  • Hello! I am an AI chatbot trained to assist you with the ABB ACS550 Series Quick start guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐2‐ PLCanddrivesintegration
Contents
Introduction...................................................................................................................................................................4
Safetyinstructions .........................................................................................................................................................4
Limitations .....................................................................................................................................................................4
Fieldbusgrounding ....................................................................................................................................................6
Fieldbusshield ...........................................................................................................................................................6
Endtermination.........................................................................................................................................................6
Pullup/pulldownresistors........................................................................................................................................6
Driveswithembeddedfieldbus.................................................................................................................................7
FieldbusmodulesforABBdrives...............................................................................................................................8
Commonrecommendations......................................................................................................................................8
ABBcableTK505........................................................................................................................................................9
AC500COM1Masteratthebuslineend .........................................................................................................11
AC500COM2Masteratthebuslineend .........................................................................................................11
AC500eCoCOM1Masteratthebuslineend..................................................................................................11
AC500eCoCOM2Masteratthebuslineend..................................................................................................12
Driveconfiguration......................................................................................................................................................13
StartingupACS310driveswithembeddedModbusRTU .......................................................................................14
StartingupACS355driveswithFMBA01ModbusRTUadapter ............................................................................15
StartingupACS800driveswithRMBA01ModbusRTUadapter............................................................................17
StartingupACS850,ACQ810driveswithembeddedModbusRTU ........................................................................18
StartingupACS880driveswithFSCA01ModbusRTUadapter..............................................................................19
StartingupACSM1driveswithFSCA01ModbusRTUadapter ..............................................................................20
Installdriveslibrary .................................................................................................................................................21
ControlBuilderPlusforPLCandDrives.......................................................................................................................22
Hardwareconfiguration ..........................................................................................................................................22
IPconfigurationofCPU(forEthernetconnectionbetweenPCandPLC) ...............................................................24
CODESYS ..................................................................................................................................................................25
CODESYStabs ......................................................................................................................................................25
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐3‐ PLCanddrivesintegration
LibraryManager ..................................................................................................................................................26
PLClogic...............................................................................................................................................................27
DownloadprogramtoPLC...................................................................................................................................32
Createbootproject .............................................................................................................................................33
Testtheprogram .................................................................................................................................................34
ReadandwritemoredatabetweenPLCanddrive(optional) ............................................................................36
Visualizations.......................................................................................................................................................43
Addmoredrives(optional)..................................................................................................................................46
Actualizationrate ................................................................................................................................................47
Otherusefuldocumentation.......................................................................................................................................47
Revision .......................................................................................................................................................................47
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐4‐ PLCanddrivesintegration
Introduction
Thisguid e willtakeyouthroughthehardwareinstallationandconfigurationofABBACSDrivesandPLCinorderto
prepare for Modbus RTU control. ABBspecific readymade function blocks and visualizations from the PS553
DRIVES library willbe used for thecontrol ofthe drives. While theguide is applicable to all AC500 PL
Cs and all
ModbusRTUcompatibleABBACSdrives,theexampleisbuiltupwithanAC500eCoPLCandanACS355drive.
Note! The ma
terial in this application might need to be adapted according to actual equipment and func tion
beforeitisused.Testingoftheeq
uipmentmustalwaysbeperformedbytheresponsiblestartuppersonaccording
to current legislation before the equipment is placed in service. ABB does not take any responsibility for possible
damagecausedbyusingthematerialinthisapplication(shownexamples,data,projecttools,etc.).
Safetyinstructions
Followallsafetyinstructionsdeliveredwiththeusedcomponents:
Readthecompletesafetyinstructionsfortheuseddrivebeforeyouinstall,commissionorusethedrive.
Thecompletesafetyinstructionsaregivenatthebeginningofthedrivesuser’smanual(e.g.forACS355:
3AUA0000066143[English]).
Read all safety and install
ation instructions of the used PLC. See the online help in CoD eSys (Help→
Contents→TargetSystem→AC500/S500→Introduction→Overview→Regulations).
Limitations
Thefollowinglimitationsarevalidforthisguide:
General
o AllinstructionsinthisguidearebasedondefaultsettingsinPLCanddrives
o PS501ControlBuilderPlusversion2.2.0orlater
o ThedrivemustbeequippedwithembeddedModbusRTUoraModbusRTUadapter
FunctionblockandvisualizationlibraryPS553DRIVEScompatibili
ty
o Communicationprofile:ABBdrives
o Drivetypes:AllModbusRTUcompatibleABBACSdriv es
o Applicationtypes:Speed/FrequencycontrolorTorquecon trol
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐5‐ PLCanddrivesintegration
Setupexample
ControlBuilderPlus


AC500PLC
ABBACSDrives
ETHERNETor
serialconnection
ModbusRTU
ABBModbus
RTUmodules
orembedded
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐6‐ PLCanddrivesintegration
Hardwarephysicalconnection
Inthefollowingchapter,physicalconnectionofthehardwarewillbeexplained.
Fieldbusgrounding
For AC500, which has optoisolated COM interfaces, it is recommended not to connect the ground. For AC500
eCo, where the COM interfaces are not optoisolated, it is recommended to connect the ground at one place,
typicallyinthebusmaster.Forconnectionexamples,seechapter“Installationexamples”.
Fieldbusshield
TheshieldshouldalwaysbeconnectedinaModbusRTUline.ThepurposeoftheshieldistoprotectagainstEMC
disturbancesandreflectiononthebusline.Forconnectionexamples,seechapter“Installationexamples”.
Endtermination
Purpose:Toavoidsignalreflections.
Resistorsize:120Ohms,¼W.
Wheretoconnect:Oneresistorineachendofthebusline(firstandlastnode).
Pullup/pulldownresistors
Purpose:Tokeepadefinedhighlevelonthebuswhilethereisnodataexchange.
Resistor size: Depends on bus master (COM) voltage level. 470Ωfor AC500 (5 V output) and 270Ωfor
AC500eCo(3.3Voutput).
Wheretoconnect:Activatepullupandthepu lldow
nresistors,butonly onceoneverybus line,atthebus
master.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐7‐ PLCanddrivesintegration
AC500andAC500eCoCOMportoverview
AC500 AC500eCo CM574RS
COM1 COM2 COM1 COM2
(optional)
COM1=COM2
(seeCOM1of
AC500,exceptpull
up/pulldown)
COMVoltagelevel 5V 5V 3,3V 3,3V 5V
Optoisolated
(electricallyisolated)
YES YES NO
optional*)
NO YES
Maximumbuscable
length
Acc.toRS485
standard
Acc.toRS485
standard
50m
*)Accto
RS485
standard
50m Acc.toRS485
standard
Connection Terminal 9poleDsub 9poleDsub
*)Terminal
Terminal Terminal
Terminationresistor
builtin
NO NO NO NO NO
Terminationresistor
size
120Ω 120Ω 120Ω 120Ω 120Ω
Pullup/pulldown
resistorsbuiltin
YES(connect
withbridges)
NO NO
*)yesconnect
withbridges
YES(connect
withbridges)
YES(connectwith
bridges)
Pullup/pulldown
resistorsize
470Ω 470Ω 270Ω 270Ω 475Ω
Pullup/pulldown
resistorsconnection
point
Master(CPU)
COMport
Master(CPU)
COMport
Master(CPU)
COMport
Master
(CPU)COM
port
Master(CPU)COM
port
Pullup/pulldown
connection
Bridges:1to
2and3to4
External470
Ωresistors
External270Ω
resistors
Bridges:1to
2and3to4
Bridges:1to2and3
to4
*)usingTK506RS485isolatorforPM554/PM564withindexA3andhigher
Driveswithembeddedfieldbus
ThefollowingABBdriveshaveModbusRTUembedded:
ACS310
ACS/ACH550
ACS850
Since the builtin end termination of the drive automatically also activates pullup/pulldown resistors, it is
recommendedtoskipthebuiltinoption.
Itis recommended to connect a separateendtermination resistor to the first node (i
.e.thePLC COM interface)
andthelastnode(i.e.thelastdriveonthebus).
Forconnectionexamples,seechapter“Installationexamples”.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐8‐ PLCanddrivesintegration
FieldbusmodulesforABBdrives
The following ABB drives Modbus RTU modules have an option to activate builtin end termination and pull
up/pulldownresistors.
RMBA01(usedwithforinstanceACS550andACS800)
FSCA01(usedwithforinstanceACS880andACSM1)
ThefollowingABBdrivesModbusRTUmoduledoesnothaveanoptiontoactivatebuil
tinendresistorsincluding
pullup/pulldownresistors.
FMBA01(usedwithforinstanceACS355)
Since the builtin end termination of the modules (RMBA01 and FSCA01) automatically also activates pull
up/pulldownresistors,itisrecommendedtoskipthebuiltinoption.
Itis recomm
ended to connect a separateendtermination resistor to the first node (i.e. the PLC COMinterface)
andthelastnode(i.e.thelastdriveonthebus).
Forconnectionexamples,seechapter“Installationexamples”.
Commonrecommendations
Note!Thefollowingbulletsareonlyrecommendationsandnogeneralrules.
Installationwheretotalcablelengthismorethan50 m
o UseCPUAC500ratherthanAC500eCoorAC500eCowithTK506RS485isolatorforCOM1.
Installationwherethereisariskthatgroundconnectionsindiffer
entnodescouldvaryinvoltagepotential
(typicallyinshipinstallationsorwithcablelengthsmorethan50m).
o UseCPUAC500anddonotconnectgroundcable,onlyshield →2wiresolution,oruseAC500eCo
withTK506RS485isolatorforCOM1.
WhenAC500eCoisused
o Use of 3wire conne
ction is recommended because the COM interface is not optoisolated,
oruseAC500eCowithTK506RS485isolatorforCOM1.
o Use of cable length more than 50m should be realized with repeaters,
oruseAC500eCowithTK506RS485isolatorforCOM1.
Cabletyp
e
o Use only cables with twisted pair wires and braided shields. Foil shields are not robust enough,
cannotbecontactedwellandhavepoorHF(HighFrequency)properties.
o Groundthecableshield directlywithaclipwhenenteringtheswitchgearcabinet.Donotcutthe
shieldun
tilthecablereachestheconnectedmodule.
o TheconnectionbetweenthePEbarandtheshieldbarmusthavelowimpedance.
o UseABBcableTK505whensuitableforeasyinstallation.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐9‐ PLCanddrivesintegration
Busline
Construction 2cores,twisted,withcommonshield
Conductorcrosssection >0.22mm
2
(24AWG)
recommendation 0.5mm
2
correspondstoØ0.8mm
Twistingrate <10/meter(symmetricallytwisted)
Coreinsulation Polyethylene(PE)
Resistancepercore <100Ω/km
Characteristicimpedance Appr.120Ω(100…150Ω)
Capacitancebetweenthecores <55nF/km(ifhigher,thenmaxbuslength
mustbereduced)
Terminatingresistors 120Ω,¼Watbothlineends
Remarks CableswithPVCcoreinsulationandacore
diameterof0.8mmcanbeuseduptoa
lengthofappr.250m.Inthiscase,thebus
terminatingresistorisappr.100Ω.
ABBcableTK505
ForaneasyModbusins tallationintheCPUend,thepremadeABB cableTK505canbeused.Itincludesa9poleD
sub contact with builtin end termination (120Ω) and pullup/pulldown resistors (2*270Ω). This contact is
suitablefor AC500eCo COM1. Itcan also be usedfor AC500 COM2 (eventhoughanother voltagele
velis used),
butonlyiftheGNDwireisnotconnectedtotheModbusslaves(2wiresolution, preferred forAC500COMports).
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐10‐ PLCanddrivesintegration
Installationexamples
Bestconnectionofshieldistoconnectdirectlytothemountingplateofthecabinetasnearaspossibletothe
AC500.Themountingplatehastobeconnectedtocommonearthinthecabinetatonepoint.
or
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐11‐ PLCanddrivesintegration
AC500COM
1Masteratthebuslineend
AC500COM
2Masteratthebuslineend
AC500eC
oCOM1Masteratthebuslineend
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐12‐ PLCanddrivesintegration
AC500eC
oCOM2Masteratthebuslineend
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐13‐ PLCanddrivesintegration
Driveconfiguration
DriveswithoutembeddedModbusRTUneedtobeequippedwithModbusRTUadapteraccordingtoactualdrive
type.
ThefollowingdriveconfigurationstepswilladaptthedrivetoModbusRTUcontrolbasedonABBspecificdrives
libraryPS553DRIVES.
Driveparameterscanbesetfromthedrive’scontrolpanelorfromdrivespecificpctool(Dri
veWindowLightfor
ACS355andACS550,DriveStudioforACS850andACSM1,DriveComposerforACS880andDriveWindowfor
ACS800).
Note!Allpar
ametersettingsarebasedondrivedefaultsettings.Ifthedrive hasbeenparameterizedpreviously,
returntodefaultsettingsbeforecontinuing.Itcanbedoneby:
Changingma
cro(andthenchangingbackagain)inparameter99.02forACS310,ACS355andACS550.
Settingparameter99.03APPLICRESTOREtoYESinACS800.
Settingparameter16.04ParamrestoretoRestoredefsinACS850andACSM1.
Settingparameter96.06ParameterrestoretoRestoredefaultsinACS880.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐14‐ PLCanddrivesintegration
StartingupACS310driveswithembeddedModbusRT
U
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting Comment
98.02 COMMPROTSEL STD
MODBUS
Activatesfieldbuscommunication
53.02 EFBSTATIONID [Address] ModbusRTUnodeaddressofthedrive
53.03 EFBBAUDRATE 19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
53.04 EFBPARITY 8NONE1
(example)
Parityandstopbits.Sameparityandstopbitsmust
bedefinedintheModbusRTUmaster.
53.05 PROFILE ABBDRV
FULL
Communicationprofile“ABBDrives”
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01 EXT1COMMANDS COMM Fieldbusinterfaceassourceforstartandstop
11.02 EXT1/EXT2SEL COMM FieldbusinterfaceassourcetoswitchtoEXT2
11.03 REF1SELECT COMM Fieldbusinterfaceassourceforspeedreference
16.04 FAULTRESETSEL COMM Fieldbusinterfaceassourceforfaultreset
Optionalparameterse
ttings
30.18 COMMFAULT
FUNC
[optional] Howthedrivereactstoafieldbuscommunication
break.
30.19 COMMFAULTTIME [optional] Timebetweencommunicationbreakdetectionand
theselectedaction.
(11.05) REF1MAX [Scalemax] Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Must
belessorequaltodriveparametermax
speed/frequency.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐15‐ PLCanddrivesintegration
StartingupACS355driveswithFMBA01ModbusRT
Uadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting ApplicMacro
”AC500
MODBUS”*)
Comment
98.02 COMMPROTSEL STD
MODBUS
STD
MODBUS
Activatesfieldbusmodule
53.02 EFBSTATIONID [Address] 2 ModbusRTUnodeaddressofthedrive
53.03 EFBBAUDRATE 19.2kbit/s
(example)
19.2kbit/s Transferrateofthelink.Samebaudratemust
bedefinedintheModbusRTUmaster.
53.04 EFBPARITY 8NONE1
(example)
8NONE1 Parityandstopbits.Sameparityandstopbits
mustbedefinedintheModbusRTUmaster.
53.05 PROFILE ABBDRV
FULL
ABBDRV
FULL
Communicationprofile“ABBDrives”
53.10 ActualSpeed 101 101 Actualspeedfeedback
53.11 ActualValue2 105 303 Actualvalue2(e.gtorque105)(303=Status
Word1)
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01 EXT1COMMANDS COMM COMM Fieldbusinterfaceassourceforstartandstop
11.02 EXT1/EXT2SEL COMM COMM FieldbusinterfaceassourcetoswitchtoEXT2
11.03 REF1SELECT COMM COMM Fieldb usinterfaceassourceforspeed
reference
16.04 FAULTRESETSEL COMM COMM Fieldbusinterfaceassourceforfaultreset
Optionalparameterse
ttings
30.18 COMMFAULT
FUNC
[optional]
FAULT
Howthedrivereactstoafieldbus
communicationbreak.
30.19 COMMFAULTTIME [optional] Default:.3s Timebetweencommunicationbreakdetection
andtheselectedaction.
(11.05) REF1MAX [Scalemax] Maxspeed/frequencyscalingvalue(usedin
functionblock/visualizationinput
“SPEED_REF_MAX”).Mustbelessorequalto
driveparametermaxspeed/frequency.
*)inPar.99.02theApplicationMacrocanbesetto“AC500Modbus(10)”thentheparametersareautomatically
setasshown.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐16‐ PLCanddrivesintegration
StartingupACS550withembeddedModbusRTU
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting Comment
98.02 COMMPROTSEL EXTFBA Activatesfieldbuscommunication
53.02 EFBSTATIONID [Address] ModbusRTUnodeaddressofthedrive
53.03 EFBBAUDRATE 19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
53.04 EFBPARITY 8NONE1
(example)
Parityandstopbits.Sameparityandstopbitsmust
bedefinedintheModbusRTUmaster.
53.05 PROFILE ABBDRV
FULL
Communicationprofile“ABBDrives”
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01 EXT1COMMANDS COMM Fieldbusinterfaceassourceforstartandstop
11.02 EXT1/EXT2SEL COMM FieldbusinterfaceassourcetoswitchtoEXT2
11.03 REF1SELECT COMM Fieldbusinterfaceassourceforspeedreference
16.04 FAULTRESETSEL COMM Fieldbusinterfaceassourceforfaultreset
Optionalparameterse
ttings
30.18 COMMFAULT
FUNC
[optional] Howthedrivereactstoafieldbuscommunication
break.
30.19 COMMFAULTTIME [optional] Timebetweencommunicationbreakdetectionand
theselectedaction.
(11.05) REF1MAX [Scalemax] Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Must
belessorequaltodriveparametermax
speed/frequency.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRT
U‐17‐ PLCanddrivesintegration
StartingupACS800driveswithRMBA01ModbusRTUadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting Comment
98.02 COMM.MODULE
LINK
STD
MODBUS
Activatesfieldbusmodule
98.07 COMMPROFILE ABBDRIVES Communicationprofile“ABBDrives”
52.01 STATION
NUMBER
[Address] ModbusRTUnodeaddressofthedrive
52.02 BAUDRATE 19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
52.03 PARITY NONE1STO
PBIT
(example)
Parityandstopbits.Sameparityandstopbitsmustbe
definedintheModbusRTUmaster.
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01 EXT1
STRT/STP/DIR
COMM.CWFieldbusinterfaceassourceforstartandstop
11.02 EXT1/EXT2
SELECT
COMM.CWFieldbusinterfaceassourcetoswitchtoEXT2control
location
11.03 EXTREF1SELECT COMM.REF Fieldbusinterfaceassourceforspeedreference
16.04 FAULTRESETSEL COMM.CWFieldbusinterfaceassourceforfaultreset
92.02 MAINDSACT1 102 Actualspeedvaluetake nfr om01.02
92.02 MAINDSACT2 e.g.105 Actualvalue2.E.gtorquetakenfrom01.05
Optionalparameterse
ttings
30.18 COMMFLTFUNC [optional] Howthedrivereactstoafieldbuscommuni cation
break.
30.19 MAINREFDST
OUT
[optional] Timebetweencommunicationbreakdetectionandthe
selectedaction.
(11.05) EXTREF1
MAXIMUM
[Scalemax] Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Mustbe
lessorequaltodriveparametermaxspeed/frequency.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRT
U‐18‐ PLCanddrivesintegration
StartingupACS850,ACQ810driveswithembeddedModbusRTU
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting Comment
50.15 Fbcwused P.02.36 SelectstheaddressofthefieldbusControlWordin
use.
58.01 Protocolenasel ModbusRTUInitializesembeddedfieldbuscommunication.
Drivetodrivelinkoperation(parametergroup
57)isautomaticallydisabled.
58.03 Nodeaddress [Address] ModbusRTUnodeaddressofthedrive
58.04 Baudrate 19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
58.05 Parity 8none1
(example)
Parityandstopbits.Sameparityandstopbitsmust
bedefinedintheModbusRTUmaster.
58.06 Controlprofile ABBClassic Communicationprofile“ABBDrives”
58.10 Refreshsettings [optional] Refreshesthesettingsofparameters
58.01…58.09.
10.01 Ext1startfunc FB Fieldbusinterfaceassourceforstartandstop
12.01 EXT1/EXT2SEL P.02.36bit
15
FieldbusinterfaceassourcetoswitchtoEXT2
controllocation
21.01 Speedref1sel EFBref1 Fieldbusinterfaceassourceforspeedreference
10.10 Faultresetsel P.02.36bit8 Fieldbusinterfaceassourceforfaultreset
Optionalparameterse
ttings
58.07 Commlosstout [optional] DefinesthetimeoutlimitfortheEFB
communicationmonitorin g.
58.08 Commlossmode Noneor
AnyMessage
Enables/disablesEFBcommunicationloss
monitoringanddefinesthemeansforresetting
thecounterofthecommunicationlossdelay.
58.09 Commlossaction [optional] DefinesthedriveoperationaftertheEFB
communicationlossmonitoringawakes.
58.10 Refreshsettings [optional] Refreshesthesettingsofparameters
58.01…58.09.
(19.01) Speedscaling [Scale max] Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Must
belessorequaltodriveparametermax
speed/frequency.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRT
U‐19‐ PLCanddrivesintegration
StartingupACS880driveswithFSCA01ModbusRTUadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting Comment
50.01 FBAAenable Enable Activatesfieldbusmodule
51.02 PROTOCOL/PROFIL
E
ABBDrives
Classicor
Enhanced
Communicationprofile“ABBDrives”
51.03 STATIONID [Address] ModbusRTUnodeaddressofthedrive
51.04 BAUDRATE 19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
51.05 EFBPARITY 8NONE1
(example)
Parityandstopbits.Sameparityandstopbits
mustbedefinedintheModbusRTUmaster.
52.02 FBAdatain2 Act116bit(5) ActualspeedasDataWord2fromthedrive
53.02 FBAdataout2 Ref116bit(2) SpeedreferenceasDataWord2tothedrive
51.27 FBAparrefresh Configure Updatesfieldbussettings(groups50to57)
19.11 Ext1/Ext2selection McwBit11
(06.01)
FieldbusinterfaceassourcetoswitchtoEXT2
controllocation
20.01 Ext1commands FieldbusA Fieldbusinterfaceassourceforstartandstop
20.02 Ext1starttrigger Level TodirectlyrestartafterCoastStop(Off3)
22.11 Speedref1
selection
FBAref1 Fieldbusinterfaceassourceforspeedreference
31.11 Faultreset
selection
P.06.01bit7 Fieldbusinterfaceassourceforfaultreset
Optionalparameterse
ttings
50.02 FBAAcommloss
func
[optional] Definesthedriveoperationafterthe
communicationlossmonitoringawakes.
51.06 MODBUSTIMEOUT [optional] Timebetweencommunicationbreakdetection
andtheselectedaction.1=100ms.
51.07 TIMEOUTMODE CONTROL
WRITE
Howthedrivereactstoafieldbuscommunication
break.
51.27 FBAPARREFRESH REFRESH Updatesfieldbussettings(groups50to53)
(46.01) Speedscaling [Scale max] Maxspeed/frequencyscalingvalue(usedin
functionblock/visualizationinput
“SPEED_REF_MAX”).Mustbelessorequaltodrive
parametermaxspeed/frequency.
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐20‐ PLCanddrivesintegration
StartingupACSM1driveswithFSCA01Modb
usRTUadapter
Minimumre
quiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting Comment
50.01 FBAENABLE Enable Activatesfieldbusmodule
51.02 PROTOCOL/PROFILE ABBDrives
Classic
Communicationprofile“ABBDrives”
51.03 STATIONID [Address] ModbusRTUnodeaddressofthedrive
51.04 BAUDRATE 19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
51.05 EFBPARITY 8NONE1
(example)
Parityandstopbits.Sameparityandstopbits
mustbedefinedintheModbusRTUmaster.
52.01 FBADATAIN1 4 StatuswordasDataWord1fromthedrive
52.02 FBADATAIN2 5 ActualspeedasDataWord2fromthedrive
53.01 FBADATAOUT1 1 ControlwordasDataWord1tothedrive
53.02 FBADATAOUT2 2 SpeedreferenceasDataWord2tothedrive
51.27 FBAPARREFRESH REFRESH Updatesfieldbussettings(groups50to53)
10.01 EXT1STARTFUNC FBA Fieldbusinterfaceassourceforstartandstop
12.01 EXT1/EXT2SEL P.02.12bit15 FieldbusinterfaceassourcetoswitchtoEXT2
controllocation
24.01 SPEEDREF1SEL FBAREF1 Fieldbusinterfaceassourceforspeedreference
10.08 FAULTRESETSEL P.02.12bit8 Fieldbusinterfaceassourceforfaultreset
Optionalparameterse
ttings
51.06 MODBUSTIMEOUT [optional] Timebetweencommunicationbreakdetection
andtheselectedaction.1=100ms.
51.07 TIMEOUTMODE CONTROL
WRITE
Howthedrivereactstoafieldbuscommunication
break.
50.02 COMMLOSSFUNC [optional] Definesthedriveoperationafterthe
communicationlossmonitoringawakes.
51.27 FBAPARREFRESH REFRESH Updatesfieldbussettings(groups 50to53)
(25.02) SPEEDSCALING [Scalemax] Maxspeed/frequencyscalingvalue(usedin
functionblock/visualizationinput
“SPEED_REF_MAX”).Mustbelessorequaltodrive
parametermaxspeed/frequency.
/