Eaton PowerXL™ Modbus RTU Communication Owner's manual

Type
Owner's manual

This manual is also suitable for

Manual
PowerXL
Modbus RTU
Communication manual
for Variable Frequency Drives
/
Variable Speed Starters
DA1, DC1, DE1
09/16 MN040018EN
Modbus
All brand and product names are trademarks or registered trademarks of the
owner concerned.
Emergency On Call Service
Please call your local representative:
http://www.eaton.eu/aftersales
or
Hotline of the After Sales Service:
+49 (0) 180 5 223822 (de, en)
AfterSalesEGBo[email protected]
For customers in US/Canada contact:
EatonCare Customer Support Center
Call the EatonCare Support Center if you need assistance with placing an order,
stock availability or proof of shipment, expediting an existing order, emergency
shipments, product price information, returns other than warranty returns, and
information on local distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 a.m. – 6:00 p.m. EST)
After-Hours Emergency: 800-543-7038 (6:00 p.m. – 8:00 a.m. EST)
Drives Technical Resource Center
Voice: 877-ETN-CARE (386-2273) option 2, option 6
(8:00 a.m. – 5:00 p.m. Central Time U.S. [UTC-6])
www.eaton.com/drives
Original Operating Instructions
The German-language edition of this document is the original operating manual.
Translation of the original operating manual
All editions of this document other than those in German language are translations
of the original German manual.
1
st
edition 2016, edition date 01/2016
2
nd
edition 2016, edition date 09/2016
© 2016 by Eaton Industries GmbH, 53105 Bonn
Production: René Wiegand
Translation: globaldocs GmbH
All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form (printed, photocopy, microfilm
or any other process) or processed, duplicated or distributed by means of electronic
systems without written permission of Eaton Industries GmbH, Bonn.
Subject to alteration without notice.
Rückenbreite festlegen! (1 Blatt = 0,106 mm, gilt nur für XBS)
(1 Blatt = 0,080 mm für Eberwein Digitaldruck bei 80 g/m
2
)
I
Before commencing the installation
Disconnect the power supply of the device.
Ensure that devices cannot be accidentally restarted.
Verify isolation from the supply.
Earth and short circuit the device.
Cover or enclose any adjacent live components.
Follow the engineering instructions (AWA/IL) for the
device concerned.
Only suitably qualified personnel in accordance with
EN 50110-1/-2 (VDE 0105 Part 100) may work on this
device/system.
Before installation and before touching the device ensure
that you are free of electrostatic charge.
The functional earth (FE, PES) must be connected to the
protective earth (PE) or the potential equalisation. The
system installer is responsible for implementing this
connection.
Connecting cables and signal lines should be installed so
that inductive or capacitive interference does not impair
the automation functions.
Install automation devices and related operating elements
in such a way that they are well protected against
unintentional operation.
Suitable safety hardware and software measures should
be implemented for the I/O interface so that an open
circuit on the signal side does not result in undefined
states in the automation devices.
Ensure a reliable electrical isolation of the extra-low
voltage of the 24 V supply. Only use power supply units
complying with IEC 60364-4-41 (VDE 0100 Part 410) or
HD384.4.41 S2.
Deviations of the mains voltage from the rated value must
not exceed the tolerance limits given in the specifications,
otherwise this may cause malfunction and dangerous
operation.
Emergency stop devices complying with IEC/EN 60204-1
must be effective in all operating modes of the automation
devices. Unlatching the emergency-stop devices must not
cause a restart.
Devices that are designed for mounting in housings or
control cabinets must only be operated and controlled
after they have been installed and with the housing
closed. Desktop or portable units must only be operated
and controlled in enclosed housings.
Measures should be taken to ensure the proper restart of
programs interrupted after a voltage dip or failure. This
should not cause dangerous operating states even for a
short time. If necessary, emergency-stop devices should
be implemented.
Wherever faults in the automation system may cause
injury or material damage, external measures must be
implemented to ensure a safe operating state in the event
of a fault or malfunction (for example, by means of
separate limit switches, mechanical interlocks etc.).
Depending on their degree of protection, frequency
inverters may contain live bright metal parts, moving or
rotating components or hot surfaces during and
immediately after operation.
Removal of the required covers, improper installation or
incorrect operation of motor or frequency inverter may
cause the failure of the device and may lead to serious
injury or damage.
The applicable national accident prevention and safety
regulations apply to all work carried on live frequency
inverters.
The electrical installation must be carried out in
accordance with the relevant regulations (e. g. with
regard to cable cross sections, fuses, PE).
Transport, installation, commissioning and maintenance
work must be carried out only by qualified personnel
(IEC 60364, HD 384 and national occupational safety
regulations).
Installations containing frequency inverters must be
provided with additional monitoring and protective
devices in accordance with the applicable safety
regulations. Modifications to the frequency inverters
using the operating software are permitted.
All covers and doors must be kept closed during
operation.
To reduce the hazards for people or equipment, the user
must include in the machine design measures that restrict
the consequences of a malfunction or failure of the drive
(increased motor speed or sudden standstill of motor).
These measures include:
Other independent devices for monitoring safety-
related variables (speed, travel, end positions etc.).
Electrical or non-electrical system-wide measures
(electrical or mechanical interlocks).
Never touch live parts or cable connections of the
frequency inverter after it has been disconnected from
the power supply. Due to the charge in the capacitors,
these parts may still be live after disconnection. Fit
appropriate warning signs.
Eaton Industries GmbH
Safety instructions
Danger!
Dangerous electrical voltage!
II
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 1
Table of contents
0 About this manual ..................................................................... 3
0.1 Target group................................................................................. 3
0.2 List of revisions ............................................................................ 3
0.2.1 Writing conventions ..................................................................... 4
0.2.2 Hazard warnings of material damages ......................................... 4
0.2.3 Hazard warnings of personal injury .............................................. 4
1 Engineering................................................................................. 7
2 Modbus RTU............................................................................... 9
2.1 General......................................................................................... 9
2.2 Communications .......................................................................... 9
2.3 RJ 45 interface ............................................................................. 11
2.3.1 Enable .......................................................................................... 12
2.3.2 Data format .................................................................................. 12
2.4 Communication parameters......................................................... 13
2.4.1 Communication parameters for DA1 variable frequency drives... 14
2.4.2 Communication parameters for DC1 variable frequency drives... 16
2.4.3 Communication parameters for DE1 variable speed starters ...... 17
2.5 Configuration of the control signal terminals ............................... 18
2.5.1 Control signal terminal configuration for DA1
variable frequency drives ............................................................. 20
2.5.2 Control signal terminal configuration for DC1
variable frequency drives ............................................................. 21
2.5.3 Control signal terminal configuration for DC1…E1
variable frequency drives ............................................................. 22
2.5.4 Control signal terminal configuration for DE1
variable speed starters ................................................................. 23
2.6 Operating mode Modbus RTU ..................................................... 25
2.6.1 Structure of the master request................................................... 26
2.6.2 Structure of the slave response ................................................... 27
2.6.3 Modbus: Register mapping.......................................................... 28
2.6.4 Input process data........................................................................ 29
2.6.5 Output process data..................................................................... 31
2.6.6 Explanation of function code........................................................ 40
3 Parameter ................................................................................... 43
3.1 Parameters for DA1 variable frequency drives............................. 43
3.2 Parameters for DC1 variable frequency drives............................. 52
3.3 Parameters for DC1…E1 variable speed starters ........................ 54
3.4 Parameters for DE1 variable speed starters ................................ 57
Alphabetical index ..................................................................... 59
2 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
0 About this manual
0.1 Target group
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 3
0 About this manual
0.1 Target group
This manual describes the Modbus RTU connection for DA1 and DC1
variable frequency drives and DE1 variable speed starters.
It is intended for experienced drive specialists and automation engineers and
technicians. It also assumes that readers are thoroughly familiar with the
Modbus RTU fieldbus and with how to program a Modbus master. Likewise,
it assumes that readers are familiar with how to operate DA1/DC1 variable
frequency drives and/or DE1 variable speed starters as applicable.
Please read this manual carefully before commissioning a Modbus RTU
connection.
We assume that you have a good knowledge of engineering fundamentals,
and that you are familiar with handling electrical systems and machines, as
well as with reading technical drawings.
0.2 List of revisions
The following significant amendments have been introduced since previous
issues:
Publication
date
Page Keyword new modified deleted
09/16 22 „Control signal terminal configuration for
DC1…E1 variable frequency drives
31 „Output process data“
54 „Parameters for DC1…E1 variable speed
starters“
01/16 Initial issue
0 About this manual
0.2 List of revisions
4 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
0.2.1 Writing conventions
Symbols used in this manual have the following meanings:
Indicates instructions to be followed.
0.2.2 Hazard warnings of material damages
0.2.3 Hazard warnings of personal injury
Indicates useful tips and
More Info
NOTICE
Warns about the possibility of material damage.
CAUTION
Warns of the possibility of hazardous situations that may
possibly cause slight injury.
DANGER
Warns of hazardous situations that result in serious injury or
death.
0 About this manual
0.2 List of revisions
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 5
DANGER – CONTROL FAILURE
When engineering your control diagram, make sure to take all
potential control path faults into account.
When it comes to critical control functions, make sure that a
safe state can be reached after a control path fails. –
Critical control function examples include:
Emergency shutdown (emergency stop),
Overtravel stop
Power supply failure
Restart.
Provide separate or redundant control paths.
Make sure that system control paths include communication
connections.
Take the effect of unforeseen transmission delays and
connection problems into account.
Carefully and individually test every implementation of a product
before putting it into operation.
Observe all general accident prevention and local safety
regulations.
Information for the USA:
For more information, please refer to the latest issue of
NEMA ICS 1.1, “Safety Guidelines for the Application, Installation,
and Maintenance of Solid State Control,” and the latest issue of
NEMA ICS 7.1, “Safety Standards for Construction and Guide for
Selection, Installation, and Operation of Adjustable-Speed Drive
Systems.”
In addition to property damage, failure to observe the
above instructions may result in serious bodily injury or
even death.
0 About this manual
0.2 List of revisions
6 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
For greater clarity, the name of the current chapter and the name of the
current section are shown in the page header.
To make it easier to understand some of the images included in
this manual, the housing and other safety-relevant parts have
been left out.
The components described here must be used only with a
properly fitted housing and all necessary safety-relevant parts.
Please follow the installation instructions in the relevant
instruction leaflets.
All the specifications in this manual refer to the hardware and
software versions documented in it.
More information on the devices described here can be found
on the Internet under: www.eaton.eu/powerxl
as well as: www.eaton.eu/documentation
1 Engineering
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 7
1 Engineering
The following diagram shows an example illustrating how to set up the
connection for a variable frequency drive (a DA1 in this specific case).
Figure 1: Engineering
a PC (with configuration tool)
b Head-end controller
c Variable frequency drive
d Motor
L
1
/
L
L2
/N
L
3
D
C-
U
DC+
BR
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
COM
V
W
1 Engineering
8 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
2 Modbus RTU
2.1 General
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 9
2 Modbus RTU
2.1 General
Modbus is a centrally polled bus system in which a so-called master (PLC)
controls the entire data transfer on the bus. Internode communication
between the individual modules (slaves) is not possible.
Every single data transfer operation is initiated by the master with a request.
Only one request can be sent on the cable at a time.
Slaves are not able to initiate transfers, and are only able to respond to
requests.
Two types of dialog are possible between master and slave:
The master sends a request to a slave and waits for a response.
The master sends a request to all slaves and does not wait for a
response (broadcast).
2.2 Communications
Figure 2: Modbus line with variable frequency drives/variable speed starters
a Splitter DX-SPL-RJ45… (T-plug connector)
b DX-CBL-RJ45… connection cable
c DX-SPL-RJ45… splitter with bus termination resistor
More information on Modbus can be found under
www.modbus.org.
L1/L
L2/N
L3
U
V
W
1
2
3
4
5
6
7
8
9
10
11
DC1
DE1 DA1
HMI-PLC
②②
RJ45
L1/L
L2/
N
L
3
U
V
W
0
V +
1
0
V
1
2
3
4
1
3
14
L1
/L
L2/N
L3
DC-
U
DC+
BR
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18
COM
V
W
RS485
Modbus RTU
2 Modbus RTU
2.2 Communications
10 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
Figure 2 shows a typical setup with a host computer (master) and any
number (a maximum of 63 nodes) of variable frequency drives (slaves).
Each variable frequency drive has a unique address on the network.
Addresses are assigned
to
each
variable frequency drive individually with the
use of a system parameter and are independent of the drive's physical
connection (position) within the network.
The aforementioned system parameter used to assign addresses is:
P5-01 for DA1 variable frequency drive,
P-36 for DC1 variable frequency drive,
P-34 for DE1 variable speed starter.
A DX-CBL-RJ45… connection cable with an RJ45 connector needs to be
used in order to establish communications between the master and slave
.
If multiple slaves are being used, they need to be connected in parallel using
DX-SPL-RJ45… splitters .
A bus termination resistor is required at the last module on the Modbus line
.
2 Modbus RTU
2.3 RJ 45 interface
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 11
2.3 RJ 45 interface
The master and slave communicate with each other via RJ45 cables.
If multiple slaves are being used, they need to be connected in parallel using
RJ45 cables and splitters.
The integrated RJ45 port (COM port) in DA1 and DC1 variable frequency
drives and DE1 variable speed starters supports the Modbus RTU protocol,
allowing for a direct network connection without the need for an additional
interface module.
A bus termination resistor with a resistance of 120 Ω needs to be connected
at each physical end (last node) of the network cable in order to prevent
signal reflection and the associated transmission errors.
EASY-NT-R resistors can be plugged into the corresponding splitter.
Figure 3: RJ45 socket wiring
PIN Significance
1 CAN-
Note:
Not used in DE1 variable speed starters (with the exception of DE11).
2 CAN+
Note:
Not used in DE1 variable speed starters (with the exception of DE11).
3 0 V
4 OP bus (operation bus) / External keypad / PC connection -
5 OP bus (operation bus) / External keypad / PC connection +
6 24 V DC power supply
7 RS485- Modbus RTU
8 RS485+ Modbus RTU
1
2
3
4
5
6
7
8
2 Modbus RTU
2.3 RJ 45 interface
12 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
2.3.1 Enable
DA1
The start signal is sent via the bus.
DC1
If using Modbus, there must always be a high signal at DI1.
Figure 4: Enable signal for bus mode in DC1 variable frequency drives
DE1
If using Modbus, there must always be a high signal at DI1.
Figure 5: Enable signal for bus mode in DE1 variable speed starters
2.3.2 Data format
DA1
When using DA1 variable frequency drives, the data format can be selected
using parameter P5-04.
The default setting is as follows:
No parity
1 start bit
1 stop bit
8 data bits
DC1, DE1
The data format is fixed for DC1 variable frequency drives and DE1 variable
speed starters and cannot be changed.
No parity
1 start bit
1 stop bit
8 data bits
DI1
2
FWD
+24 V
1
1
+10 V
DI1
1
+10 V
DI1
1
+24 V
DI1
0 V
2 Modbus RTU
2.4 Communication parameters
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 13
2.4 Communication parameters
The following tables list the communication parameters (sent to the PLC) for
DA1 and DC1 variable frequency drives and DE1 variable speed starters.
Abbreviation Significance
ID The parameter's identification number in Modbus (identification number)
RUN The parameter can be accessed during operation (Run signal)
ro/rw
Parameter read and write permissions:
ro = read only
rw = read and write
DS
Default setting (the parameter's value when using the device's factory settings)
2 Modbus RTU
2.4 Communication parameters
14 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
2.4.1 Communication parameters for DA1 variable frequency drives
Table 1: Communication parameters for DA1
Display
ID Access right Designation Value
range
Description DS
RUN ro/rw
P1-12 rw Control level 0, …, 6,
9, 10, 11,
13
Local Configuration of Command and Reference
Sources
Possible values:
0: Terminal Control. The drive responds directly to
signals applied to the control terminals.
1: Uni-directional digital reference. The drive can
be controlled in the forward direction only using a
digital reference (via internal or remote Keypad or
terminals)
2: Bi-directional digital reference. The drive can be
controlled in the forward and reverse directions
using a digital reference (via internal or remote
Keypad or terminals). Pressing the keypad START
button toggles between forward and reverse.
3: PID controller. The output frequency will be
controlled by the internal PID controller
4: Fieldbus Control. Control via Modbus RTU if no
fieldbus option is present, otherwise control from
the fieldbus option module
5: Slave Mode. The Variable Frequency Drive acts
as a slave to a connected drive operating in Master
Mode.
6: CANopen Control. Control via the CANopen bus
connected to the RJ45 serial interface connector.
7: Reserved
8: Reserved
9: SmartWire Device Control and speed ref.
10: SmartWire Device Control and terminal speed
ref.
11: Terminal Control and SmartWire Device speed
ref.
12: not permissible
13: SmartWire Device Control and speed ref.
Digital input sets enable.
0
P5-01
501 rw Variable frequency drive
slave address
0 - 63 The drive‘s unique address on a communication
network
1
P5-03
503 rw Modbus RTU Baud rate 0, 1, …, 4 RS485 Baudrate
Possible values:
0: 9.6 kBit/s
1: 19.2 kBit/s
2: 38.4 kBit/s
3: 57.6 kBit/s
4: 115.2 kBit/s
4
P5-04
504 rw Modbus RTU data
format – Parity type
0, 1, 2, 3 RS485 0 Parity Type
Possible values:
0: No parity, 1 stop bit (N-1)
1: No parity, 2 stop bits (N-2)
2: Odd parity, 1 stop bit (0-1)
3: Even parity, 1 stop bit (E-1)
n-1
2 Modbus RTU
2.4 Communication parameters
Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com 15
P5-05 505 rw Timeout –
Communications
dropout
Timeout
With an active communication link, if a valid telegram
is not received by the drive within the period set with
this parameter, the drive will react as set in P5-06.
2
P5-06
506 rw Response in the event of
a communications
dropout
0, 1, 2, 3 Modbus communication loss error
Possible values:
0: Switch off
1: Ramps down to a full stop and is switched off.
2: Ramps down to a full stop; no fault message.
3: Ramps to fixed frequency 8 (P2-08).
0
P5-07
507 rw Ramp via fieldbus 0, 1 Fieldbus Ramp Control
Possible values:
0: OFF. Ramps are controlled from internal drives
parameters
1: ON. Ramps are controlled by the fieldbus.
0
Display
ID Access right Designation Value
range
Description DS
RUN ro/rw
2 Modbus RTU
2.4 Communication parameters
16 Modbus RTU for variable frequency drive DA1, DC1, DE1 09/16 MN040018EN www.eaton.com
2.4.2 Communication parameters for DC1 variable frequency drives
Table 2: Communication parameters for DC1
PNU
ID Access right Designation Value
range
Description DS
RUN ro/rw
P-12 140 rw Local Process Data
Source
0, 1, …, 11,
13
Local Configuration of Command and Reference Sources
Possible values:
0: Terminal Control. The drive responds directly to
signals applied to the control terminals.
1: Uni-directional Keypad Control. The drive can be
controlled in the forward direction only using an internal/
external or remote Keypad
2: Bi-directional Keypad Control. The drive can be
controlled in the forward and reverse directions using an
internal/external or remote Keypad. Pressing the keypad
START button toggles between forward and reverse.
3: Modbus Control.Control via Modbus RTU
communication.
4: Modbus Control. Ramp times via Modbus
5: PI controller with external actual value
6: PI controller with external actual value and totalized
value of AI1
7: CANOpen (internal ramp times)
8: CANOpen (CANOpen ramp times)
9: SmartWire Device Control and speed ref.
10: SmartWire Device Control and terminal speed ref.
11: Terminal Control and SmartWire Device speed ref.
12: not permissible
13: SmartWire Device Control and speed ref. Digital
input sets enable
0
P-36
164 rw variable frequency
drive slave address
1 - 63 Unique drive address in a communication network. 1
rw Baud Rate 2, 3, 4, 5, 6 RS485 Baudrate
•2: 9.6 kbit/s
3: 19.2 kbit/s
4: 38.4 kbit/s
5: 57.6 kbit/s
6: 115.2 kbit/s
2
rw Time Out 0, 1, …, 8 Modbus RTU0 COM Timeout
Time between a communication loss and the resulting
action.
Setting 0 disables the action after communications trip.
t: indicates the drive will trip if time exceeded.
r: indicates the drive will ramp to stop if time exceeded.
Possible values:
0: no action
1: t 30 ms
2: t 100 ms
3: t 1000 ms
4: t 3000 ms
5: r 30 ms
6: r 100 ms
7: r 1000 ms
8: r 3000 ms
3000
ms
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63

Eaton PowerXL™ Modbus RTU Communication Owner's manual

Type
Owner's manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI