Static 50% Unbalanced Load
Static 100% Unbalanced Load
Dynamic 50% Load Step
Dynamic 100% Load Step
±1%
±3%
±5%
±3%
±5%
Output Voltage Transient Recovery Time <30ms (to 3% RMS)
Output Voltage Distortion (THD)
Linear Load
Non Linear Load (100% 3:1 Crest Factor Load)
<3%
<5%
Output Voltage Phase Displacement
Balanced Load
100% Unbalanced Load
120° ±1%
120° ±3%
Nominal Output Frequency 50 or 60Hz
Output Frequency Regulation
Synchronised With Input
Free Running
±1% or ±4%, selectable
±0.005%
Maximum Slew Rate 1Hz/sec
Nominal Output Power Rating
kVA
kW
10
8
15
12
20
16
30
24
Output Nominal Power Factor 0.8
Overload Capability on Inverter (Load Will Transfer to
Static Bypass if Times are Exceeded)
125% for 10 minutes, 150% for 10 seconds
Output Short Circuit Current 300% of nominal current for 100ms
Maximum Load Crest Factor 3:1 (at full load without deĆrating)
Service Manual
Specification
Prelim Page viiiUPS Preliminary Pages
Issue 2 - November 2001
10kVA 15kVA 20kVA 30kVA
Intermediate DC Circuit Data
Internal Battery Type valve regulated, sealed, lead acid cells
Number of Battery Cells 192
Nominal Battery Voltage 384Vdc
Internal Battery Rating 7.2Ahr 2 x 7.2Ahr 2 x 7.2Ahr 3 x 7.2Ahr
Full Load Autonomy Time With Standard Internal Battery
(For part load and battery configuration Autonomy times
refer to the table on page Ćxiii)
6 minutes 9 minutes 6 minutes 6 minutes
DC Bus Overvoltage Trip 500Vdc
End of Battery Discharge Voltage 320Vdc
Battery PreĆalarm Discharge Voltage Level 350Vdc
Battery Charger Nominal Float Voltage at 20°C 432Vdc
Battery Charger Voltage Stability ±1%
Battery Charger Output Voltage Ripple <1%
Maximum Battery Recharging Current 1, 3, 5 or 7A (Selectable)
Automatic Battery Test 12, 24 or 48 hour impedance test
System Data
Topology
True OnĆline double conversion, high frequency,
transformerless design
Power Upgrade Yes ć up to a maximum rating of 30kVA
StartĆup On Battery Yes
System Efficiency (Excluding Battery Charging)
50% Linear Load
100% Linear Load
88%
90%
88%
90%
89%
91%
90%
91%
Full Load Inverter Efficiency 94% 94% 94% 94%
Operating Temperature Range 0° Ć 40°C (20°C for optimal battery lifetime)
Storage Temperature Range Ć20° to 70°C (excluding battery)
Operating Relative Humidity Range <95% (nonĆcondensing)
Maximum Altitude Above Sea Level 1000m before deĆrating
Audible Noise Level At 1 Metre <52dBA
Relay Communications Card
Alarm Contacts
DB9 connector
On Battery
Low Battery
Internal Terminals
On Battery
Low Battery
On Bypass
UPS On
Remote Stop Contacts Open to disable inverter and static bypass
Cable Entry Bottom entry at rear of unit
Service Manual
Specification
Prelim Page ixUPS Preliminary Pages
Issue 2 - November 2001
10kVA 15kVA 20kVA 30kVA
Bypass Data
Input Voltage Range For Bypass Switching Nominal ±10%
Overload Capability on Static Bypass 150% for 30 minutes, 1000% for 100 m seconds
Mechanical Data
Unit Dimensions (w x h x d) 530 x 1220 x 950 mm
Unit Weight Without Battery 185kg
Unit Weight With Standard Battery 275kg 365kg 365kg 455kg
Shipping Dimensions (w x h x d) 545 x 1260 x 965 mm
Unit Shipping Weight Without Battery 215kg
Unit Shipping Weight With Standard Battery 305kg 395Kg 395kg 485kg
Enclosure Rating IP20
Colour
RAL 7035 Metal Covers
RAL 7042 Plastic Door
Design Standards
Safety
Radio Frequency Interference (RFI)
Electromagnetic Compatibility (EMC)
European Directive
Quality
EN50091Ć1Ć1
EN50091Ć2 Class A
CE marked compliance LVD / EMC
ISO9001
Service Manual
Specification
Prelim Page xUPS Preliminary Pages
Issue 2 - November 2001
BATTERY AUTONOMY TIMES
Confi
g
uration Part Nº
Approximate Autonomy Time in Minutes at
Stated Load and 25°C
Configuration
Part
N
100% 75% 50% 25% 10%
3 Phase 10kVA
UPS with 1 internal set of batteries
(Standard configuration)
6 9 17 35 115
UPS with 2 internal sets of batteries
+ 1 x BATT
17 24 40 82 282
UPS with 3 internal sets of batteries
+ 2 x BATT
28 41 66 133 486
UPS with 4 internal sets of batteries
+ 3 BATT
41 57 94 191 600
3 Phase 15kVA
UPS with 2 internal sets of batteries
(Standard configuration)
9 14 24 55 157
UPS with 3 internal sets of batteries
+ 1 x BATT
17 24 40 91 269
UPS with 4 internal sets of batteries
+ 2 x BATT
24 35 56 128 398
3 Phase 20kVA
UPS with 2 internal sets of batteries
(Standard configuration)
6 9 17 39 108
UPS with 3 internal sets of batteries
+ 1 x BATT
11 17 28 64 178
UPS with 4 internal sets of batteries
+ 2 xBATT
17 24 40 91 263
3 Phase 30kVA
UPS with 3 internal sets of batteries
(Standard configuration)
6 9 17 40 110
UPS with 4 internal sets of batteries
+ 1 x BATT
9 14 24 56 157
Service Manual
Table of Contents
Prelim Page i3x3 UPS Preliminary Pages
Issue 1 - May 2001
Table of Contents
Manual Registration i. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Amendment Record ii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Limitations of Use iv. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important Instructions for safe use v. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Personnel Categorisation vi. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specification vii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents xi. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 - Overview 1 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 - Introduction 1 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 - Equipment Construction 1 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 - Principle of operation 1 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 - UPS Power Configuration 1 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3 - Battery fuses switch 1 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 - Installation 2 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 - Installation (Mechanical) 2 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1 - Preliminary Checks 2 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 - Installation (Electrical) 2 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 - Power Cabling 2 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2 - Power Cable connections 2 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.3 - Safety Earth 2 - 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.4 - Protective devices 2 - 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 - Battery Installation 2 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1 - Battery Safety 2 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2 - Battery Installation Check 2 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.3 -Installing the Battery Upgrade Kit (BATTCABLE)2 - 9. . . . . . . . . . . . . .
2.4 -Setting Standard Relay Interface PCB2 - 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4.1 - Setting Options on the standard Relay Interface 2 - 12. . . . . . . . . . . . . . . . .
2.4.2 - Relay Interface Connections 2 - 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4.3 - Remote EPO (Emergency Power Off) 2 - 14. . . . . . . . . . . . . . . . . . . . . . . . . .
2.4.4 - Emergency Power Off (E.P.O.) pushĆbutton connection 2 - 14. . . . . . . . . . .
2.4.5 - Connection to Personal Computer 2 - 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4.6 - UPS Monitoring 2 - 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 - Commissioning 3 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 - PreĆpower Checks 3 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 - Validating the Installation 3 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 - Positioning 3 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 - Preliminary checks 3 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 - Setting UPS Parameters 3 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 - Control Logic PCB CS0072. 3 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2 - Driver Interface PCB CS0071 Settings 3 - 2. . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.3 - Auxiliary DC-DC PSU Converter PCB CS0070 Settings 3 - 3. . . . . . . . . .
3.3.4 - Battery Charger PCB CS0074 Setting 3 - 3. . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.5 - LCD Display Monitor Board CS0077 Settings 3 - 3. . . . . . . . . . . . . . . . . . .
Service Manual
Table of Contents
Prelim Page iiUPS Preliminary Pages
Issue 1 - May 2001
3.4 - Initial UPS Start-up. 3 - 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 - Converter and Inverter Output Calibration. 3 - 4. . . . . . . . . . . . . . . . . . . . . .
3.4.2 - Inverter to Bypass Synchronisation Check. 3 - 6. . . . . . . . . . . . . . . . . . . . .
3.4.3 - Battery Charger Output Calibration. 3 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 - Power Checks 3 - 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.1 - Bupass Failure Test 3 - 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.2 - Mains Failure Checks 3 - 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.3 - Test Transfer to the Reserve Line (Automatic Bypass). 3 - 8. . . . . . . . . . . .
3.5.4 - Manual Bypass Operation Check 3 - 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.5 - Local EPO 3 - 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.6 - External EPO 3 - 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 - Normal UPS Start-Up Instructions 3 - 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6.1 - LCD Messages and LED status after starting the UPS. 3 - 12. . . . . . . . . . .
3.7 - Normal Shutdown to Manual Bypass 3 - 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 - Setting Options 3 - 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8.1 - Setting options on the Relay card 3 - 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 - Operation and control4 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 - Operator Control Panel 4 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5 - Functional description 5 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 - Control Logic PCB CS0072 5 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1 - Potentiometer adjustment 5 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2 - Link and Jumper functions 5 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 - Auxiliary Supply PCB CS0070 5 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1 - Battery Threshold settings 5 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 - Driver Interface PCB CS007I 5 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 - Bypass Voltage Threshold Adjustment 5 - 3. . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2 - Link and Jumper functions 5 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 - Battery Charger CS0074 5 - 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1 - Battery Charger Voltage Adjustment 5 - 4. . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.2 - Link and Jumper Functions 5 - 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3 - Battery test 5 - 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.5 - UPS monitor board PCB CS0077 5 - 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6 - Relay Interface PCB CS0082 5 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.1 - EPO Connections. 5 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.6.2 - Optional Second Relay Interface PCB 5 - 6. . . . . . . . . . . . . . . . . . . . . . . . . .
5.7 - LCD MIMIC DISPLAY CS0075 5 - 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.7.1 - Control panel indicator LEDs 5 - 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6 - Maintenance 6 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 - Scheduled Maintenance 6 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.1 - Daily Checks 6 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2 - Weekly Checks 6 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.3 - Annual Maintenance 6 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 - Battery Maintenance 6 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.1 - Factors Effecting Battery Use 6 - 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.2 - Battery Testing 6 - 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Manual
Table of Contents
Prelim Page iii3x3 UPS Preliminary Pages
Issue 1 - May 2001
6.2.3 - Battery capacity testing. 6 - 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 - Battery Replacement 6 - 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 - UPS Storage 6 - 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 - Troubleshooting 7 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 - Introduction 7 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.1 - General Fault Identification Procedure 7 - 1. . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 - Special Tools. 7 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 - Removing the UPS Covers 7 - 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4 - Component Location 7 - 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.5 - Fault Identification 7 - 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.6 -Typical Voltage Values7
7.7 -Fuse Check List7 - 12
- 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.8 -Test Procedures7 - 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.8.1 - DC Bus Discharge Routine, Shutdown to Maintenance Bypass. 7 - 13. . .
7.8.2 -DC offset7 - 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.8.3 - IGBT Replacement 7 - 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.8.4 -IGBT testing7 - 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.8.5 - SCR Testing 7 - 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.8.6 - Inverter Drive Signal Testing 7 - 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.8.7 -Checking power circuit capacitors.7 - 27. . . . . . . . . . . . . . . . . . . .
7.9 -PCB Replacement Procedures7 - 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.9.1 - Auxiliary DC Ć DC Converter Part Nº OSDE0070 (PCB Label: CS0070 Exx) 7 - 28
7.9.2 - LCD UPS Monitor Board OSDE0077 (PCB Label: CS0077 Exx) 7 - 29. . . .
7.9.3 - Inverter Driver/Feedback Interface Part OSDE0071 7 - 30. . . . . . . . . . . .
7.9.4 - 3ph TL Control Logic Part Nº OSDE0072 * (PCB Label: CS0072 Exx) 7 - 32. . .
7.9.5 - Battery Charger Part Nº OSDE0074 (PCB Label: CS0074) 7 - 34. . . . . . . .
7.9.6 - Input Filter Part Nº OSDE0079 (PCB Label: CS0079 Exx) 7 - 36. . . . . . . . .
7.9.7 - Operator Control Panel (LDC) Part Nº OSDE0075 (PCB Label: CS0075 Exx)7 - 36
Chapter 8 - Optional Equipment 8 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1 - Second Relay card (Optional) 8 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 - Remote Alarm Panel 8 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2.1 - Remote Alarm Panel connection 8 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3 - Upgrade Kit 8 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.4 - Isolation Transformer 8 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.5 - Internal Extended Battery Kit 8 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.6 - Battery Connecting Kit 8 - 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 9 - Spare Parts 9 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 10 - Schematic Diagrams 10 - 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 - 13x3 UPS Overview
Issue 2 - November 2001
Chapter 1 - Overview
1.1 - Introduction
The aim of this chapter is to give a general overview of the, control principles and construction of the
series onĆline Uninterruptible Power Supply (UPS).
The UPS is a standĆalone, single module, system designed to furnish a well regulated 3 phase
power supply to a critical load, such as a computer, under all rated load and input supply conditions.
The unit is of a category known as an `onĆline' UPS and is therefore permanently connected between
the utility 3Ćphase supply and the load equipment and operational at all times
A battery provides the standĆby power source for the UPS when the input utility supply fails.
The system offers the user the following advantages:
Increased power quality. The UPS has its own internal voltage and frequency regulator circuits
which ensure that its output is maintained within close tolerances independent of voltage and frequency
variations on the utility power lines.
Increased noise rejection. By rectifying the input AC power to DC power, and then converting it
back to AC, any electrical noise present on the input utility supply line is effectively isolated from the UPS
output, therefore the critical load sees only clean power.
Powewr blackout protection. If the utility power fails, the UPS continues to power the critical load
from its backĆup battery source, leaving the load immune from power disturbances ć even complete
power blackouts.
1.2 - Equipment Construction
The equipment is constructed around a steel frame with removable panels. The door which can be seĆ
cured with a key is opened to give easy access to the input, bypass, output, reserve line circuit breakers
and battery C.B. fused switch, protecting them from accidental operation.
A string LED and control panel on the front of the cabinet permits the operator to monitor the UPS.
The cabinet houses both the power components and the batteries.
It is carried on four wheels. Jacking feet help to support the UPS, and also prevent it from moving once
it has been wheeled into its final position. These feet are also used to secure the equipment to its shipĆ
ping pallet during transit.
Cooling is by internal fan. Air is drawn in from beneath the UPS and exhausted through ventilation grills
of the front panel. These areas must be kept free of anything that may avoid the air flow into and out of
the unit.
Figure 1-1Front view of cabinet.
Service ManualChapter 1 - Overview
Equipment Construction
1 - 23x3 UPS Overview
Issue 2 - November 2001
1.2.1 - Principle of operation
Normal operation
During normal operation, i.e. when the UPS input supply is present and within specification, both the
converter and inverter sections are active and the automatic byĆpass is turned on to connect the inverter
output to the critical load terminals. The battery fuseĆholder switch is also closed and the battery is thereĆ
fore permanently float charged at the d.c. terminals voltage level.
Mains Failure
If the mains has a failure or is out of tolerance the converter will be supplied from the battery, while the
Inverter will continue to operate for a period of time which depends on the load and the capacity of the
battery. If the mains supply has not returned within this time, the Inverter will go off automatically and
an alarm condition will appear on the UPS operator control panel.
Critical load will not be interrupted in the event of a drop or return of the AC power mains.
Return of power mains
When the mains returns within the required tolerance, the converter will be automatically supplied from
mains, supplying power to the Inverter and recharging the battery at the same time. There will be no
interruption of the critical load.
UPS fault
In the event of an inverter failure, the automatic byĆpass will automatically transfer the load onto the
mains with no interruption. In such an event, request qualified technical assistance.
The load will be transferred with no interruption if the inverter is synchronised with the mains; if this is
not the case, there will be an interruption of some milliseconds.
The intervention of the automatic byĆpass line is shown on the front panel by the yellow led on.
WARNING CAUTION: When the load is being supplied from the bypass line through the automatic byĆ
pass, it is connected directly to the mains supply and is therefore no longer protected
against mains faults.
Maintenance Bypass
A second bypass circuit contained in the UPS cabinet, identified as the 'Maintenance Bypass' line is
included to enable the reserve supply to be made available to the load while facilitating a safe working
environment for carrying out scheduled UPS system maintenance or trouble shooting. The circuit is
manually selected by the Manual Bypass Switch (3) which can be padlocked in the OFF position.
WARNING CAUTION CAUTION: If an automatic circuit breaker device is not present in the input disĆ
tribution panel, there remains a dangerous voltage at the output terminals and also on the
input terminals of the UPS module that is switched off.
Note: The load is not protected from mains aberrations when operating on the
maintenance bypass mode.
Service Manual Chapter 1 - Overview
Equipment Construction
1 - 33x3 UPS Overview
Issue 2 - November 2001
Figure 1-2Split Bypass" configuration
UPS
Output
UPS
Input
Battery
UPS
Split
Bypass
Link
1.2.2 - UPS Power Configuration
Common Bypass
The UPS is factory set to operate in the Common Bypass" configuration. Split Bypass links shown
in Figure 1-2 connect the Input Mains supply to the Reserve Input (Bypass) line creating a common
input. A separate Reserve Input is therefore not required.
Split Bypass
To configure the with a Split Bypass input, the Split Bypass links shown in Figure 1-2 are removed
by the commissioning engineer. In the Split Bypass" configuration the static bypass line is connected
by a separate power switch to a dedicated `bypass' power source which also feeds the maintenance
bypass line. Where a separate power source is not available the Reserve and Converter input supply
connections would be linked together.
With the exception of the maintenance bypass switch (3), all the isolators shown must be closed during
normal UPS operation.
1.2.3 - Battery fuses switch
The battery is connected to the d.c. bus through a battery fuses switch (5) fitted inside the UPS cabinet
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117

Powertronix 20kVA User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI