Siemens AE-30U Operation And Installation Instructions

Type
Operation And Installation Instructions
P/N 315-085099-16
Operation and Installation Instructions
Model AE-30U
Alarm Extender Module
Fire Safety
Operation
The SIEMENS Model AE-30U Alarm Extender
Module is designed to provide one Style Y (Class
B) super-vised notification appliance circuit,
utilizing polarized, parallel connected notification
appliances.
Actuation of the module is caused by
high-going DC input signal between 12 and 24 volts
above system common. Dual input activation termi-
nals are provided to facilitate programming.
The Model AE-30U contains a yellow LED trouble
indicator to display open or shorted alarm lines
except when that particular module is not in an
activated condition.
The yellow LED can be lamp tested from the
system control panel.
Installation
1. Mount the module to the horizontal mounting
brackets in the control enclosure.
2. Install the Model JA-5 (5 in. long) bus connector
cable assembly between receptacle P2 of the
module and receptacle P1 of the module or
control panel immediately preceding it in the
bus.
Note: If the preceding module is on another
row in the enclosure, a JA-24 (24 in.
long) bus connector cable assembly will
be required.
3. Modules are to be bus-connected from right to
left. For two-row enclosures, the modules in the
lower row are to be connected from left to right.
Succeeding rows are to be alternately con-
nected, right to left, left to right, etc.
4. If a module is the last module in the system,
install either a JS-30 (30 in. long) or JS-64
(64 in. long) bus connector assembly from the
unused receptacle of the last module to
terminal 41 of the CP-35 control panel. This
completes the module supervision circuit.
5. If a DC notification appliance circuit is to be
used, install a JP-D program plug into
receptacle P2 of the CP-35 control panel.
Note: If a battery charger/transfer module is
used, the program plug is not
necessary.
If an AC notification appliance circuit is to
be used, install a JP-A program plug into
receptacle P2 of the control panel.
Note: When a JP-A program plug is used, an
EL-32 end of line device is required for
the notification appliance circuit.
6. Wire the circuits as described in the MODEL
CP-35 CONTROL PANEL INSTALLATION
AND MAINTENANCE INSTRUCTIONS, P/N
315-085063 and the CP-35 WIRING DIAGRAM,
P/N 315-084902. The maximum line resistance
should be 3 ohms, and a minimum of 14 AWG
wire is recommended. All wiring should comply
with the local and national codes that apply to
the particular installation.
Operational Test
Refer to INSTALLATION AND WIRING in the
Instruction Manual (P/N 315-085063) for the
control panel.
Troubleshooting
Refer to TROUBLESHOOTING THE CP-35 in the
Instruction Manual for the control panel.
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
P/N 315-085099-16
NOTES:
1. When emergency power is provided using
charger/ transfer module, Model BC-35, 24 VDC
notification appliances must be used with EOL
device, Model EL-31. When BC-35 is not used,
120 VAC notification appliances may be
employed by use of AC program plug, Model
JP-A, in P2 of CP-35 and Model EL-32 EOL
device, or by use of 24 VDC notification
appliances with DC program plug, Model
JP-D, in P2 and Model EL-31 EOL device.
2. Notification appliance circuits may be
activated from the silenceable system alarm
output signal, terminal 36 of CP-35, or from the
non-silenceable system alarm output signal,
terminal 42 of CP-35. When other alarm signals
such as coding or time delay/limit are required,
see individual module connection diagrams.
3. Use only the compatible polarized notification
appliances listed in P/N 315-096363.
4. To use power limited wiring to NFPA 70, NEC
Article 760, the notification appliance circuits
(terminals 3 and 4) must use the PLM-35
module. Refer to Instructions P/N 315-093495.
NOTE:
Refer to the BI-35 Installation
Instructions, P/N 315-086257,
for detailed wiring information
when using the AE-30U in
conjunction with the BI-35
module.
ACTUATION
INPUT
POLARIZED NOTIFICATION
APPLIANCES (SEE NOTE 3)
END OF LINE DEVICE
(SEE NOTE 1)
CP-35
(SEE NOTE 2)
3 OHMS MAX TOTAL LINE
RESISTANCE OF NOTIFICATION
APPLIANCE CIRCUIT
CONNECTING WIRES
INPUT POWER
(SEE NOTE 1)
CP-35
STYLE Y (CLASS B)
CONNECTED
POLARIZED
NOTIFICATION
APPLIANCES
POLARITY SHOWN IN
SUPERVISORY CONDITION:
SUPV 24 VDC, 5mA
ALARM 24 VDC or 120 VAC,
1.5A MAX
  • Page 1 1
  • Page 2 2

Siemens AE-30U Operation And Installation Instructions

Type
Operation And Installation Instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI