Eaton VoCALL 16 Operating instructions

Type
Operating instructions
VoCALL 16 Emergency Voice Communication System
Installation and operation manual
2 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
Contents
Contents
1. DOCUMENT UPDATE NOTES ..................................4
2. PROPRIETARY NOTICE .......................................4
3. DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY .....4
4. SUPPORT SERVICES .........................................5
5. IMPORTANT SAFETY INFORMATION ...........................6
6. RECEIPT/UNPACKING ........................................8
7. ABOUT THIS MANUAL .......................................9
8. LIST OF ABBREVIATIONS .....................................9
9. OVERVIEW ................................................10
9.1 Introduction ...............................................10
9.2 Master Panel – All Variants ....................................12
9.3 Type A Outstation – All variants .................................13
9.4 Type B Outstation – All variants .................................14
9.5 Features ...................................................15
10. INSTALLATION ............................................16
10.1 Placement guidelines (As per BS 5839-9: 2011) ...................16
10.2 Mounting Instructions .......................................17
10.3 Network topology ..........................................29
10.4 Cabling requirements .......................................30
10.5 Wiring details ..............................................31
11. COMMISSIONING .........................................39
11.1 Wiring check ..............................................39
11.2 Configuration steps .........................................40
11.3 Definitions of Access levels ..................................54
11.4 Configuring access profiles ...................................56
11.5 Test procedure .............................................63
11.6 Documentation .............................................63
3INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
Contents
12. COMMUNICATION .........................................64
12.1 Making a call from an Outstation ..............................64
12.2 Receiving the call on Outstation ...............................64
12.3 Ending a call from an Outstation ...............................64
12.4 Dial Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
12.5 Receiving a call at the panel handset ...........................66
12.6 Making a call from the panel handset ...........................66
12.7 Ending a call at panel handset .................................66
12.8 Holding the call at panel handset ..............................67
13. INDICATIONS .............................................68
13.1 Visual indications - Panel .....................................68
13.2 Audible indications - Panel ....................................69
13.3 Visual indications - Outstation .................................69
13.4 Audible Indication – Outstation ................................70
14. LOGGING FACILITY ........................................71
14.1 Call logs ..................................................71
14.2 Fault logs .................................................73
14.3 Event log .................................................75
15. SOFTWARE UPGRADES ....................................76
16. MAINTENANCE (AS PER BS 5839 – 9:2011) ....................77
16.1 Responsibility .............................................77
16.2 Routine ..................................................77
16.3 Non routine ...............................................78
APPENDIX ..................................................79
APPENDIX 1 - Package Content Checklist ...........................79
APPENDIX 2 - Default PINS ......................................80
APPENDIX 3 - SD Card folder structure .............................80
APPENDIX 4 – Quick reference ....................................81
APPENDIX 5 – Checklist .........................................83
APPENDIX 6 – Menu tree ........................................84
APPENDIX 7 – Cyber security Guidelines ............................85
4 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
1. Document Update Notes
1. DOCUMENT UPDATE NOTES
S.No. Release / Change Notes Date Approved By
1 First Release - Standalone configuration Sep 18
2. PROPRIETARY NOTICE
All data and information contained within this manual is of proprietary nature.
Do not reproduce, transcribe, store in a retrieval system or translate into any
language, any part of this manual without the prior permission of ‘EATON‘. EATON
reserves the right to make changes to product specification without notice or liability.
Every care has been taken to ensure the accuracy of the information contained in
this manual, but no liability can be accepted for any errors or omission.
3. DISCLAIMER OF WARRANTIES AND
LIMITATION OF LIABILITY
The information, recommendations, descriptions and safety notations in this
document are based on Eaton Corporations (“Eaton”) experience and judgment and
may not cover all contingencies. If further information is required, an Eaton sales
office should be consulted. Sale of the product shown in this literature is subject
to the terms and conditions outlined in appropriate Eaton selling policies or other
contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED
OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR
PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET
OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH
CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF
THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT
BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort
(including negligence), strict liability or other-wise for any special, indirect, incidental
or consequential damage or loss whatsoever, including but not limited to damage
or loss of use of equipment, plant or power system, cost of capital, loss of power,
additional expenses in the use of existing power facilities, or claims against the
purchaser or user by its customers resulting from the use of the information,
recommendations and descriptions contained herein. The information contained in
this manual is subject to change without notice.
5INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
4. Support Services
4. SUPPORT SERVICES
The goal of Eaton is to ensure your greatest possible satisfaction with the operation
of our products. We are dedicated to providing fast, friendly, and accurate assistance.
Website
Use the Eaton website to find product information. You can also find information on
local distributors or Eaton sales offices.
Website URL: https://www.uk.eaton.com/
Please mail us if you need assistance with placing an order, stock availability or
proof of shipment, expediting an existing order, emergency shipments, product price
information, returns other than warranty returns, information on local distributors or
sales offices and technical support.
Tech support: FireTechSuppor[email protected] Tel: +44 (0)1302 303350
Customer services: FireCustomerService@eaton.com Tel: +44 (0)1633 628566
6 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
5. Important Safety Information
5. IMPORTANT SAFETY INFORMATION
Personnel who install, maintain or repair this equipment must read the safety
information below before starting work.
Denitions and symbols
WARNING
Indicates a potentially hazardous situation which, if not avoided, can result in
serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, can result in
minor to moderate injury, or serious damage to the product.
General Safety Precautions
WARNING
This equipment is defined as Class 1 in EN 62368-1:2014 and must be EARTHED.
WARNING
This equipment is intended for continuous operation and as such should be
permanently connected to the mains supply. This unit does not contain an
external mains switch. Each compact unit requires a 3A fused connection unit,
returning to a breaker clearly marked EVCS DO NOT TURN OFF.
WARNING
Voltages in excess of 30V RMS AC or 50V DC is considered Hazardous and
in certain circumstances can be lethal .This product contains wiring and
terminations that are energized to 230V RMS AC mains. Before attempting to
remove this component, ensure the Mains Power Supply and Battery Backup
have been disconnected.
WARNING
No user serviceable parts. Testing, maintenance or repair with Mains Power
(and/or battery) connected should only be undertaken by personnel who are
trained and have taken adequate precautions.
7INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
5. Important Safety Information
WARNING
If the units are distributed around a site it is essential all units are on the same
mains phase, as they are classified TEN 230V, powering from different phases
can mean a 440V potential can be present in a unit during a major
fault incident.
WARNING
Indoor use only. Do not expose this unit to rain or moisture.
CAUTION
VoCALL 16 must only be installed by certified Eaton personnel i.e. an Eaton
Customer Service Engineer or certified installer. In case of violating these
requirements the warranty provided will not apply and EATON will not be held
legally accountable.
CAUTION
Before handling PCB, operator should get rid of any electrostatic charge. Always
handle PCBs by their sides and avoid touching any components.
This product must only be disposed of in
accordance with the WEEE directive.
8 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
6. Receipt/unpacking
6. Receipt/unpacking
On receiving the unit, verify that the catalog number and unit options stated on
the shipping container match those stated on the order/purchase form. Inspect the
equipment upon delivery. Report any crate or carton damage to the carrier prior to
accepting the delivery, and have this information noted on the freight bill.
Remove all packing material from the unit. Check the unit for any signs of shipping
damage. If damage is found after unpacking, report it to the Freight Company and
EATON. Retain the packaging materials for the carrier to review.
Storage
It is recommended that the unit should be stored in its original shipping box/crate
until it is to be installed. The unit should be stored in a location where:
The ambient temperature is -5ºC to 40ºC
The relative humidity is 0% to 95%, non-condensing
The environment is dry, clean and non-corrosive
The unit will not be subjected to high shock or vibration conditions
ote:N Refer to Appendix 1 for package content checklist
ote:N Batteries are not supplied with the unit and should be procured separately.
9INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
7. About this manual
7. About this manual
This manual contains important instructions that must be followed during installation,
start, start-up, configuration and customization, operation and maintenance of the
VoCALL 16 range of products. All instructions must be read before installing and
operating the equipment. This manual should be saved for future reference as well.
This manual is aimed at specialist personnel, who are responsible for the installation,
commissioning and maintenance of VoCALL 16 emergency voice communications
system (EVCS) and other personnel who are responsible for operating the system.
8. List of Abbreviations
Abbreviation Definition
EVCS Emergency Voice Communication System
VoCALL Eaton product range for EVCS
BS British Standard
MX16 Master panel /Telephone
OS Out-station / Remote Terminal
PSU Power Supply Unit
SS Stainless steel
SLA Sealed lead acid
10 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
9. Overview
9. Overview
9.1 Introduction
VoCALL 16 EVCS is a loop-wired, fully addressable, monitored and secure,
bi-directional communication system.
The VoCALL 16 product range is designed to comply with BS 5839 Part 9 : 2011.
VoCALL 16 system comprises of two subsystems:
Panel: MX16
Outstations: Type A, Type B
Product range
The offerings under EATON VoCALL 16 product range are listed below:
CATALOGUE NUMBER DESCRIPTION
Panel
MX16 VoCALL 16 Master panel
MX16-SSC VoCALL 16 Master panel stainless front pack, Flush mounting
Outstation
TA16-RS Type A Outstation - Red, Surface mounting
TA16-BEZ Type A Outstation bezel - Red, Flush mounting
TB16-GS Type B Outstation - Green, Surface mounting
TB16-GF Type B Outstation - Green, Flush mounting
TB16-RS Type B Outstation - Red, Surface mounting
TB16-RF Type B Outstation - Red, Flush mounting
11INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
9. Overview
Technical specifications
Unless otherwise stated, the following technical specifications apply to the
VoCALL 16 product range:
Feature Range
Standards compliance BS 5839-9: 2011*
EMC EN 55103-2: 2009
EN 55032: 2015 (Emission)
EN 55035: 2017 (Immunity)
Cable FP200 type
Max. distance between Outstations 200 metres
Network configuration Loop Wired – Outstation / Remote Terminal
AC supply voltage - Input 230V ± 10% RMS 50/60 Hz AC
Temperature (operating and storage) -5°C up to +40°C
Humidity 98% Non-Condensing
IP Rating IP20
*BS 5839-9: 2011 Fire detection and fire alarm systems for buildings. Code of
practice for the design, installation, commissioning and maintenance of emergency
voice communication systems.
12 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
9. Overview
9.2 Master Panel – All Variants
Figure 1: MX16 and MX16 –SSC
MX16 VoCALL 16 Master panel
MX16-SSC VoCALL 16 Master panel stainless front pack, Flush mounting
Dimension H 355 X W 488 X D 155 mm
Front Pack Dimension H 390 X W 522 X D 2.5 mm
Weight 6.2 kg excluding battery (MX16).
3.5 kg excluding battery (MX16-SSC).
Knockouts 20 X 20mm dia at top, Rectangular knockout at rear - W 114 X H 37 mm
Power Supply 230V ± 10% RMS 50/60Hz AC
Power Consumption 2.7 Watts
Fault Indications Audio visual - Network/Communication, Sensors, Health
Security Handset behind lockable door
Memory 4 GB SDHC card
Batteries 2 x 12 V, 12 Ah SLA battery. Yuasa NP12-12 (Recommended)
ote:N MX16-SSC front pack is available as a separate front pack unit
for flush mounting.
Flush mounting: MX16 Panel + MX16-SSC (Front pack). MX16-SSC should to be
procured separately.
13INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
9. Overview
9.3 Type A Outstation – All variants
Figure 2: TA16-RS and TA16-BEZ
TA16-RS Type A Outstation - Red, Surface mounting
TA16-BEZ Type A Outstation bezel - Red, Flush mounting
Dimension H 320 X W 152 X D 114 mm
Bezel Dimension W 189 X H 343 X D 1 mm
Weight 2.2 Kg
Knockouts 4 X 20mm dia at bottom
Power Supply 21V to 27.6V (Nominal 24V) DC
Power Consumption Active - 0.65 Watts
Standby - 0.52 Watts
Fault Indications Audio visual - Network/Communication, Sensors
Security Handset behind latched door
ote:N TA16-BEZ is available as a separate bezel unit.
Flush mounting: TA16-RS + TA16-BEZ (Bezel). TA16-BEZ should be procured separately.
14 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
9. Overview
9.4 Type B Outstation – All variants
Figure 3: TB16-RS , TB16-GS, TB16-RF and TB16-GF
TB16-GS Type B Outstation - Green, Surface mounting
TB16-GF Type B Outstation - Green, Flush mounting
TB16-RS Type B Outstation - Red, Surface mounting
TB16-RF Type B Outstation - Red, Flush mounting
Dimension H 137 X W 137 X D 56 mm
Flush unit Dimension H 162 X W 162 X D 56 mm
Weight 0.8 Kg
Knockouts 5 X 20mm; 1 X 25m at side walls; 6 X 20mm at rear
Power Supply 21V to 27.6V (Nominal 24V) DC
Power Consumption Active - 0.65 Watts
Standby - 0.52 Watts
Fault Indications Audio visual - Network/Communication, Sensors
Security Not applicable. User interaction using buttons on front.
15INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
9. Overview
9.5 Features
Fully compliant with BS5839-9: 2011 (abb. Pt9): VoCALL 16 supports the
features required to support designing, installing, commissioning and servicing
according to BS 5839-9:2011 Part 9: Code of practice for the design, installation,
commissioning and maintenance of emergency voice communication systems.
Loop wired configuration: VoCALL 16 outstations are connected on a loop.
Studies have shown this approach can support up to a 75% reduction in cable
installation costs. i.e. cables, tray, fixings, conduit and most importantly, time.
Simple and easy installation: VoCALL 16 Panel can support up to 16 Outstations
on a loop. Outstations can be of any Type A/B. No extra accessories are required
to extend the system. System size modifications could be achieved with ease with
minimum design effort.
Continuous fault monitoring and fault tolerant design: VoCALL 16 continuously
monitors faults throughout the entire system. The system is designed with a fault
tolerant loop to ensure high availability – isolators protect the signal path from loss
of operation during times of a single cable fault.
Superior audio quality: VoCALL 16 is a designed as a fully digital system.
The panel and outstations communicate via a digital signal which provides high
immunity to electrical noise and ensures superior audio quality for maximum safety.
Appealing look: VoCALL 16 product range is an attractive offering, supporting
flush mounted variants for all units.
User interface: Large LCD screen, keypad and a simple menu system to allow
ease of working during system configuration, monitoring and normal operation.
User configuration: VoCALL 16 allows up to a maximum of 10 user login / profiles
to be created per panel. Each user can be configured independently allowing
the system administrator the flexibility to support the needs of even the most
demanding applications. For more information, refer to Section 11.
Secure communications: VoCALL 16 has been designed within Eatons stringent
cyber security guidelines. The system is designed to protect against unauthorized
and malicious users. For more information refer to Appendix 7.
Storage: The VoCALL 16 system supports capacity to store 2000 transactional
records in a history log per panel. A 4GB SD card is provided with each panel
which provides storage for the historical records.
16 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
10. Installation
10. Installation
10.1 Placement guidelines (As per BS 5839-9: 2011)
The VoCALL 16 system is intended for indoor usage. Outstations should not be
installed outdoors unless an IP65, or better housing, is used and cables are installed
so as to prevent the ingress of moisture.
General guidelines – Panel
There should be at least one panel in a building or complex.
Panel(s) should be located:
1. Close to the main fire alarm panel or a repeater fire panel, in an area of low
fire risk.
2. In an area with low background noise, particularly during an emergency.
Fire alarm sounders should not be located near to panel.
3. Preferably in a manned control or security room. In a control room, the panel
should be within easy reach from the operators normal position.
General guidelines – Outstation
Outstation location should be as per application of the EVCS system.
1. Fire and rescue service assistance: Outstations should be provided on all
floors of the building served by firefighting stairs, and in the firefighting lobby
to each firefighting stair. An additional outstation should be provided at each
fire and rescue service access point.
2. Evacuation Management: Outstations should be provided on all escape
staircases on every floor of the building.
3. In an emergency, communication with disabled building occupants:
Outstations should be provided in all refuges and, where appropriate, an
outstation should be provided adjacent to the evacuation lift on each floor.
They should be mounted at a height of between 900 mm and 1.2 m above the
floor in an easily accessible, well illuminated and conspicuous position, free
from obstruction.
ote:N Background noise levels in the vicinity of devices should be kept as low as
possible, preferably less than 40dB.
17INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
10. Installation
10.2 Mounting Instructions
MX 16 and MX 16 – SSC
1. Take the unit out of the packing material.
2. Check the content against checklist provided in Appendix 1.
Figure 4: MX 16 panel
Front display: MX 16 panel contains user interface – keypad input and screen.
Handset is secured behind a locked door.
Handset
User Interface
Lock
18 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
10. Installation
3. To lift top cover – Open screws. Lift the cover from bottom and push back to
disengage clips. Disconnect ground cable for easy operation.
Figure 5: Steps to open top cover
Figure 6: View of panel with top cover detached
Ground Cable. Disconnect for easy operation.
1.
2.
3.
4.
19INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
10. Installation
4. Wire entry points: Knockouts are provided on top and rear for wire entry.
Double tag knockouts are provided for easy removal. Remove knockouts as
per requirement.
a. Top: 20 X 20mm diameter
b. Rear: W 114 X H 37mm
Connection Knockout # 2 core wire Knockout # 4 core wire
Outstation communication 4 2
Relay – In Use, Fault 2 1
Power supply 1 1
Input – Enable 1 1
Figure 7: Wiring holes are provided at top of enclosure.
ote:N Do not remove more knockouts than required. Use appropriate glands while
wiring. Recommended glands: AMP – TE Connectivity (178771-3)
Top Knockouts
20 INSTALLATION AND OPERATION MANUAL 25-13741-C October 2018 www.eaton.com
10. Installation
5. Wall mounting: Features are provided to support wall mounting of panel.
“Keyhole” design enables quick and simple mounting. Ensure all mounting
points are used to mount the console securely. 3x M4 screws can be used.
Figure 8: Front view of panel with user interface removed.
Only for display purpose. DO NOT DETACH THE UNIT.
Wire the unit. For details refer to section 10.5
6. Battery: VoCALL 16 MX panel requires 2 x 12V @ 12Ah sealed lead acid batteries
to provide backup power in event of mains failure. When mounting panel on wall,
place batteries in panel after mounting.
7. Reconnect ground cable, between top cover and back cover, before
closing the unit.
8. Security: To prevent inadvertent use of system, key lock is provided for handset
cabin. When panel is installed in public area please lock the door to ensure
authorized usage. When panel is installed in secured area, magnetic latch can be
used to hold the door in place. Authorized users should be provided with
key as required.
Mounting Holes
200mm 195mm
39mm
281mm
27mm
248mm
Mounting Hole Rear Knockout
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88