Wolf TGB-60, TGB-40 Installation Instructions Manual

  • Hello! I am an AI chatbot trained to assist you with the Wolf TGB-60 Installation Instructions Manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
I nstaIlationinstructions
---
WOJ,
Technology for life.
Gas~firedwall-mountedcondensingboiler
TGB-40.
TGB-GO
., ,.,.r
&J f,i Control unit IFunction IOperation.
r /
~1
fr[
!
r
ft .
~
.J.
ON/OFFswitch
Display
Programming
keys
DHW
temperature
selector
Systempressure
Resetbutton
Programselector
Heatingwater
temperature
selector
ON/OFFswitchON/OFF
CD
ResetAfault isresetbypressingthe reset button whichwill alsorestartthe
system.Thesystemisrestarted ifthe resetkeyisactivated when there was
nofault present
inthe system.
Heatingwatertemperaturedisplayorfault codemessage(flashing)
Thecurrent heating
watertemperatureis displayedbya two digitLCD
display.Adot illuminatesnext to the heating water temperature when a
flamehasbeenestablished.Aflashingfault codeappears inthe LCDdisplay
insteadofthe heatingwater temperature, whenafault hasbeendiagnosed.
Thefollowingtable explainstheir causes:
<II @
Fault code specification
Fault
Gasvalve,fault 2
Gasvalve,fault 1
Lackof air
Differential pressure switch fault
Gasfan,fault
Gasfan,
fault
CRCfault, boiler
CRCfault, burner
Fault in 24 VACsupply
Low-water indicator
Internal fault - control PCB
(flashing quickly)
Faultcode Fault
Faultcode
1
STB- High-limitsafetycut-out
20
4
Noflame established
21
5
Flamefailure duringoperation
22
6
STW- Excesstemperature
23
7
STBA- Excesstemperature
25
11
Flamepretence
26
12
Flowsensor faulty
30
13
Fluegas sensor faulty
31
14
DHWsensor faulty
32
(onlyfor SWconnection)
40
15
Outside temperature sensor
XX
fauIty
16
Returnsensor faulty
6
Setting
i
. .
9l
JiIif
Anti-seizing pump
protection
Cycle block
~
Control unit IFunction IOperation
The heating program selector enables you to choose four operating modes:
Summer mode(central heating off)onlyDHWheating;frost protectionfor
the centralheatingsystemisensured.Integralanti-seizingpumpprotection.
Winter mode;inwintermode,the boilerheatsthe heatingwater temperature
to the value set at the heating water thermostat. Accordingto the pump
operatingmode,the circulationpumpoperatesconstantly(factorysetti1'19)
or onlyparallelto the burner control with/without run-on period.
Select this setting .!!iTwhen connecting control accessories.
Emissionstest mode:
Theemissionstest modeisactivated byrotating the programselector into
position i. A dot illuminates between the heating water temperature
indicationonthe LCDdisplay,whilstthe systemisin emissionstest mode.
The program selector returns automatically to winter mode when it is
released.Afteremissionstest modehas been activated,the boilerheats to
the temperature set at the heatingwater thermostat without modulation
orto the maximumheating water temperature adjustedvia parameterno.
8. Any previouscycle blockwill be cancelled.The red dot between the
heating water temperature indication extinguishes when emissionstest
modeends.Inconjunctionwith DRT/ DWT/ DWTM/ DWTK,the emissions
test symbolwillbetransferred to the function display.Activationonlyon
the boiler.
°,
DHWtemperature selection
When gas-fired condensing boilers are combined with a DHWcylinder,
setting1-9 correspondstoa cylindertemperatureof15-70°c.
°,
Heating water temperature selection
Thesetting range 1-9 correspondsto a heating water temperature of
20-75 (85)°C.Thesetting on the heating water thermostat willbecome
ineffectivewhen the system is used inconjunction with a digitalroom
thermostat or a weather-compensated controller.
Pressure di~play
Thisindicatesthe water pressurein the heating system.Innormal
operation,the water pressureshould be between 1.5-2.5bar.
Insummer mode, the circulator pump operates for approx. 30 seconds after
a maximum idle period of 24 hours.
Aburnerstart-up delayisintegrated to avoidfrequent burnerstarts during
the heating mode.Thecycleblockcan be adjusted from0-30 minutes.
7
~
Program
selector
Setting
or
.:=u
11\
Setting
m-
Layout
1GB-40 11GB-GO
Fluepipe
Fanmotor
Gasfan
Gas-airmixing chamber
Gasrestrictors
STB/flow sensor
Pressurecell
(in the combustion
chamber)
Fluegassensor
Condensatesiphon
Gas combinationvalve
Central heatingflow
Gassupply pipe
8
Quickacting
air vent valve
Combustionchamber
casing
Burner
Heatingwaterheat
exchanger
Flow switch
Returnsensor
Heating circuit pump
Overflowvalve
Centralheating return
.
107
0
M
M
N
U)
M
r--.
(!)
0
N
200
480
Fig.: DimensionsTGB-40jSO
4
1Heatingflow
2 Gasconnection
3 Heatingreturn
4 Condensatedrain
Fig.: ConnectionsTGB-40jSO
~\
Dimensions
105
U)
U)
co
370
13
Fig.: DimensionsTGB-40jSO
General
Theheating output will bedeterminedby the fan
speed. You can modify the heating output by
changing the fan speed in accordancewith the
setting valueslisted in table "Output adjustment".
Lower output limit
. Press both programming keys (+) and (-)
simultaneously;the displaywill show"a.".
. With key(+)selectparameter no. 2forthe lower
output Iimit.
. Pressresetkey;the factory-set parametervalue
accordingtothetablebelowwiIIthenbedisplayed.
.Changethe parameterwith the (+) or (-) key.
. Pressthe reset key; the modified value will be
adopted, and the display will again show the
heatingwater flow temperature.Thisterminates
the adjustment of the loweroutput.
Upper output limit
. Press both programming keys (+) and (-)
simultaneously;the displaywill show"a.".
. With key(+),selectparameter no.3forthe upper
output limit of DHW cylinder loading or
parameter no. 4 for heating mode.
. Pressresetkey;the factory-set parametervalue
accordingtothetable belowwill thenbedisplayed.
.Changethe parameterwith the (+)or (-) key.
. Pressthe reset key;the modified value will be
adopted and the display will again show the
heatingwater flow temperature.Thisterminates
the adjustmentof the upperoutput.
Changingthe output
Resetbutton
(-) (+)
Programmingkeys
Fig.: Controlunit display
Table: Output adjustment TGB-40
Table:
Output adjustment TGB-60
~ -eating
23
Displayinglmodifying control parameters
~
Modifications must onlythe carried out
bya recognised heating contractor or by
Wolf service engineers.
~
Incorrect operation can lead to the
system developing faults.
Please note when using parameter 5
(frost protection/outside temperature),
that frost protection is not safeguarded
ifyou set temperatures lowerthan 0 °c.
To'preventdamageto the heating system,
cancel night setback when outside
temperatures fall below -12°C. If this
rule isnot observed, icemayaccumulate
on the flue outlet, which may cause
injury to individuals or damage to
property.
Displaying/modifyi ng control
parameters
. Press both programming keys (+) and (-)
simultaneouslyuntil
the displayshows"0.".
. Changethe requiredparameterno.with programming
keys(+)or (-).
. Pressresetkey;the factory-set valuesaccording
to the "Factorysettings" will
then be displayed.
. Changethe parametervalue with the (+) or (-)
programmin~keys.
. Pressthe reset key;the modified value will be
adopted and the display will
again show the
heatingwaterternperatureo
24
Resetbutton
(-)
(+)
Programmingkeys
Fig.: Controlunit display
Displaying/modifying control parameters
Control unit parameters
Table:Factorysettings control unit parameters
* Setparameter10to 1 if the control unit accessorytype DWTMisco.nnected.
** When connectinga DWTK,parameter95 will indicate the modulation level,not the setflow temperature.
Gas-air connection adjustment
Implementation
Thisadjustment isonlypermissibleafter changing
the type of gas. or in case of problems.
Implementthe gas-air-connection firstinthe upper
loadrange(emissionstest mode)andthen inthe
lowerload range (softstart).
Adjusting the CO2value in the upper
load range (emissions test mode)
. Setthe programselectorto Ii emissionstest (a
reddotappearsbetweenthefiguresonthedisplay).
. Removethe cap nut from the r.h. test nipple
"Ventilation air" <ID.
. Check the CO2concentration at the ventilation
air nipple<ID.Theflue pipe is not gas tight ifthe
CO2content> 0.3 °/0;rectifythe leak.
. Checkthe C02contentat full load.
CO2valueinthe upperloadrange in emissionstest
mode:
Table:CO2 content to beselected
.CorrecttheCO2adjustment(ifrequired)bycarefully
rotating the gasflowadjustment screw@ onthe
gas combinationvalve.
.Turnto the right - the C02contentwillbe
reduced
Turnto the left - the CO2content willincrease
26
ON/OFF switch
Programselector
Fig.: Control unit overview
Gas flow adjustment
screw@
Adjustmentscrew @
lower load
Fig.: Adjusting the CO2content
Fig.: Testnipples
Gas-air connection adjustment
Adjusting the CO2value in the lower
load (soft start) range
. Setthe heating programme switch to heating
mode.
. Turn to the right - the-CO2content will be reduced
Turn to the left - the CO2content will increase
CO2value in the lower
load range:
Table:CO2 content to beselected
Basic setting
Thebasicsetting mayonlybe implemented if the
gas combinationvalve has been adjusted and the
burner nolongerstarts.
Please carry out the following steps:
- Turnthe gasflowadjustmentvalve@untilit is
flush with the top of the cast component
(gascombinationvalve).Thenturn the screw at
TG6-40three half-turns to the right.
- Turnthe adjusting screw@ on the gas
combinationvalvefullyto the right,andthen five
half-turns to the left.
- Then start the boiler and adjust the
gas-air-connection.
ON/OFFswitch
Resetbutton
Fig.: Control unit overview
Gas flow adjustment
screw
@
Adjustment screw @
lower load
Fig.: Adjusting the CO2content
Programselector
Maintenance
Dismantling the combustion chamber
unit
.
Removethe combustion chamberhousing after
releasingthe toggles.
. Removethe plugconnectionsfrom the following
components:
Ignition, ionisation, flow and return sensor,flue
gastemperaturesensorandgasfan.
.Pullthe anti-radiation panelforwardandunhook
the panel.
. Releasethe fixings betweenthe gasconnection
and mixing chamber.
. Release the nuts (three no.) on the small
combustion chamberlid.
.Removethe wholeunit (mixingchamber,fan and
small combustionchamberlid).
Flowsensor.
plug
Gasfanplug
Ignitionplug
lonisationplug
Earthplug
Fluegas
sensorplug
Fig.: Gas-firedcondensingboilerwith combustion chamber
housing removed
Anti-radiation panel
Fig.: Anti-radiation panel
Fixingsbetweenthe gasconnection and mixing chamber
Fig.: Fixingsbetweenthe gasconnectionandmixingchamber
Nut on thesmall combustion chamberlid
Fig.: Nut onthe combustion chamberlid
. Slackenthe union nut of the ventilation pipe
towards the quick-acting air-vent valve and
remove the whole quick-acting vent valve
upwards.
.Releasethe flow andreturn compressionfittings.
.Pushthe flue pipe damperupwards.
.Unscrewand drain the boiler siphon.
.Undoscrewfrom the lid/rear panel.
.Lift the complete combustion chamberunit out
until the condensatedrainconnectionisfreeand
the combustion chamber unit can be removed
towardsthe front.
Maintenance
Screw,lid, rearpanel
Fig.: Unionnut/rear panel,lid
Flowcompressionfitting Returncompressionfitti ng
Fig.: Compressionfittings
Boilersiphon
Fig.: Boilersiphon
Combustion chamber unit
Fig.: Combustionchamberunit
/
.~
~
Maintenance
Burner/heatingwater heat exchange
disassembly. cleaning and assembly
.Slackenandremovethethreadedrodsofthe large
combustionchamberlid (four no.).
.Removethe burner upwards.
.Removethe largecombustionchamberlid.
.Removethe combustion chamberbase.
Threadedrod
Fig.: Threadedrodsof the largec:ombustionc:hamberlid
Burner
Fig.: Burner
32
Fig.: Largec:ombustionc:hamberlid
Fig.: Combustionc:hamberunit
Ic:ondensatesump
Combustionc:hamberbase
Fig.: Combustionc:hamberbase
.Removecombustionresidueswith aplastic brush
(non-metallic brush).
.Washseverelycontaminated burnersin a soapy
solution andrinsewith tap water.
.Cleanseverelycontaminated heatingwater heat
exchangerswith Fauch600,Fauch610,Sotin230
(230GA)orequivalentcleaningagentsandrinse
with tap water.
.Reassembleinthe reverseorder.
Generally,replaceall gasketsonwater andflue
gascomponentswhichhavebeenseparatedand
coatwithsilicongrease(othergreasewilldestroy
the gaskets)priorto reassembly.
.Duringreassembly,checkfor correct positioning
of the combustionchamberunit inrelation to the
condensatesump.
.During reassembly,checkfor correct position of
the control cables.
Safety instructions
Carryout the following stepsafter completingthe
abovemaintenancesteps:
. Openthe shut-off valveat the heatingflow
andreturn. Openthe cold water inlet.
. Topupthe heating system,if required,to
approximately 1.5bar,andvent the heating
system.
. Openthe gasshut-off valve.
. Switch on the emergencystopswitch (if
installed).
. Switch on the ON/OFFswitch on the Wolf gas-
fired boiler.
. Checkthe boiler water and gasconnectionsfor
leaks.
. Checkthe boilerfor perfectfunction andflue gas
values.
. Hookin the front casing.
Maintenance
Heating water heatexchangercomplete with the
combustion chambercylinder
I
Fig.: Heating water heatexchanger
Combustionchamberunit
Condensatesump
Fig.: Positionof the combustion chamberunit/condensate
sump
Fig.: Controlcableposition
33
cfi
~~
Specification
Ratedoutputat 80/60°C
Ratedoutput at 50/30 DC
Ratedthermal load
Lowestoutput (modulating)at 80/60
Lowestoutput (modulating)at 50/30
Lowestthermal load (modulating)
kW
kW
kW
kW
kW
kW
37.2
40.5
37.9
11.2
12.1
11.4
55.4
60.6
57.2
21.9
23.6
22.3
Gasconnection value:
NaturalgasE/H(Hi=9.5 kWh/m3=34.2MJ/m3)m3/h
Natural gas LL(Hi=8.6 kWh/m3=31.0MJ/m3)m3/h
LPG(Hi= 12.8kWh/kg=46.1MJ/kg) kg/h
Gassupplypressure:
Naturalgas
LPG
4.0
4.4
3.0
6.0
6.7
mbar
mbar
17-25
25-45
17-25
Permissiblesensor temperatures
Fluegas massflow rate
Fluegas temperature 80/60 - 50/30
Availablegasfan draught
Fluegas valuegroup accordingto DVGWG635
DC
g/s
DC
Pa
95
17.3
67- 43
130
G52
95
26.7
80-50
185
G52
* notapplicabletoAustria/Switzerland
36
w
00
T1 (transformer)
YO(Gaskombiventil)
Wiring
TGB-40/60
diagram
X6 r.- M2(Fan)
(PE terminal) i
A
- M
~rrrrn . 32'
-'f'j";"')"j' I"'TT 12345
go/gn,. I , ,. gO/g~'lbrl gl kmobJ 1:.s
GNol I~WM
n-Halll 124VDC
!! i i 1.':.:.-_'.-:...
iii:r-;::;;:
,
' ge/grr
~-'...!
'LII
!! ii
II' .
. .11
!! ii
!! ii
II' .
. .11
!! ii
II' .
, .11
_.I! ii
I' .
.11
I' ,
.11
!ii
I' .
.11
!ii
I' .
.1,
I' .
.1,
!ii
I' .
: : ~~~ffl'l~ r~ltf.~~J~lb~.-. -, -,.
~
gr/rs "I oG-t!
84 (boiler return sensor)
vio
I I Ii '/iiefgn gr/r.
Flow, return, fluegas sensor, differential pressure switch
vii>~!if
Secondary
transformer
.. ..
lonisation / Fan
Earth conductor
Trafa Y2
+
-
.' '. .' '.
~B~ ~8~
Pump
PWM
Net Z FV
Thermo- Access. AF
stat Bus
LNLNL ab+-+.
Printed wiring board
of control contacts
L N L N
,- .- .go/gn
bl
S1 (water flow detector)
"~~~
Rod
casing
X1 (dummy plug)
, , , ,
'
I(
,
. .
, .
. .
1.~ ~ !
,~~J!?~!!?~i.~.~r..~.~~.~~r.L ,
1.~~~.~~.~~.~.~~~~.~.~~.~Jr)
85 (Ionisation) L.E1 (igintion devicb)
- '+ Ibr
!)f)f)!)()f:> -~
p
~
Brenner @ ibl
-,-,-,-8,-,-,
Burner t;p. go/gn
Bruleur >0;;1
Bruciatore
Brander
ICiCi(i)1
I I..............
~2 ~2 X4 (dummy plug) 1~:~"fi'>!I
Bla,ck G~y *When connectin
g a roomthermostat i ~ il~2
casing casmg . ;..~ ,Vollowcasmg
V
remove Jumper. X5 (plug for 3-way valvel)
PIP: Prior to replacing of fuse isolate [""""""""""""""""1
& appliance from main supply. :~:
The ON/OFF switch does not provide i ~-~:
main supply isolation of appliance. i ~.~.~~!:...~i
M1(Pump) Y3 (3-way-valve)
~
-.
~
-.
~
~
c.
-.
Q,)
~
~
Q,)
3
p
";,\
m
"
, '
, .
\1',',
:.'
Z':
:, Z
.' . .'
CD
i!
, '.
.'
. I I. . I
::
:')
. ..
...
Y1 Zund
Pump
Net
L N L N
L N
Troubleshooting
If afault occurs,the BIASoperating,information anddisplaysystemdisplaysafauIt code,to whichcauseand
remedyfromthefollowing tablemaybeallocated.Thistableisdesignedto allowyour localheatingcontractor
to tracethe fault moreeasily.
E= pressthe reset button after a fauIt has been removed
E
STB
- High-limitsafety cut-out
Theflow temperaturehasexceeded110°C.
The maintenance valves were closed during maintenance,
no fault.
No flow through the heat exchanger due to
- an inadequately vented system
- a faulty overflow valve
- a faulty pump + a faulty flow switch
- a blocked water pipe + a faulty flow switch
The control unit records an incorrect flow temperature due to
- a faulty flow sensor
5 E
Flame failure during operation
Flamefailure within 15 s after
the flame hasbeensuccessfullyrecognised.
Lack of gas because
- the gas supply pressure is too low.
The gas mixture is difficult to ignite because
- the CO,value is outside the permissible range
- flue gas is getting into the combustion air supply - flue pipe is not gas-tight
- the gas restrictors or their gasket not OK,if required for this boiler
- of wind influence, the wind protection is missing
Faulty components must be replaced with original spare parts.
Troubleshooting
If afault occurs,the BIASoperating,information anddisplaysystemdisplayafault code,to which causeand
remedyfromthefollowing tablemaybeallocated.Thistableisdesignedto allowyour localheatingcontractor
to trace the fault moreeasily.
E = pressthe reset button after a fault has been removed
7 E
STBA
- Excess temperature
The flue gas temperature has exceeded
the limit for the STBAshutdown of 110 °c.
Flue gas temperature too high because
- the output is too high
- of a contaminated or faulty heat exchanger
Flue
gas system protection.
!
I
i~ .~
23
Differential pressure switch fault
The differentia I pressure switch does not
switch OFF.
Gas fan does not switch OFF.
Monitoring interrupted by
- a faulty differential pressure switch
- water or contamination in the hoses to the
differentia I pressure switch.
Faulty components must be replaced with original spare parts.
Lr
,"
,;,;
i
-
I'
:-i
Troubleshooting
If afaultoccurs, the BIASoperating,information anddisplaysystemdisplaysafault code,to whichcauseand
remedyfrom the following table may beallocated. Thistable isdesigned to allowyour local heating contractor
to tracethe fauIt moreeasiIy. .
E = press the reset button after a fau It has been removed
X.y.
E
Control PCB faulty
Electronic module fault
The internal self-test has discovered
an error.
Faulty components must be replaced with original spare parts.
/