WURM SLD342-C Product information

  • Hello! I have reviewed the datasheet for the Wurm SLD342-C switch card. This document provides information about a device designed for compressors, fans, and pumps, highlighting its features such as manual-0-automatic switches, LEDs for operation and fault indication, and its connection via Wurm CAN bus. I'm ready to answer your questions about this device.
  • For what devices this switch card is designed?
    How many switches are present on the card?
    How many LEDs are associated with each switch?
    How switch card connected to master module?
SLD342-C
Switch card for compressors, fans and pumps
SLD342-C_V3.0_PI_2019-11_EN Subject to technical changes Page 1 of 4
Front View
Features
4 switches Manual–0–Automatic
2 LEDs per switch: operation and fault
12 switch cards per master module HVB-G3/G4, HVV-G3/G4 and HVI-G3/G4
Simple labelling of switches by replaceable labelling strips
Connection to master module by Wurm CAN field bus (F-BUS)
SLD342-C
Switch card for compressors, fans and pumps
Page 2 of 4 Subject to technical changes SLD342-C_V3.0_PI_2019-11_EN
Writing conventions
Symbol
Meaning
CAUTION
Avoid the described hazard: Otherwise minor or medium bodily injury or
property damage will result.
WARNING
Avoid the described hazard: Otherwise there is danger from electric voltage
that can lead to death or serious bodily injury.
For your safety
For safe operation and to avoid personal injury and equipment damage through operational error,
always read these instructions, become familiar with the device, and implement all of the safety
instructions on the product and in these instructions as well as the safety guidelines of Wurm GmbH &
Co. KG Elektronische Systeme. Keep these instructions ready to hand for quick reference and pass
them on with the device when the product is sold.
Wurm GmbH & Co. KG Elektronische Systeme accepts no liability in case of improper use or use for
other than the intended purpose.
Target group
These instructions are intended for "service technician" personnel.
Intended purpose
The SLD342-C is a switch card for compressors, fans and pumps.
WARNING
Danger of death from electric shock and/or danger of fire!
Switch off the power to the entire system when installing, wiring or removing! Otherwise
a mains voltage and/or external voltage may still be present even if the control voltage
is switched off!
The wiring of the device should be carried out only by a qualified electrician!
Use only the correct tools for all work!
Check all wiring after connection!
Ensure the maximum loads on all connections!
Never expose the device to moisture, for example due to condensation or cleaning
agents!
Take the
device out of operation if it is faulty or damaged and is therefore compromising
safe operation!
Do not open the device.
Do not repair the device yourself! If required, send it in for repair with an exact
description of the fault!
CAUTION
Faults are caused by electromagnetic interference!
Use only shielded data lines and place them far away from power lines!
Wurm Infocenter
paperless info
Software revisions and validity of documentation
V3.0
2019-11
Documentation status
Any software versions not listed are special solutions for individual projects and are not documented in detail in this description.
This document automatically ceases to be valid if a new technical description is issued.
Manufacturer: Wurm GmbH & Co. KG Elektronische Systeme, Morsbachtalstraße 30, D-42857 Remscheid
For further information, see our website at www.wurm.de
SLD342-C
Switch card for compressors, fans and pumps
SLD342-C_V3.0_PI_2019-11_EN Subject to technical changes Page 3 of 4
Circuit diagram
Mounting
WARNING
Danger of death from electric shock!
Switch off the power to the entire system before installing! Otherwise, mains voltage
and/or external voltage can be present even when control voltage is shut off.
Installation in the mounting frame
Installation in the mounting frame MGR131/141
Push the device in the mounting frame to the stop until it locks
between the spring clips.
NOTICE
Please observe the product information for the
MGR131/141 mounting frame.
SLD342-C
Switch card for compressors, fans and pumps
Page 4 of 4 Subject to technical changes SLD342-C_V3.0_PI_2019-11_EN
Rotary code switch
0 Compressors 1-4
4 Fans 1-4
8 Pumps 1-4
C Spare
1 Compressors 5-8 5 Fans 5-8 9 Pumps 5-8 D Spare
2 Compressors 9-12 6 Fans 9-12 A Pumps 9-12 E Spare
3 Compressors 13-16 7 Fans 13-16 B Pumps 13-16 F Spare
The address range C-F is not assigned.
Technical data
Power supply
230V~, +10% / -15%, 50Hz, max. 4VA
Switch
4 switches Manual–0–Automatic
Fusing
Max. 6A
Output relay
Switch function via relays
4 x changeover contact, 230V~, 4(2)A
Displays
2 x LEDs per switch (operation, fault), flashing in the event of
fault
Communication F-BUS
3-wire CAN bus interface, shielded,
Push-in terminals 2.5mm² and RJ45 socket
Dimensions
(WxHxD) 54.5 x 109 x 92mm
Housing
Plastic, foil
Mounting
In the mounting frame MGR
Ambient temperature
Operation: 0...+55°C, storage: -25...+70°C
Weight
Approx. 360g
CE conformity
2014/30/EU (EMC Directive)
2014/35/EU (Low Voltage Directive)
RoHS II
Valid from
Version 3.0
Labelling strips templates
The individual switches of the switch card can be labelled with a paper strip that can be inserted into a
tab on the housing surface.
NOTICE
The templates of the labelling strips can also be found in the
Infocenter of Wurm.
/