Sabroe Enclosure Operating instructions

Type
Operating instructions
Sabroe enclosure
for ChillPAC, HeatPAC and ChillPAC LP
Installation and operation manual EN
Installation and operation manual
0013321 en 2021.11 3/14
Contents
1. Introduction ..........................................................................................4
2. Transport...............................................................................................5
2.1 Transport ....................................................................................5
2.2 Lifting the enclosure .....................................................................5
2.3 Fixing the enclosure during transport .............................................6
2.4 Enclosed trailer............................................................................6
2.5 Enclosure preparations ................................................................6
3. Installation on site .................................................................................7
3.1 Lifting brackets ...........................................................................7
3.2 Safety relief system .....................................................................7
3.3 Electrical connection ....................................................................8
3.4 Settings for heating panels ...........................................................8
4. Service of the plant and enclosure ........................................................9
4.1 Safety .........................................................................................9
4.2 Access for service...................................................................... 10
4.3 Sensors .................................................................................... 11
4.4 Ventilation ................................................................................. 12
4.5 Oil trap for protection of safety valves .......................................... 12
4.6 Siren and alarm ......................................................................... 13
4.7 Access for major repairs or service.............................................. 13
5. Appendix............................................................................................. 14
Installation and operation manual
4/14 0013321 en 2021.11
Introduction
1. Introduction
This manual contains guidelines for transport, installation and service of the Sabroe enclosure
and instructions on how to ensure access to the equipment inside the enclosure.
Installation and operation manual
0013321 en 2021.11 5/14
Transport
2. Transport
2.1 Transport
The enclosure is top heavy. See the centre of gravity location on the specific GA drawings.
2.2 Lifting the enclosure
A crane, which can lift the stated weight of the enclosure, is required. Further, a lifting yoke
must be used to make sure the panel plates are not damaged when lifted, see Fig. 1
Fig. 1
Installation and operation manual
6/14 0013321 en 2021.11
Transport
2.3 Fixing the enclosure during transport
Place the enclosure on straws and fasten it by lashing straps to prevent it from tipping during
transport, see Fig. 2.
Fig. 2
2.4 Enclosed trailer
If there is a risk of salt from the road or somewhere else, the enclosure must be transported in
an enclosed trailer.
2.5 Enclosure preparations
The door panels must be stabilised during transport. By inserting blocks underneath the doors
as shown in Fig. 3 and Fig. 4, the hinges are protected from damage.
The threaded plunger from the safety relief system should be closed with tape or a plug during
transport, see Fig. 5
Fig. 3 Fig. 4 Fig. 5
Truck
Installation and operation manual
0013321 en 2021.11 7/14
Installation on site
3. Installation on site
3.1 Lifting brackets
When the enclosure is placed on site, the lifting bracket should be disassembled and stored, if
needed. See Fig. 6.
Fig. 6
3.2 Safety relief system
Remove the plug or tape to assemble the rest of the safety relief system with the included pipe
fittings. The opening should point down, see Fig. 7 and Fig. 8.
Fig. 7 Fig. 8
Installation and operation manual
8/14 0013321 en 2021.11
Installation on site
3.3 Electrical connection
The enclosure is supplied with a reinforced panel for cable lead-in. The exact location of the re-
inforced panel is shown in the GA drawing, see also Fig. 9. The panel section is reinforced with
a glued double outer plate to mount cable glands for cable entry. The construction of the rein-
forced panel is illustrated in Fig. 10.
Fig. 9 Fig. 10
3.4 Settings for heating panels
The heating panel secures against frost. The turn-on temperature should be set at 5°C and the
turn-off temperature at 15°C.
To install the thermostat, follow instructions in ”Nobø NCU-2Te” manual, see Fig. 11.
Fig. 11
Reinforced plate
for cable glands
Inside:
Perforated plate
In the middle:
Insulation
Outside:
2 x alu-zink plate
Installation and operation manual
0013321 en 2021.11 9/14
Service of the plant and enclosure
4. Service of the plant and enclosure
4.1 Safety
Safety box
The enclosure is classified as a machinery room. As the room is not part of a building, some re-
quirements can be waived. There is light inside and an emergency exit light above the doors.
Manual control of the fans, main switch and emergency stop is possible from the front of the
safety box. It has indicators for Fan running, Gas detector (low and high alarm) and Tempera-
ture from inside probe.
Fig. 12
For more specific information, please see the electrical drawings in the appendix.
Installation and operation manual
10/14 0013321 en 2021.11
Service of the plant and enclosure
4.2 Access for service
Fig. 13 - Fig. 16 show the access options for a specific “6 high” version enclosure. The number
of sections and the positioning of doors may vary depending on the plant inside. However, in
general, access will be possible as shown in Fig. 13 - Fig. 16 through the doors or demount-
able panels.
A: Panel access C: End panel access
B: Door access D: End door access
Fig. 13 Fig. 14
Fig. 15 Fig. 16
Opening the doors
The doors provide the main access. They are locked in the top, middle and at the bottom. Use
the supplied square key to unlock the three latches, see Fig. 17.
Fig. 18 shows how the open door provides access to part of the compressor and the WHC
system.
AA
A
A
A
B
B B
A
C
A
B B B
D
Installation and operation manual
0013321 en 2021.11 11/14
Service of the plant and enclosure
Fig. 17 Fig. 18
Access through the panels
For extra service access, the panels can be disassembled by loosening the pan head screws,
see Fig. 19.
Fig. 19: Loosen the pan head screws and remove the panels. Press your hand against the panel when loosening the last screws
to make sure it does not tip over on you.
4.3 Sensors
Two sensors are mounted at the top of the enclosure: one for ammonia and one for ventilation.
Fig. 20 Fig. 21
Fig. 20 shows the ammonia detector, which activates the ventilation system at certain quanti-
ties (350 mg/m3starts a prealarm) and turns off the plant at other quantities (21,200 mg/m3
starts the main alarm).
Fig. 21 shows a temperature sensor, which starts the ventilation system at 35°C.
Installation and operation manual
12/14 0013321 en 2021.11
Service of the plant and enclosure
4.4 Ventilation
Check regularly that the ventilation filter is not clogged with dirt. The filter is accessible from
the inside of the door panel, see Fig. 22 and Fig. 23.
Fig. 22 Fig. 23
4.5 Oil trap for protection of safety valves
Check regularly that the oil trap has oil. The green ball should float in the sight glass, Fig. 24.
The oil trap prevents moisture from getting into the safety valve and cause jamming. If the oil
trap is empty, check if there has been a pressure relief from the vessels. If necessary, there is
a nipple for charging and one for draining oil, see Fig. 24.
Fig. 24
Installation and operation manual
0013321 en 2021.11 13/14
Service of the plant and enclosure
4.6 Siren and alarm
Do NOT open the door, if the siren and alarm are on.
If the siren and alarm are on, gas has been detected. The detection will also activate the venti-
lation system to let fresh air into the enclosure and ensure that the gas concentration cannot
cause explosion hazard.
When a leak is identified, it must be determined whether it is so severe that it requires full
emergency procedures, or if it can be contained by trained personnel on site.
The siren and alarm are placed on the outside of the enclosure over the double door in the end
or over the control box at the front.
Fig. 25
4.7 Access for major repairs or service
If major repair is required, the entire front can be demounted. Pay attention to disassembly of
panels with pipe penetration as they will require new insulation and covering at the pipes. Also
be aware of the three-part panel section with the control box, which is not optimal to disassem-
ble because of wires etc.
Fig. 26
Installation and operation manual
14/14 0013321 en 2021.11
Appendix
5. Appendix
Please find electrical drawings for the Sabroe enclosure in the following pages.
Johnson Controls Denmark ApS
Sabroe Factory
Christian X's Vej 201 ∙ 8270 Højbjerg
Denmark
Phone +45 87 36 70 00
www.sabroe.com
Version 2
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16