General Settings
NOTE: These settings are for trained installers only.
To enter the Setting mode, press and hold button 13 for 3
seconds. In this mode, buttons 11 and 12 proceed up and
down through the following table. Pressing 13 a second time
allows the selected item to be set with 11 and 12.
To exit a selected item, press 13 again. To exit the Setting
mode, press the ESC button 8.
The Setting mode is displayed in items 14, 15, and 16. 14
displays the numbered program item. 16 (and sometimes 15)
displays the selection. The Item column below also shows the
default setting.
Wiring
Settings
900-0247-01-00 REV B
©2019 OutBack Power. All Rights Reserved.
14
15
16
Item
1 8
bOF
1 9
ESP
20
LON
22
AON
23
byd
25
FEN
26
Cv
28.2
56.4
27
FLv
27.0
54.0
29
COv
21.0
42.0
Description
Alarm control. Selections: bOF (alarm off), bON (alarm on). Turns
audible alarm on or off. See item 23 on the opposite side of this sheet.
Return to default display. Selections: ESP (auto return), rEP (remain).
Sets the screen to return to the default display after 1 minute if no
button is pressed, or to remain on the current screen.
Backlight control. Selections: LON (Light on), LOF (Light off).
Turns the display backlight on or off.
Unit beeps when primary source (according to item 0 1) is interrupted.
Selections: AON (Alarm on), AOF (Alarm off).
Overload bypass. Selections: byd (Bypass disabled), byE (Bypass
enabled). If overload shutdown occurs while using batteries, unit
switches to the AC source. (Used only when item 0 1 is set to SbU.)
Record error codes. Selections: FEN (Recording ena
bled), FdS
(Recording disabled).
Bulk charging voltage. The setting for the main stages of constant-
voltage (CV) charging. This is settable when item 05 is set to USE.
Selection range (model ATL3024E): 25.0 to 31.5 Vdc
Selection range (model ATL5048E): 48.0 to 61.0 Vdc
Float charging voltage. The setting for the float stage of charging.
This is settable when item 05 is set to USE.
Selection range (model ATL3024E): 25.0 to 31.5 Vdc
Selection range (model ATL5048E): 48.0 to 61.0 Vdc
Low batte
ry cut-out voltage. The battery setting which shuts down
the inverter (or transfers to the AC source). This is settable when
item 05 is set to USE.
Selection range (model ATL3024E): 25.0 to 31.5 Vdc
Selection range (model ATL5048E): 48.0 to 61.0 Vdc
It
em
05
AGn
06
Lrd
07
trd
09
50
1 0
230
1 1
30
1 2
23.
0
46.0
1 3
27.0
54.0
1 6
SNU
Description
Battery type. Selections: AGn (AGM), FLd (flooded),
USE (user-defined).
If USE is selected, battery charging and low battery
cut-out voltages can be set in items 26, 27, and 29.
A
uto restart when overload shutdown occurs.
Selections: Disable (Lrd) or Enable (lre).
Auto restart when over-temperature shutdown occurs.
Selections: Disable (trd) or Enable (tre).
Output frequency. Selections: 50 Hz or 60 Hz.
Chooses the inverter’s AC output frequency.
Output voltage. Selections: 220 Vac, 230 Vac, or
240 Vac. Chooses the inverter’s AC output voltage.
Maximum AC charge current. Selection range:
2 to 60 Adc.
If item 02 is less than item 1 1, the 02 setting will be used.
AC transfer voltage (if item 0 1 is set to SbU).
Selections (model ATL3024E): 22.0 Vdc to 25.5 Vdc
Selections (model ATL5048E): 44.0 Vdc to 51.0 Vdc
Battery transfer voltage (after using AC in item 1 2).
Selections (model ATL3024E): FUL (full) to 29.0 Vdc
Selections (model ATL5048E): FUL (full) to 58.0 Vdc
Charger source priority. Selections: CSO, SNU, OSO.
CSO (charge solar) uses PV as first priority. The AC source
is used only if PV is not available.
SNU (solar and AC) charges with both sources (as available).
OSO (only solar) charges only with PV.
Item
30
EEN
31
Ev
29.2
58
.4
33
60
34
120
35
30d
36
AdS
37
Nrt
93
Nrt
94
10
Description
Equalization function. Selections: EEN (Equalize
enabled), EdS (Equalize disabled).
Allows equalization to take place automatically. This is
settable when item 05 is set to either FLd or USE.
Equalization charging voltage. The setting for
equalization once enabled in item 30 or item 36.
Selection range (model ATL3024E): 25.0 to 31.5 Vdc
Selection range (model ATL5048E): 48.0 to 61.0 Vdc
E
qualization time. This timer begins running once
item 31 is reached. Selection range: 5 to 900 minutes.
Equalization timeout. The maximum time permitted for
equalization. Selection range: 5 to 900 minutes.
Equalization interval. The days between automatic
equalization cycles. Selection range: 0 to 90 days.
Immediate equalization. The main display reads Eq.
S
elections: AEN (Enabled), AdS (Disabled).
This is usable when 30 is set to EEN.
If AdS is selected, it will cancel equalization until the
next automatic cycle based on item 35.
Reset PV accumulation kWh data.
Selections: Nrt (Not reset), rSt (Reset).
Erase data log (all accumulated data).
Selections: Nrt (Not reset), rSt (Reset).
Data log storage period (the time period for recording
a block of data). Selection range: 3 to 60 days.
95 (nIN), 96 (HOU), 97 (dAY), 98 (nON), and 99 (yEA):
Time and date in minutes, hours, days, months, and years.
The range of the year setting is 17 to 99 (2017 to 2099).
Function Settings
USB OTG Functions
These include the ability to upgrade firmware, export data logs, and import new internal settings.
These functions are normally used only by installers. See the Alino product manual for more information.
Output Source Priority timer
This allows the inverter to switch between USb, SUb, and SbU using a timer. (See 0 1 above.)
To enter this function, press and hold button 9 for 3 seconds. Use button 8 to change USb settings.
Use button 9 to change SUb settings. Use button 10 to change SbU settings. In each case, adjust the
time settings with buttons 11 and 12 (between 0 and 23 hours). Confirm the settings with button 13.
Charger Source Priority timer
This allows the charger to switch between CSO, SNU, and OSO using a timer. (See 1 6 above.)
To enter this function, press and hold button 10 for 3 seconds.
Use button 8 to change CSO settings. Use button 9 to change SNU settings. Use button 10
to change OSO settings. In each case, adjust the time settings with buttons 11 and 12 (between
0 and 23 hours). Confirm the settings with button 13.
Errors and Warnings (with red LED indicator)
Item
00
ESC
0 1
USb
02
60
03
APL
Description
Exit the Setting mode.
Power source priority for loads. Selections: USb, SUb, SbU.
USb ([unspecified] AC source, PV [solar], battery): AC power is used first.
PV and battery provide power only when the AC source is not available.
SUb (solar, AC, battery): PV (solar) power is used first. If it is not
enough, the AC source assists PV. Batteries will be used if neither PV
nor AC is available.
SbU: PV (solar) power is used first. If it is not enough, battery power
assists PV. The AC source is only used if the battery drops to the voltage
setting in item 1 2.
Maximum charging current (total for PV + AC sources). Selections:
10 to 80 Adc.
Acceptable AC input voltage range.
Selections: 90 to 280 Vac (APL) or 170 to 280 Vac (UPS).
Error Codes
These codes may accompany unit failure.
If the audible alarm is enabled, it will sound.
Code Description
F0
1 Both of the unit’s fans have failed.
F02 Temperature is too high. (See item 07.)
F03 Battery voltage is too high.
F04 Battery voltage is too low.
F05 Output is short-circuited, or
internal over-temperature is detected.
F06 Output AC voltage is too high.
F07 Overloaded output (timeout has expired)
or overloaded PV input. (See item 06.)
F08 Internal bus voltage is too high.
F09 Internal bus soft start failed.
F5
1 Overloaded output.
F52 Internal bus voltage is too low.
P53 Incorrect voltage is present at AC output.
F55 Unbalanced AC output.
F57 Current sensor failed.
F58 Output AC voltage is too low.
F59 PV input voltage is too high.
Warning Codes
These codes may appear if the unit is
continuing to operate with a fault present.
If the audible alarm is enabled, it will
beep as noted.
Code Beep Description
0 1
⚠
3/sec One of the unit’s fans has
failed.
02
⚠
None Temperature is too high.
03
⚠
1/sec Battery voltage is too high.
04
⚠
1/sec Battery voltage is too low.
07
⚠
½ sec Overloaded output (timeout
is in progress).
1 0
⚠
⅔ sec Output power has been
derated due to conditions.
1 5
⚠
⅔ sec PV energy is low.
1 6
⚠
None High AC input voltage
(<280 Vac).
32
⚠
None Internal communications
interrupted.
Eq
⚠
None Battery equalization is
occurring.
bP
⚠
None Battery is not connected.
9
11
12
8
1310