12
Accessory Kits Description Suggested and Required Use
1. Disconnect Kit
The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.
SUGGESTED USE: FC4, FB4, and FA4 units for 3kw through 10kw electric resistance heaters and cooling controls.
2. Downflow Base Kit
This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap free
seal with the floor.
REQUIRED USE: This kit must be used whenever FC4, FB4, and FA4 fan coils are used in downflow applications.
3. Downflow Conversion Kit
Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water drainage and
support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils.
REQUIRED USE: This kit must be used whenever FC4, FB4, and FA4 fan coils are used in downflow applications.
4. Single Point Wiring Kit
The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run 2 heavy-gage, high-
voltage wires into the fan coil rather than 4 light-gage, high-voltage wires.
SUGGESTED USE: FC4, FB4, and FA4 fan coils only with 15kw and 20kw heaters.
5. Fan Coil Filter
The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevents them from collecting
on the coil. This process helps to keep the coil clean, which increases heat transfer and in turn the efficiency of the system.
SUGGESTED USE: To replace filters in FC4, FB4, and FA4 fan coils.
REQUIRED USE: All FA4A units unless a filter grille is used.
6. Power Plug Kit
The kit consists of 25 wire harness assemblies. Each plug provides the high-voltage power connection to the fan coil in the absence of electric heat.
REQUIRED USE: FA4A units installed without electric heat.
FACTORY INSTALLED HEATER OPTIONS
Accessory electric heaters
Smart heat
* Field convertible to 1 phase.
† Field convertible to 3 phase.
‡ Approved for Canadian application.
** Blower motor heat not included.
When using units with 20-, 24-, and 30-kw electric heaters, maintain a 1-in. clearance from combustible materials to discharge plenum and ductwork
and maintain a distance of 36 in. from the unit. Use an accessory downflow base to maintain proper clearance on downflow installations.
Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat resistant material
for flexible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and
covered with vapor barrier.
MODEL 018 024 030 036 042 048 060
FA4ANF 5, 8, 10 5, 8, 10 5, 8, 10, 15 5, 8, 10, 15 8, 10, 15 8, 10, 15 10
FA4ANC 5, 8, 10 5, 8, 10 5, 8, 10 5, 8, 10 8, 10 8, 10 10
FB4ANF 5, 8, 10 5, 8, 10 5, 8, 10, 15 5, 8, 10, 15 8, 10, 15 8, 10, 15 10
HEATER
PART NO.
KW
@ 240V VOLTS/PH KW/STAGE
INTERNAL
CIRCUIT
PROTECTION
FAN COIL SIZE
USED WITH
HEATING CAP.**
@ 230V
KFAEH0101N03 3 230/1 3 None‡ 018–024 9,400
KFAEH0201N05 5 230/1 5 None‡ 018–060 15,700
KFAEH0301N08 8 230/1 8 None‡ 018–070 25,100
KFAEH0401N10 10 230/1 10 None‡ 018–070 31,400
KFAEH0601F20 20 230/1 10, 10 Fuse 030–070 62,800
KFAEH0801315 15 230/3 5, 10 None‡ 036–070 47,100
KFAEH0901318 18 230/3 6, 6, 6 None‡ 042–070 56,500
KFAEH1001F24 24 230/3* 8, 8, 8 Fuse 048, 060, 070 78,300
KFAEH1101F30 30 230/3* 10, 10, 10 Fuse 048, 060, 070 94,100
KFAEH1301C05 5 230/1 5 Circuit Breaker‡ 018–060 15,700
KFAEH1401C08 8 230/1 8 Circuit Breaker‡ 018–038 25,100
KFAEH1501C10 10 230/1 10 Circuit Breaker‡ 018–070 31,400
KFAEH1701C20 20 230/1 10, 10 Circuit Breaker‡ 030–070 62,800
KFAEH1901S20 20 230/1 10, 10 Fuse‡ 030–070 62,800
KFAEH2501N09 9 230/1† 3, 6 None‡ 030–070 28,200
KFAEH2601F15 15 230/1 5, 10 Fuse 024–070 47,100
KFAEH2701S15 15 230/1 5, 10 Fuse‡ 024–070 47,100
KFAEH2801C15 15 230/1 5, 10 Circuit Braker‡ 024–070 47,100
HEATER
PART NO.
KW
@ 240V VOLTS/PH KW/STAGE
INTERNAL
CIRCUIT
PROTECTION
FAN COIL SIZE
USED WITH
HEATING CAP.**
@ 230V
KFAEH2201H10 10 230/1 4, 6 None‡ 018–036 31,400
KFAEH2301H15 15 230/1 3, 8, 4 Fuse 024–048 47,100
KFAEH2401H20 20 230/1 5, 10, 5 Fuse 030–070 62,800