ENGINEERING MANUAL
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
Engineering Manual
TC-18001
Technical Catalog for Outdoor Unit
< Indoor Units >
●Ducted(HighStatic)Type
(H,Y)IDH018B21S
(H,Y)IDH024B21S
(H,Y)IDH030B21S
(H,Y)IDH036B21S
(H,Y)IDH048B21S
●Ducted(MediumStatic)Type
(H,Y,C)IDM006B21S
(H,Y,C)IDM008B21S
(H,Y,C)IDM012B21S
(H,Y,C)IDM015B21S
(H,Y,C)IDM018B21S
(H,Y,C)IDM024B21S
(H,Y,C)IDM030B21S
(H,Y,C)IDM036B21S
(H,Y,C)IDM048B21S
●Ducted(Slim)Type
(H,Y,C)IDS006B21S
(H,Y,C)IDS008B21S
(H,Y,C)IDS012B21S
(H,Y,C)IDS015B21S
(H,Y,C)IDS018B21S
TC-18001
i
IMPORTANT NOTICE AND SAFETY SUMMARY
1. Introduction
2. Important Safety Instructions
Thismanualshouldbeconsideredasapermanentpartoftheairconditioningequipmentandshould
remainwiththeairconditioningequipment.
(Transportation/InstallationWork)>(RefrigerantPipingWork)>(ElectricalWiringWork)>(Ref.ChargeWork)>(Test
Run)>(User)
ThisEngineeringManualconcentratesonairconditioningunitsforuseinheatpumpandheatrecovery
systems.Readthismanualcarefullybeforeperforminginstallationsoroperations.
Signal Words
Indicatesahazardoussituationthat,ifnotavoided,couldresultindeathor
seriousinjury.
Indicatesahazardoussituationthat,ifnotavoided,couldresultinminoror
moderateinjury.
Indicatesinformationconsideredimportant,butnothazard-related
(forexample,messagesrelatingtopropertydamage).
General Precautions
Toreducetheriskofseriousinjuryordeath,readtheseinstructions
thoroughlyandfollowallwarningsorcautionsincludedinallmanualsthat
accompaniedtheproductandareattachedtotheunit.Referbacktothese
instructionsasneeded.
ThissystemshouldbeinstalledbypersonnelcertiedbyJohnsonControls,Inc.Personnelmustbe
qualiedaccordingtolocal,stateandnationalbuildingandsafetycodesandregulations.Incorrect
installationcouldcauseleaks,electricshock,reorexplosion.InareaswhereSeismic‘’Performance
requirementsarespecied,theappropriatemeasuresshouldbetakenduringinstallationtoguard
againstpossibledamageorinjurythatmightoccurinanearthquakeiftheunitisnotinstalled
correctly,injuriesmayoccurduetoafallingunit.
UseappropriatePersonalProtectiveEquipment(PPE),suchasglovesandprotectivegogglesand,
whereappropriate,haveagasmasknearby.Alsouseelectricalprotectionequipmentandtoolssuited
forelectricaloperationpurposes.Keepawetclothandareextinguishernearbyduringbrazing.Use
careinhandling,rigging,andsettingofbulkyequipment.
Whentransporting,becarefulwhenpickingup,movingandmountingtheseunits.Althoughthe
unitmaybepackedusingplasticstraps,donotusethemfortransportingtheunitfromonelocation
toanother.Donotstandonorputanymaterialontheunit.Getapartnertohelp,andbendwith
yourkneeswhenliftingtoreducestrainonyourback.Sharpedgesorthinaluminumnsontheair
conditionercancutngers,sowearprotectivegloves.
Donottouchoradjustanysafetydevicesinsidetheindoororoutdoorunits.Allsafetyfeatures,
disengagement,andinterlocksmustbeinplaceandfunctioningcorrectlybeforetheequipmentis
putintooperation.Ifthesedevicesareimproperlyadjustedortamperedwithinanyway,aserious
accidentcanoccur.Neverbypassorjump-outanysafetydeviceorswitch.
JohnsonControlswillnotassumeanyliabilityforinjuriesordamagecausedbynotfollowingsteps
outlinedordescribedinthismanual.UnauthorizedmodicationstoJohnsonControlsproductsare
prohibitedasthey…
Maycreatehazardswhichcouldresultindeath,seriousinjuryorequipmentdamage.
Willvoidproductwarranties.
Mayinvalidateproductregulatorycertications.
MayviolateOSHAstandards.
ii
TC-18001
Takethefollowingprecautionstoreducetheriskofpropertydamage.
Preventmoisture,dust,ornoncondensablecompoundsfromenteringtherefrigerantcycleduring
installationwork.Foreignmattercoulddamageinternalcomponentsorcauseblockages.
Ifairltersarerequiredonthisunit,donotoperatetheunitwithouttheairltersetinplace.Iftheair
lterisnotinstalled,dustmayaccumulateandbreakdownmayresult.
Donotinstallthisunitinanyplacewheresilicongasescancollect.Ifthesilicongasmoleculesattach
themselvestothesurfaceoftheheatexchanger,thennedsurfaceswillrepelwater.Asaresult,any
amountofdrainagemoisturecondensatecanoverowfromthedraincondensatepanandcouldrun
insideoftheelectricalbox,possiblycausingelectricalfailures.
Wheninstallingtheunitinahospitalorotherfacilitywhereelectromagneticwavesaregenerated
fromnearbymedicaland/orelectronicdevices,beawareofnoiseandelectronicinterference
ElectromagneticInterference(EMI).DonotinstallwhereEMIwavescandirectlyradiateintothe
electricalbox,controllercable,orcontroller.Inverters,appliances,high-frequencymedicalequipment,
andradiocommunicationsequipmentmaycausetheunittomalfunction.Theoperationoftheunit
mayalsoadverselyaffectthesesamedevices.Installtheunitatleast10ft.(approximately3m)away
fromsuchdevices.
Whenawirelesscontrollerisused,locateatadistanceofatleast3.3ft.(approximately1m)between
theindoorunitandelectriclighting.Ifnot,thereceiverpartoftheunitmayhavedifcultyreceiving
operationcommands.
Donotinstalltheunitinanylocationwhereanimalsandplantscancomeintodirectcontactwiththe
outletairstream.Exposurecouldadverselyaffecttheanimalsandplants.
Donotinstalltheunitwithanydownwardslopetothesideofthedrainadapter.Ifyoudo,youmay
havecondensateowingbackwhichmaycauseleaks.
Besurethecondensatehosedischargeswaterproperly.Ifconnectedincorrectly,itmaycauseleaks.
Donotinstalltheunitinanyplacewhereoilcanseepontotheunits,suchastableorseatingareasin
restaurants,andsoforth.Fortheselocationsorsocialvenues,usespecializedunitswithoil-resistant
featuresbuiltintothem.Inaddition,useaspecializedventilationunitdesignedforrestaurantuse.
Thesespecializedoil-resistantunitscanbeorderedforsuchapplications.However,inplaceswhere
largequantitiesofoilcansplashontotheunit,suchasafactory,eventhespecializedunitscannotbe
used.Theseproductsshouldnotbeinstalledinsuchlocations.
Ifthewiredcontrollerisinstalledinalocationwhereelectromagneticradiationisgenerated,make
surethatthewiredcontrollerisshieldedandcablesaresleevedinsideconduittubing.
Ifthereisasourceofelectricalinterferencenearthepowersupply,installnoisesuppression
equipment(lter).
Duringthetestrun,checktheunit’soperationtemperature.Iftheunitisusedinanenvironment
wherethetemperatureexceedstheoperationboundary,itmaycauseseveredamage.Checkthe
operationaltemperatureboundaryinthemanual.Ifthereisnospeciedtemperature,usetheunit
withintheoperationaltemperatureboundaryof32to104°F(0to40°C).
ReadinstallationandappropriateusermanualsforconnectionwithPCorperipheraldevices.Ifa
warningwindowappearsonthePC,theproductstops,doesnotworkproperlyorworksintermittently,
immediatelystopusingtheequipment.
TC-18001
iii
Installation Precautions
Toreducetheriskofseriousinjuryordeath,thefollowinginstallation
precautionsmustbefollowed.
Wheninstallingtheunitinto…
Awall:Makesurethewallisstrongenoughtoholdtheunit’sweight.Itmaybenecessaryto
constructastrongwoodormetalframetoprovideaddedsupport.
Aroom:Properlyinsulateanyrefrigeranttubingruninsidearoomtoprevent“sweating”thatcan
causedrippingandwaterdamagetowallandoors.
Damporunevenareas:Usearaisedconcretepadorconcreteblockstoprovideasolid,level
foundationfortheunittopreventwaterdamageandabnormalvibration.
Anareawithhighwinds:Securelyanchortheoutdoorunitdownwithboltsandametalframe.
Provideasuitablewindbafe.
Asnowyarea:Installtheoutdoorunitonaraisedplatformthatishigherthandriftingsnow.
Providesnowprotectionhood.
Iftheremotesensorsarenotusedwiththiscontroller,thendonotinstallthiscontroller…
inaroomwherethereisnothermostat.
wheretheunitisexposedtodirectsunshineordirectlight.
wheretheunitwillbeincloseproximitytoaheatsource.
wherehot/coldairfromtheoutdoors,oradraftfromelsewhere(suchasairvents,diffusersor
grilles)canaffectaircirculation.
inareaswithpooraircirculationandventilation.
Donotinstalltheunitinthefollowingplaces.Doingsocanresultinanexplosion,re,damage,
corrosion,orproductfailure.
Explosiveorammableatmosphere.
Wherere,oil,steam,orpowdercandirectlyentertheunit,suchasincloseproximityordirectly
aboveakitchenstove.
Whereoil(includingmachineryoil)maybepresent.
Wherecorrosivegasessuchaschlorine,bromine,orsuldecanaccumulate,suchasnearahot
tuborhotspring.
Wheredense,salt-ladenmistisheavy,suchasincoastalregions.
Wheretheairqualityisofhighacidity.
Whereharmfulgasescanbegeneratedfromdecomposition.
Donotpositionthecondensatepipefortheindoorunitnearanysanitarysewerswherecorrosive
gasesmaybepresent.Ifyoudo,toxicgasescanseepintobreathableairspacesandcancause
respiratoryissues.Ifthecondensatepipeisinstalledincorrectly,waterleakageanddamagetothe
ceiling,oor,furniture,orotherpossessionsmayresult.Ifcondensatepipingbecomesclogged,
moisturecanbackupandcandripfromtheindoorunit.Donotinstalltheindoorunitwheresuch
drippingcancausemoisturedamageorunevenlocations:Usearaisedconcretepadorconcrete
blockstoprovideasolid,levelfoundationfortheunittopreventwaterdamageandabnormal
vibration.
Beforeperforminganybrazingwork,besurethattherearenoammablematerialsoropenames
nearby.
Performatestruntoensurenormaloperation.Safetyguards,shields,barriers,covers,andprotective
devicesmustbeinplacewhilethecompressor/unitisoperating.Duringthetestrun,keepngersand
clothingawayfromanymovingparts.
Cleanupthesitewhennished,rememberingtocheckthatnometalscrapsorbitsofwiringhave
beenleftinsidetheunitbeinginstalled.
Duringtransportation,donotallowthebackrestoftheforkliftmakecontactwiththeunit,otherwise,
itmaycausedamagetotheheatexchangerandalsomaycauseinjurywhenstoppedorstarted
suddenly.
Removegasinsidetheclosingpipewhenthebrazingworkisperformed.Ifthebrazingllermetalis
meltedwithremaininggasinside,thepipeswillbeblownoffanditmaycauseinjury.
Besuretousenitrogengasforanairtighttest.Ifothergasessuchasoxygengas,acetylenegasor
uorocarbongasareaccidentallyused,itmaycauseexplosionorgasintoxication.
Afterinstallationworkforthesystemhasbeencompleted,explainthe“SafetyPrecautions,”theproperuse
andmaintenanceoftheunittothecustomeraccordingtotheinformationinallmanualsthatcamewiththe
system.AllmanualsandwarrantyinformationmustbegiventotheuserorleftneartheIndoorUnit.
iv
TC-18001
Refrigerant Precautions
Toreducetheriskofseriousinjuryordeath,thefollowingrefrigerant
precautionsmustbefollowed.
Asoriginallymanufactured,thisunitcontainsrefrigerantinstalledbyJohnsonControls.Johnson
Controlsusesonlyrefrigerantsthathavebeenapprovedforuseintheunit’sintendedhomecountry
ormarket.JohnsonControlsdistributorssimilarlyareonlyauthorizedtoproviderefrigerantsthat
havebeenapprovedforuseinthecountriesormarketstheyserve.Therefrigerantusedinthisunit
isidentiedontheunit’sfaceplateand/orintheassociatedmanuals.Anyadditionsofrefrigerantinto
thisunitmustcomplywiththecountry’srequirementswithregardtorefrigerantuseandshouldbe
obtainedfromJohnsonControlsdistributors.Useofanynon-approvedrefrigerantsubstituteswillvoid
thewarrantyandwillincreasethepotentialriskofinjuryordeath.
Ifinstalledinasmallroom,takemeasurestopreventtherefrigerantfromexceedingthemaximum
allowableconcentrationintheeventthatrefrigerantgasesshouldescape.Theinstallationshould
meettherequirementsinASHRAEStandards15and34.Ifrefrigerantgashasleakedduringthe
installationwork,ventilatetheroomimmediately.
Checkthedesignpressureforthisproductis601psi(4.15MPa).Thepressureoftherefrigerant
R410Ais1.4timeshigherthanthatoftherefrigerantR22.Therefore,therefrigerantpipingfor
R410AshallbethickerthanthatforR22.Makesuretousethespeciedrefrigerantpiping.Ifnot,the
refrigerantpipingmayraptureduetoanexcessiverefrigerantpressure.Besides,payattentionto
thepipingthicknesswhenusingcopperrefrigerantpiping.Thethicknessofcopperrefrigerantpiping
differsdependingonitsmaterial.
WhenR410Aisused,therefrigerantoiltendstobeaffectedbyforeignmatterssuchasmoisture,
oxidelm,(orfat).Performtheinstallationworkwithcaretopreventmoisture,dust,ordifferent
refrigerantfromenteringtherefrigerantcycle.Foreignmattercanbeintroducedintothecycletosuch
partsastheexpansionvalvecausingoperationalissues.
Toavoidthepossibilityofdifferentrefrigerantorrefrigerantoilbeingintroducedintothecycle,the
sizesofthechargingconnectionshavebeenchangedfromR407CtypeandR22type.Itisnecessary
toverifytheappropriatetoolsareonhandbeforeperforminginstallationwork.
UserefrigerantpipesandjointswhichareapprovedforusewithR410A.
Acompressor/unitcomprisesapressurizedsystem.Neverloosenthreadedjointswhilethesystemis
underpressureandneveropenpressurizedsystemparts.
Beforeinstallationiscomplete,makesurethattherefrigerantleaktesthasbeenperformed.If
refrigerantgasesescapeintotheair,turnOFFthemainswitch,extinguishanyopenamesand
contactyourservicecontractor.Refrigerant(Fluorocarbon)forthisunitisodorless.Iftherefrigerant
shouldleakandcomeintocontactwithopenames,toxicgascouldbegenerated.Also,becausethe
uorocarbonsareheavierthanair,theysettletotheoor,whichcouldcauseasphyxiation.
Wheninstallingtheunit,andconnectingrefrigerantpiping,keepallpipingrunsasshortas
possible,andmakesuretosecurelyconnecttherefrigerantpipingbeforethecompressorstarts
operating.Iftherefrigerantpipingisnotconnectedproperlyandthecompressorstartswith
thestopvalveopened,airmaybepulledintothesystemandtherefrigerantcyclewillbecome
subjectedtoextremelyhighpressure,whichcancauseanexplosionorre.
Tightenthearenutwithatorquewrenchinthespeciedmanner.Donotapplyexcessiveforcetothe
arenutwhentightening.Ifyoudo,thearenutcancrackandrefrigerantleakagemayoccur.
Whenmaintaining,relocating,anddisposingoftheunit,dismantletherefrigerantpipingafterthe
compressorstops.
Whenpipesareremovedoutfromunderthepipingcover,aftertheinsulationworkiscompleted,
coverthegapbetweenthepipingcoverandpipeswithadditionalinsulatingmaterial(eld-supplied).
Ifthegapisnotcovered,theunitmaybedamagedifsnow,rainwaterorsmallanimalsentertheunit.
Donotapplyexcessiveforcetothestopvalvewhenopening.Ifdamaged,thestopvalvecouldcome
apartduetorefrigerantpressure.Atthetestrun,fullyopenthegasandliquidvalves,otherwise,
thesedeviceswillbedamaged.(Itisclosedbeforeshipment.)
Ifthesetupforoutdoorunitsisincorrect,itmaycauseowbackoftherefrigerantandresultinfailure
oftheoutdoorunit.
Therefrigerantsystemmaybedamagediftheslopeofthepipingconnectionkitexceeds+15
o
.
TC-18001
v
Electrical Precautions
Takethefollowingprecautionstoreducetheriskofelectricshock,reor
explosionresultinginseriousinjuryordeath.
Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagram
andtheseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancause
seriousinjuryordeath.
Performallelectricalworkinstrictaccordancewiththisinstallationandmaintenancemanualandall
therelevantregulatorystandards.
Beforeservicing,shutoffandtagalldisconnectswitches.Neverassumeelectricalpoweris
disconnected.Alwaysverifywithameter.
Onlyuseelectricalprotectionequipmentandtoolssuitedforthisinstallation.
Insulateawiredcontrolleragainstmoistureandtemperatureextremes.
Usespeciedcablesbetweenunits.
Theinstalledairconditionermaynotfunctionnormallyinthefollowinginstances:
Ifelectricalpowerforthenewairconditionerissuppliedfromthesametransformerasthe
externalequipment*referredtobelow.
Ifthepowersupplywiringforthisexternalequipment*andthenewairconditionerunitarelocated
incloseproximitytoeachother.
externalequipment*:(Example):Alift,containercrane,rectierforelectricrailway,inverter
powerdevice,arcfurnace,electricfurnace,large-sizedinductionmotorandlarge-sized
switch.
Regardingthecasesmentionedabove,surgevoltagemaybeinductedintothepowersupply
cablesforthepackagedairconditionerduetoarapidchangeinpowerconsumptionofthedevice
andanactivationofaswitch.
Checkeldregulationsandstandardsbeforeperformingelectricalworkinordertoprotectthe
powersupplyforthenewairconditionerunit.
CommunicationcablemustbeaminimumofAWG18(0.82mm
2
),2-Conductor,StrandedCopper.
ShieldedcablemustbeusedforapplicationsandroutinginareasofhighEMIandothersourcesof
potentiallyexcessiveelectricalnoisetoreducethepotentialforcommunicationerrors.Whenshielded
cablingisapplied,properbondingandterminationofthecableshieldisrequiredasperJohnson
Controlsguidelines.Plenumandriserratingsforcommunicationcablesmustbeconsideredper
applicationandlocalcoderequirements.
Thepolarityoftheinputterminalsisimportant,sobesuretomatchthepolaritywhenusingcontacts
thathavepolarity.
Useadedicatedcircuitfortheairconditionerattheunit’sratedvoltage.
Highlydangerouselectricalvoltagesareusedinthissystem.Carefullyrefertothewiringdiagramand
theseinstructionswhenwiring.Improperconnectionsandinadequategroundingcancauseserious
injuryordeath.
Beforeinstallingthecontrollerorremotedevices,ensurethattheindoorandoutdoorunitoperation
hasbeenstopped.Further,besuretowaitatleastveminutesbeforeturningoffthemainpower
switchtotheindoororoutdoorunits.Otherwise,waterleakageorelectricalbreakdownmayresult.
DonotopentheservicecoveroraccesspaneltotheindoororoutdoorunitswithoutturningOFFthe
mainpowersupply.Beforeconnectingorservicingthecontrollerorcablestoindoororoutdoorunits,
shutoffandtagalldisconnectswitches.Neverassumeelectricalpowerisdisconnected.Alwaysverify
withameter.
ThisequipmentcanbeinstalledwithaGroundFaultCircuitBreaker(GFCI),whichisarecognized
measureforaddedprotectiontoaproperlygroundedunit.Installappropriatesizedbreakers/fuses
/overcurrentprotectionswitches,andwiringinaccordancewithlocal,stateandNECcodesand
requirements.Theequipmentinstallerisresponsibleforunderstandingandabidingbyapplicable
codesandrequirements.
vi
TC-18001
- CONTENTS -
1. GeneralInformation(Features).................................................................................................................. 1-1
2. DuctedType............................................................................................................................................... 2-1
2.1 UnitNomenclature............................................................................................................................. 2-1
2.2 Line-up.............................................................................................................................................. 2-1
2.3 DuctedHighStatic............................................................................................................................. 2-2
2.3.1 GeneralData........................................................................................................................... 2-2
2.3.2 DimensionalData.................................................................................................................... 2-3
2.3.3 Structure.................................................................................................................................. 2-4
2.3.4 ComponentData...................................................................................................................... 2-5
2.3.5 OperationSpace...................................................................................................................... 2-6
2.3.6 SensibleHeatFactor(SHF)..................................................................................................... 2-6
2.3.7 FanPerformance..................................................................................................................... 2-7
2.3.8 ElectricalData.......................................................................................................................... 2-9
2.3.9 SoundData.............................................................................................................................. 2-10
2.3.10 ControlSystem........................................................................................................................ 2-12
2.3.10.1 RefrigerantSystem......................................................................................................... 2-12
2.3.10.2 StandardOperationSequence........................................................................................ 2-13
2.3.10.3 SafetyandControlDeviceSetting.................................................................................. 2-16
2.3.10.4 WiringDiagram............................................................................................................... 2-17
2.4 DuctedMediumStatic....................................................................................................................... 2-18
2.4.1 GeneralData........................................................................................................................... 2-18
2.4.2 DimensionalData.................................................................................................................... 2-19
2.4.3 Structure.................................................................................................................................. 2-22
2.4.4 ComponentData...................................................................................................................... 2-23
2.4.5 OperationSpace...................................................................................................................... 2-24
2.4.6 SensibleHeatFactor(SHF)..................................................................................................... 2-24
2.4.7 FanPerformance..................................................................................................................... 2-25
2.4.8 ElectricalData.......................................................................................................................... 2-28
2.4.9 SoundData.............................................................................................................................. 2-29
2.4.10 ControlSystem........................................................................................................................ 2-32
2.4.10.1 RefrigerantSystem......................................................................................................... 2-32
2.4.10.2 StandardOperationSequence........................................................................................ 2-33
2.4.10.3 SafetyandControlDeviceSetting.................................................................................. 2-36
2.4.10.4 WiringDiagram............................................................................................................... 2-37
IMPORTANTNOTICEANDSAFETYSUMMARY......................................................................................... i
1. Introduction................................................................................................................................................ i
2. ImportantSafetyInstructions..................................................................................................................... i
TC-18001
vii
- CONTENTS -
2.5 DuctedSlim....................................................................................................................................... 2-38
2.5.1 GeneralData........................................................................................................................... 2-38
2.5.2 DimensionalData.................................................................................................................... 2-39
2.5.3 Structure.................................................................................................................................. 2-40
2.5.4 ComponentData...................................................................................................................... 2-41
2.5.5 OperationSpace...................................................................................................................... 2-42
2.5.6 SensibleHeatFactor(SHF)..................................................................................................... 2-42
2.5.7 FanPerformance..................................................................................................................... 2-43
2.5.8 ElectricalData.......................................................................................................................... 2-45
2.5.9 SoundData.............................................................................................................................. 2-46
2.5.10 ControlSystem........................................................................................................................ 2-48
2.5.10.1 RefrigerantSystem......................................................................................................... 2-48
2.5.10.2 StandardOperationSequence........................................................................................ 2-49
2.5.10.3 SafetyandControlDeviceSetting.................................................................................. 2-52
2.5.10.4 WiringDiagram............................................................................................................... 2-53
3. OptionalParts............................................................................................................................................ 3-1
3.1 LineUp.............................................................................................................................................. 3-1
3.2 AirFilter............................................................................................................................................. 3-2
3.3 Infrared(IR)ReceiverKit:CWDIRK01.............................................................................................. 3-4
3.3.1 Specications........................................................................................................................... 3-4
3.3.2 Dimensions.............................................................................................................................. 3-4
3.3.3 ApplicableModels.................................................................................................................... 3-4
3.3.4 Accessories/Options.............................................................................................................. 3-5
3.3.5 Installation................................................................................................................................ 3-5
3.3.6 ElectricalWiring....................................................................................................................... 3-8
3.3.7 SettingDIPSwitchesonIndoorUnitSide............................................................................... 3-8
3.3.8 SettingDIPSwitchonIRReceiverKitSide............................................................................. 3-9
3.3.9 IdentifyingIndoorUnitsInstalledinaSide-by-SideOperation................................................ 3-10
3.3.10 SimultaneousOperation.......................................................................................................... 3-11
3.3.11 TestRunbyWirelessController(CIR01)................................................................................. 3-13
3.3.12 AlarmIndication....................................................................................................................... 3-13
3.4 3PConnectorCable:PCC-1A........................................................................................................... 3-14
3.5 RemoteSensor:THM-R2A................................................................................................................ 3-14
3.6 Relayand3PinConnectorKit:PSC-5RA......................................................................................... 3-15
4. SelectionData............................................................................................................................................ 4-1
4.1 SelectionGuide................................................................................................................................. 4-1
4.2 CapacityTable................................................................................................................................... 4-1
4.2.1 CoolingCapacity...................................................................................................................... 4-1
4.2.2 HeatingCapacity..................................................................................................................... 4-4
FEATURES
TC-18001
1-1
VRF Air Conditioners
Johnson Controls proudly introduces new Variable Refrigerant Flow (VRF) air conditioners, a highly-efcient
and reliable air-conditioning system. Recently, increased numbers of buildings are requiring "intelligent"
facilities that include communication networks, ofce automation, and a comfortable environment. In
particular, a comfortable environment is becoming more of a year-around requirement in ofce buildings.
The VRF multi-split system air conditioner meets these requirements. The proven combination of the scroll
compressor and inverter provides the best air conditioning for small and medium ofce buildings.
VRF System
Johnson Controls has developed the VRF system with its customers in mind.
This system, allows the interconnection of indoor units for all our VRF air conditioners.
This system provides the consumer with greater exibility for installation, which means that the air-
conditioning systems will integrate better within complex facility structures.
1. General Information (Features)
Wide Range Line-up
Indoor Unit Type
Capacity (MBH)
6 8 12 15 18 24 30 36 48
Ducted High Static (H,Y)IDH_B21S
Ducted Medium Static (H,Y,C)IDM_B21S
Ducted Slim (H,Y,C)IDS_B21S
: Available
Table 1.1 Indoor Unit Type List
Ducted Type Models
High Static Type:
(H,Y)IDH018B21S, (H,Y)IDH024B21S, (H,Y)IDH030B21S, (H,Y)IDH036B21S, (H,Y)IDH048B21S
Medium Static Type:
(H,Y,C)IDM006B21S, (H,Y,C)IDM008B21S, (H,Y,C)IDM012B21S, (H,Y,C)IDM015B21S,
(H,Y,C)IDM018B21S, (H,Y,C)IDM024B21S, (H,Y,C)IDM030B21S, (H,Y,C)IDM036B21S,
(H,Y,C)IDM048B21S
Slim Type:
(H,Y,C)IDS006B21S, (H,Y,C)IDS008B21S, (H,Y,C)IDS012B21S, (H,Y,C)IDS015B21S,
(H,Y,C)IDS018B21S
FEATURES
1-2
TC-18001
Space Saving Design
A small height design is adapted.
These units can be installed in a false ceiling space in almost any building.
Unit: inch (mm)
Capacity
(MBH)
Model h
18 (H,Y)IDH018B21S 10-5/8 (270)
24 (H,Y)IDH024B21S 13-3/4 (350)
30 (H,Y)IDH030B21S 13-3/4 (350)
36 (H,Y)IDH036B21S 13-3/4 (350)
48 (H,Y)IDH048B21S 13-3/4 (350)
2-7/
8
(74)
h
High Static Type
Unit: inch (mm)
Capacity
(MBH)
Model h
6 (H,Y,C)IDM006B21S 10-5/8 (270)
8 (H,Y,C)IDM008B21S 10-5/8 (270)
12 (H,Y,C)IDM012B21S 10-5/8 (270)
15 (H,Y,C)IDM015B21S 10-5/8 (270)
18 (H,Y,C)IDM018B21S 10-5/8 (270)
24 (H,Y,C)IDM024B21S 11-13/16 (300)
30 (H,Y,C)IDM030B21S 11-13/16 (300)
36 (H,Y,C)IDM036B21S 11-13/16 (300)
48 (H,Y,C)IDM048B21S 11-13/16 (300)
2-7/
8
(74)
h
Medium Static Type
Unit: inch (mm)
Capacity
(MBH)
Model h
6 (H,Y,C)IDS006B21S 7-9/16 (192)
8 (H,Y,C)IDS008B21S 7-9/16 (192)
12 (H,Y,C)IDS012B21S 7-9/16 (192)
15 (H,Y,C)IDS015B21S 7-9/16 (192)
18 (H,Y,C)IDS018B21S 7-9/16 (192)
5-1/8
(130)
h
Slim Type
FEATURES
TC-18001
1-3
Alternative External Static Pressure Setting (only for Medium Static Type and Slim Type)
The external static pressure setting on the Medium Static type can be set using any of three steps from
the wired controller as shown below.
Medium Static Type
Slim Type
Static Pressure Wired Controller Setting
0.32 in.W.G. (80 Pa) C501
0.20 in.W.G. (50 Pa) C500
0.14 in.W.G. (35 Pa) C502
* Static pressure setting on the wired controller ("C5").
Refer to the “Installation and Maintenance Manual” for the wired controller for details.
* Static pressure setting on the wired controller ("C5").
Refer to the “Installation and Maintenance Manual” for the wired controller for details.
Model Static Pressure Wired Controller Setting
(H,Y,C)IDS006 - 012B21S
0.12 in.W.G. (30 Pa) C501
0.04 in.W.G. (10 Pa) C500
0 in.W.G. (0 Pa) C502
(H,Y,C)IDS015, 018B21S
0.12 in.W.G. (50 Pa) C501
0.04 in.W.G. (10 Pa) C500
0 in.W.G. (0 Pa) C502
DUCTED
TC-18001
2-1
2. Ducted Type
2.1 Unit Nomenclature
Model Descriptions
Example
H I DH 018 B 2 1 S
Nomenclature Description
H = Hitachi Brand
Y = York Brand
C = Coleman Brand
H
Indoor Unit I
Indoor Unit Type
DH = High Static
DM = Medium Static
DS = Slim
DH
Capacity (MBH) 018
Refrigerant Type
B = R410A
B
Voltage
2 = 208/230Volts - 1Phase - 60Hz
2
1 = 1st Generation 1
S = Standard Type S
2.2 Line-up
Type
Capacity
Model
RT MBH
Indoor Unit
Ducted High Static
1.5 18 (H,Y)IDH018B21S
2.0 24 (H,Y)IDH024B21S
2.5 30 (H,Y)IDH030B21S
3.0 36 (H,Y)IDH036B21S
4.0 48 (H,Y)IDH048B21S
Ducted Medium Static
0.5 6 (H,Y,C)IDM006B21S
0.7 8 (H,Y,C)IDM008B21S
1.0 12 (H,Y,C)IDM012B21S
1.3 15 (H,Y,C)IDM015B21S
1.5 18 (H,Y,C)IDM018B21S
2.0 24 (H,Y,C)IDM024B21S
2.5 30 (H,Y,C)IDM030B21S
3.0 36 (H,Y,C)IDM036B21S
4.0 48 (H,Y,C)IDM048B21S
Ducted Slim
0.5 6 (H,Y,C)IDS006B21S
0.7 8 (H,Y,C)IDS008B21S
1.0 12 (H,Y,C)IDS012B21S
1.3 15 (H,Y,C)IDS015B21S
1.5 18 (H,Y,C)IDS018B21S
DUCTED
2-2
TC-18001
2.3 Ducted High Static
2.3.1 General Data
NOTES:
*1. Nominal capacity is based on combinations within the VRF system under the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80°F DB (26.7°C DB)
67°F WB (19.4°C WB)
Outdoor Air Inlet Temperature: 95°F DB (35.0°C DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 70°F DB (21.1°C DB)
Outdoor Air Inlet Temperature: 47°F DB (8.3°C DB)
43°F WB (6.1°C WB)
Piping Length: 24 ft. 7-3/16 in. (7.5m) Piping Lift: 0ft. (0m)
*2. The sound pressure level is based on the following conditions.
4.9 ft. (1.5m) beneath the units.
The above data was measured in an anechoic chamber so that reected sound should be taken into consideration in the eld.
*3. For the (H,Y)IDH series, the fan speeds are only “High” and “Low”. Therefore, the fan speed indication of the LCD is changed as
High → Low , by pressing the fan speed key “
” or “ ”.
If one wired controller is connected to multiple indoor units (included with 3 or 4 taps speed of the indoor unit), the fan speed
indication of LCD is changed as (High 2 →) High → Medium → Low . However, the actual fan speed is as shown in the table
below.
LCD
Indication
Actual Fan
Speed
High 2 High
High High
Medium High
Low Low
Indoor Unit Type Ducted High Static
Model (H,Y)IDH018B21S (H,Y)IDH024B21S (H,Y)IDH030B21S (H,Y)IDH036B21S (H,Y)IDH048B21S
Indoor Unit Power Supply AC 1Phase, 208/230V, 60Hz
Nominal Cooling Capacity *1 Btu/h 36,000 48,000
(kW) (10.5) (14.1)
Nominal Heating Capacity *1 Btu/h 40,000 54,000
(kW) (11.7) (15.8)
dB 43-34/46-37 44-35/47-40
Outer Dimensions
Height in.(mm) 10-5/8 (270) 13-3/4 (350) 13-3/4 (350) 13-3/4 (350) 13-3/4 (350)
Width in.(mm) 35-7/16 (900) 35-7/16 (900) 35-7/16 (900) 51-3/16 (1300) 51-3/16 (1300)
Depth in.(mm) 28-3/8 (720) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800) 31-1/2 (800)
Net Weight lbs(kg) 75 (34) 106 (48) 106 (48) 128 (58) 132 (60)
Refrigerant
Indoor Fan
Airflow Rate *3 cfm 1190-830 1236-890
(Hi-Lo)
(m
3
/min)
(33.7-23.5) (35-25.2)
External Pressure (208/230V)
High Pressure
in.W.G(Pa)
0.6/0.74 (150/185) 0.6/0.74 (150/185) 0.6/0.74 (150/185) 0.6/0.74 (150/185) 0.6/0.74 (150/185)
Standard
in.W.G(Pa)
0.20/0.40 (50/100) 0.20/0.40 (50/100) 0.20/0.40 (50/100) 0.20/0.40 (50/100) 0.20/0.40 (50/100)
Motor Nominal Output W 250 280
Connections
Refrigerant Piping
Liquid Line in.(mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Gas Line in.(mm) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)
Condensate Drain VP25 VP25
OD in.(mm) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32) 1-1/4 (32)
ID in.(mm) 1 (25) 1 (25) 1 (25) 1 (25) 1 (25)
Sound Pressure Level *2
(Overall A Scale)
[Fan Speed (Hi-Lo) 208V/
Fan Speed (Hi-Lo) 230V]
18,000 24,000 30,000
(5.3) (7.0) (8.8)
20,000 27,000 34,000
(5.9) (7.9) (10.0)
38-29/44-37 39-30/42-34 39-30/42-34
547-388 883-618 883-618
VP25 VP25 VP25
R410A
Flare-Nut Connection (with Flare Nuts)
130 150 150
(15.5-11) (25-17.5) (25-17.5)
DUCTED
TC-18001
2-3
2.3.2 Dimensional Data
Model: (H,Y)IDH018B21S
Models: (H,Y)IDH024B21S, (H,Y)IDH030B21S, (H,Y)IDH036B21S and (H,Y)IDH048B21S
Unit: inch (mm)
DUCTED
2-4
TC-18001
2.3.3 Structure
Unit: inch (mm)
Model: (H,Y)IDH018B21S
Models: (H,Y)IDH024B21S, (H,Y)IDH030B21S, (H,Y)IDH036B21S and (H,Y)IDH048B21S
DUCTED
TC-18001
2-5
2.3.4 Component Data
Indoor Heat Exchanger and Fan
Tube Material
Outer Diameter
in (mm)
1/4 (7.0) 1/4 (7.0) 1/4 (7.0) 1/4 (7.0) 1/4 (7.0)
Rows
Number of Tube/Coil
Fin Material
Pitch in (mm) 0.071 (1.8) 0.071 (1.8) 0.071 (1.8) 0.071 (1.8) 0.063 (1.6)
psi (MPa) 601 (4.15) 601 (4.15) 601 (4.15) 601 (4.15) 601 (4.15)
ft
2
(m
2
)
Number/Unit
Outer Diameter
in
(mm)
Nominal Airflow cfm
(Hi-Lo)
(m
3
/min
)
Starting Method
Nominal Output W
Quantity
Insulation Class
Model
Heat Exchanger Type
323 3
44 42 62 62 62
3
(0.29) (0.46) (0.46)
Maximum Operating Pressure
Total Face Area 2.26 3.12 3.12 4.95
Number of Coil/Unit 1111
Indoor Fan
2222
Indoor Fan Motor
(15.5-11) (25-17.5) (25-17.5)
7-1/16 7-7/8 7-7/8
(180) (200) (200)
11111
130 150 150 250 280
FBBBB
(H,Y)IDH048B21S
1236-890547-388 883-618 883-618
(H,Y)IDH018B21S (H,Y)IDH024B21S (H,Y)IDH030B21S (H,Y)IDH036B21S
7-7/8 7-7/8
(35-25.2)
Drip-Proof Type Enclosure
PSC (Permanent Split Capacitor)
Multi-Pass Cross Finned Tube
Copper Tube
Aluminum
Multi-Blade Centrifugal Fan
(33.7-23.5)
1190-830
(200) (200)
2
1
4.95
(0.21) (0.29)
DUCTED
2-6
TC-18001
Models: (H,Y)IDH018B21S, (H,Y)IDH024B21S, (H,Y)IDH030B21S, (H,Y)IDH036B21S
and (H,Y)IDH048B21S
2.3.5 Operation Space
2.3.6 Sensible Heat Factor (SHF)
Model SHF*
(H,Y)IDH018B21S 0.83
(H,Y)IDH024B21S 0.85
(H,Y)IDH030B21S 0.83
(H,Y)IDH036B21S 0.83
(H,Y)IDH048B21S 0.84
Rear Side
≥ 39-3/8
(1000)
≥ 39-3/8
(1000)
View from Top
Front Side
(5-1/8(130))
≥ 23-5/8
(600)
≥ 23-5/8(600)
Electrical Box
(Unit: inch (mm))
Service Access
Door (≥
17-11/16 (450))
If the ceiling board
cannot be found
for servicing,
prepare a service
access door
below the indoor
unit for removing
the indoor unit.
NOTE:
* SHF is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80
o
F DB (26.7
o
C DB)
67
o
F WB (19.4
o
C WB)
Outdoor Air Inlet Temperature: 95
o
F DB (35.0
o
C DB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0 ft .(0m)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87