WURM HCO2-G4 Product information

Type
Product information
Master module for process control of R744 refrigeration plants
HCO2-G4_V8.4.0_PI_2021-06_EN 1
Subject to technical changes
HCO2-G4
1 HCO2-G4
Master module for process control of R744 refrigeration plants
1.1 Front view
Fig. 1: Front view of HCO2-G4
1.2 Features
Plant-specific installation of control circuits
Start-up support with special start-up mode
High pressure control and medium pressure control with up to 2 valves
Analogue gas cooler control or via Modbus interface in 2 groups with functions for cleaning, addi-
tional cooling, emptying and sub-area shutdown
Refrigerant level monitoring in collector and MT/LT separators with level switches or filling level
probes, flooding of MT and LT cold locations
Oil return and oil pressure control
Compressor protection via load shedding
Post-injection and hot gas bypass with optional partial load reduction
Parallel compression with 1 constant and 2 multi-step compressors, load shedding
Ejector operation for Wurm ejectors: gas (3 x constant) and liquid (1 x constant) incl. control of
the valves mounted on the suction side
Air conditioning at medium pressure level with pump control incl. safety functions
Heat recovery
Up to 2 heat recovery units, 7-stepped sequences for desuperheating, power increase, GC fan
shut-down, GC bypass, GC heat pump, 2 external heat sources
Heating operation with optional reservoir control (electric heating element, pumps)
Heat pump control
1 GC heat pump and up to 2 external heat pumps in the refrigerant circuit at MT1, MT2 or LT
level including defrost, outside temperature-controlled rack shift and optional compressor decou-
pling in heat pump operation
CAN bus connection by patch cable and push-in terminals
Wurm G4 operating concept
Innovative user interface with 1-finger operation
Graphical display with backlighting, plain text, 6 operating keys, and 1 Info key
Context-sensitive Help with links to the paperless info Wurm-App
Direct navigation by Quicklink
Fastening in the installation frame, or individual installation without frame
Connection to the Wurm system via Wurm CAN communication bus (C-BUS) and
FRIGODATA XP
Master module for process control of R744 refrigeration plants
2HCO2-G4_V8.4.0_PI_2021-06_EN
Subject to technical changes
HCO2-G4
1.3 Safety instructions
Writing conventions
CAUTION
Avoid the described hazard: Otherwise minor or medium bodily injury or property damage will
result.
WARNING
Avoid the described hazard: Otherwise there is danger from electric voltage that can lead to
death or serious bodily injury.
For your safety
For safe operation and to avoid personal injury and equipment damage through operator error, always
read these instructions, become familiar with the device, and follow all safety instructions on the prod-
uct and in this document, as well as the safety guidelines of Wurm GmbH & Co. KG Elektronische
Systeme. Keep these instructions ready to hand for quick reference and pass them on with the device
if the product is sold. Wurm GmbH & Co. KG Elektronische Systeme accepts no liability in the case
of improper use or use for purposes other than the intended purpose.
WARNING
DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire plant when carrying out installation, wiring or removal work.
Otherwise a mains voltage and/or external voltage may still be present even if the control voltage
is switched off.
The wiring of the device must be carried out only by qualified electricians.
Use only the correct tools for all work.
Check all wiring after connection.
Take note of the maximum loads on all connections.
Never expose the device to moisture, for example due to condensation or cleaning agents.
Take the device out of operation if it is faulty or damaged and is therefore compromising safe
operation.
Do not open the device.
Do not repair the device yourself. If the device requires repairs, send it in with an exact descrip-
tion of the fault.
CAUTION
ELECTROMAGNETIC INTERFERENCE CAN CAUSE FAULTS!
Always use shielded data cables and place them far away from power lines.
Target group This manual is intended for “service technician” personnel.
Intended use The HCO2-G4 is a master module for process control of R744 refrigera-
tion plants.
Wurm Infocenter paperless info
Master module for process control of R744 refrigeration plants
HCO2-G4_V8.4.0_PI_2021-06_EN 3
Subject to technical changes
HCO2-G4
Version and validity of the documentation
Any versions not listed are special solutions for individual projects and are not described in detail in this document.
This document automatically ceases to be valid if a new technical description is issued.
Manufacturer: Wurm GmbH & Co. KG Elektronische Systeme, Morsbachtalstraße 30, D-42857 Remscheid
You can find more information on our website at www.wurm.de.
1.4 Device installation
WARNING
DANGER TO LIFE FROM ELECTRIC SHOCK AND/OR FIRE!
Switch off the power to the entire plant before installing. Otherwise, mains voltage and/or exter-
nal voltage may still be present, even if the control voltage is switched off.
Installing in the MGR131/141 and MGR231/241 installation frame
The entire plant must be free of voltage.
1. Push the device into the installation frame up to the stop.
The device snaps in between the spring clips.
Fig. 2: Installing in the MGR131/141 installation frame
NOTICE
Please refer to the product information for the MGR131/MGR141 and MGR231/241 installation
frames.
Installing the device with ZEM type screw-in clamps
The entire plant must be free of voltage.
1. Insert the device up to the stop in a mounting cutout in the switch cabinet door.
2. Fix the device to the switch cabinet door using the ZEM type screw clamps.
Fig. 3: Installing in a mounting cut-out with ZEM clamps
Version Date
V8.4.0 and
higher
2021-06 Documentation status
9
S
S
S
102
106
9
S
S
S
Master module for process control of R744 refrigeration plants
4HCO2-G4_V8.4.0_PI_2021-06_EN
Subject to technical changes
HCO2-G4
1.5 Circuit diagram
Fig. 4: HCO2-G4 circuit diagram
Wiring and connection of several master modules
Fig. 5: Wiring and connecting master modules
1.6 Technical data
11
12
13
14
15
16
17
27
26
25
24
23
22
21
29
28
0V
L
S
C-BUS
H
F-BUS
H
S
L
0V
F-BUS
C-BUS
99
98
OUTPUT INPUT
71
72
73
74
81
82
83
84
L
N
OFF
ON
OFF
ON
Modbus1
HR 1 Request - Step 2
Fault(NC) Min. REF MP
Fault(NC) Max. REF MP
Fault(NC) UPS
Valve HR 1
HR 1 Request - Step 1
Pump HR 1
LT Desuperheater
Hot gas bypass
Post-injection
MT Fastreturn
11 11 1112 1212
24V 24V 24V
Access
barrier
Access
barrier
Access
barrier
Power supply 230V~, +10% / -15%, 50Hz, max. 13VA
Display Graphical display with backlight
1 x red LED, flashes in case of fault
1 x green LED, for parameter adjustment
1 x yellow LED, for C-BUS operating status
1 x yellow LED, for F-BUS operating status
C-BUS communication 3-wire CAN bus interface, shielded, galvanically isolated, 2.5mm2 push-
in terminals / RJ45 socket and switchable terminating resistor for com-
munication with system devices
F-BUS communication 3-wire CAN bus interface, shielded, galvanically isolated, 2.5mm2 push-
in terminals / RJ45 socket and switchable terminating resistor for com-
munication with field modules
Communication Modbus 3-wire Modbus RTU, galvanically isolated, RJ45 socket
Digital inputs 6 x 24V=, self-powered, 5mA approx. per input, push-in terminals
2.5mm²
Digital outputs 8 x normally open contact with common supply, 1A,
rated voltage 230V~, push-in terminals
Dimensions (W x H x D) 109 x 109 x 92mm
Housing Plastic, foil
Fastening In MGR installation frame, individual installation with ZEM
Ambient temperature Operation: 0...+55°C, storage: -25...+70°C
Weight About 650g
CE conformity - 2014/30/EU (EMC Directive)
- 2014/35/EU (Low Voltage Directive)
EAC conformity - TR ZU 004/2011
- TR ZU 020/2011
RoHS II
Valid from Version 8.4.0
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

WURM HCO2-G4 Product information

Type
Product information