Parameter
Parameter
FunctionFunction
Setrange
SetrangeDefault
Default
~
Settemp.
Settemp.
~
E1
Lowersetpointlimit
F4
00=Parallelwithcomp.
(Stopwhendefrost)
01=Continuousrunning
(Stopwhendefrost)
02=Parallelwithcomp.
(Startwhendefrost)
03=Continuousrunning
(Startwhendefrost)
Evap.Fanstarting
mode
0160Min
~
0024Hr
~
20Min
4Hr
F1
F2
F3
0010Min
~
03Min
E2
E3
E4
E5
E6
Highersetpointlimit
Temp.hysteresis
Comp.Startdelaytime
Offsetonroomtemp.
OffsetonEvap.Temp.
Max.Defrostduration
Defrostintervaltime
01
F5
113
45℃
℉
75
24℃
℉
-49
-45℃
℉
23
-5℃
℉
02~
18
01~
10℃
℉
05
03℃
℉
-18
~18
-10~
10℃
℉
-18
~18
-10~
10℃
℉
54
12℃
℉
32~113
00~45℃
℉
01
Defrostterminationtemp.
Displayduringdefrost
00=Nomaldisplay
01=Lastvaluebefore
defrost
00
00℃
℉
00
00℃
℉
~
H1.
H2
~
H1
Hightemp.Alarmvalue
H2
H3
Alarmdelaytime
113
45℃
℉
86℉
30℃
-40/℃℉
5
-15℃
℉
Lowtemp.Alarmvalue
00120Min
~
30Min
00=Nomaldisplay
01=Lockingslowly
display
01
01
A1
A2
Cold-roomtemp.
Displaymode
Doorswitchcontrol
00=thereisnot
01=thereis
A3
00=settemp.Adjustable
01=settemp.Canbe
checkedonly,unadjustable
Settemp.Adjustment
mode
00
Functiondetail
1.Temperaturecontrol
(Whenfirsttimepoweron,pressbuttonforoncecancanceldelayandenterautomaticcontrolmode)
Thecompressorstartsoperatingwhencoldroomtemperature(settemperature+hysteresis),andwill
beoffwhencoldroomtemperaturesettemperature.
Toprotectthecompressor,itcanre-startunlessthetimewhenthecompressorstopseverytimeislonger
thanthedelaytime(ParameterE4).
2.Defrostfunction
Afterworkingadefrostintervalwillautomaticenterthedefroststatus.ThedefrostLEDison,the
compressorstops.Afterdefrostduration,willexitdefroststatus,after2minutesdrippingtime,ifthe
cold-roomtemperatureishigherthan(settemp.+TemperaturehysteresisE3),thecompressorstarts.
Whendefrostintervalissetto00,theautomaticdefrostfunctionwillbecancelled.
3.Temperaturedisplay
WhenparameterA1=01,thetemperaturewilldisplayslowly:withthespeedofonedegreeevery30
secondstoreachtheactualtemperature,anddonotaffectthecompressorworkingnormally.
Whenstartedup,andaftertheactualtemperaturereachthesettemperatureforonce,onlyifthecold
roomtemperatureiswithintherangeof(settemp.+parameterE3+1),willdisplaythesettemperature,
otherwisethetemperaturewilldisplayinlowspeed.
4.Displayduringdefrost
WhensettingparameterF4=0,thecoldroomtemperaturewilldisplaynormally.
WhensettingparameterF4=1,theroomtemp.islockedduringdefrost,andthelastvaluebefore
defrostisdisplayed.Whendefrostends,normaldisplaywillberesumedafter20minutesdelayofroom
temp.Display.If(parameterA1=01),thecold-roomtemperaturewilldisplayslowly,thedefrostLED
flashesduringthelockingdelayprocess.
5.Fancontrol
WhenparameterF5=01,theEvap.Fanpoweronandkeepworking.(Stopwhendefrost)
Thecondenserfanworksynchronizedwiththecompressor.
6.Doorswitchcontrol
WhenparameterA2=01,whendetectthedoorisopen,theEvap.Fanstops,thelightison,atthistime,
when(parameterA1=01),willlockthecold-roomtemperaturedisplay;ifthedoorisnotclosedformore
thanoneminute,thebuzzersound,pressrandombuttontocancelthesound;ifthedoorisnotclosed
formorethan10minutes,thelightwillturnoffautomatically;untilthedoorisclosedfor5minutes,
thenthetemperaturewilldisplayinlowspeed.(Doorswitchlineopen-circuited=doorclosestatus;
doorswitchlineshort-circuited=dooropenstatus.)
7.Highlowtemperatureoverlimitalarm
Afterthecompressorturningonandoffnormallyforonce,canenterthealarmstatus.
Whencold-roomtemperatureishigherthanH1parametersetvalue,andpassalarmdelaytime(parameterH3),
willflashanddisplaythecold-roomtemperatureandexitthedefroststatus.Whenthecoldroomtemperature
islowerthanH2parametersetvalue,andpassthealarmdelaytime(parameterH3),willflashanddisplay
thecold-roomtemperature,thebuzzersound,pressrandombuttontocancelthesound.
≥
≤