Hamworthy Dorchester DR-FC 80-95 Installation guide

Category
Water heaters & boilers
Type
Installation guide
1
DORCHESTER MODELS: DR-FC 80, 95
Condensing, Closed Combustion, Direct Gas Fired Hot Water Storage Heaters
with Automatic Ignition for
Domestic Hot Water Installations
NOTE: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE
INSTALLING, COMMISSIONING, OPERATING OR SERVICING EQUIPMENT.
THIS WATER HEATER IS FOR USE ON GROUP H NATURAL GAS (2ND FAMILY) I2H OR
LPG (3RD FAMILY) I3P. PLEASE ENSURE RELEVANT INFORMATION REQUIRED WITHIN
DOCUMENT IS FOUND RELATING TO SPECIFIC GAS TO BE FIRED BEFORE FIRING
HEATER.
THIS WATER HEATER COMPLIES WITH ALL RELEVANT EUROPEAN DIRECTIVES.
PUBLICATION NO. 500001154
ISSUE ‘A’
FEBRUARY 2006
DORCHESTER
DR-FC 80 to DR-FC 95
HOT WATER
STORAGE HEATERS
Installation, Commissioning
and Maintenance Instructions
Instruction Manual DR-FC 3
gis
Table of contents
Table of contents - - - - - - - - - - - - - - - - - - - - - - - - - 3
1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
1.1 About the water heater - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
1.2 What to do if you smell gas- - - - - - - - - - - - - - - - - - - - - - - - - 7
1.3 Regulations and documents - - - - - - - - - - - - - - - - - - - - - - - - 7
1.4 Target groups - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8
1.5 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.6 Forms of notation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.7 Overview of this document - - - - - - - - - - - - - - - - - - - - - - - - 10
2 Functioning of the water heater - - - - - - - - - - - - - - - - 11
2.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11
2.2 Functional description of the water heater - - - - - - - - - - - - - - - - 12
2.3 The water heater’s heating cycle - - - - - - - - - - - - - - - - - - - - - 13
2.4 Protection for the water heater - - - - - - - - - - - - - - - - - - - - - - 13
2.4.1 Water temperature protection - - - - - - - - - - - - - - - - - 14
2.4.2 Gas control - - - - - - - - - - - - - - - - - - - - - - - - - - 14
2.4.3 Fan - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 14
2.4.4 Pressure switch - - - - - - - - - - - - - - - - - - - - - - - - 14
2.4.5 Flame probe - - - - - - - - - - - - - - - - - - - - - - - - - 15
2.5 Safety of the installation - - - - - - - - - - - - - - - - - - - - - - - - - 15
2.5.1 Unvented installation - - - - - - - - - - - - - - - - - - - - - 15
2.5.2 Vented installation- - - - - - - - - - - - - - - - - - - - - - - 15
2.5.3 T&P valve - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
2.6 Options - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
2.6.1 LPG- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
2.6.2 Unvented Supply - - - - - - - - - - - - - - - - - - - - - - - 15
2.6.3 Top to Bottom Circulation - - - - - - - - - - - - - - - - - - - 15
3 Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - 17
3.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 17
3.2 Packaging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 17
3.3 Environmental conditions- - - - - - - - - - - - - - - - - - - - - - - - - 17
3.3.1 Humidity and ambient temperature- - - - - - - - - - - - - - - 18
3.3.2 Maximum floor loading - - - - - - - - - - - - - - - - - - - - 18
3.3.3 Working clearances - - - - - - - - - - - - - - - - - - - - - - 19
3.4 Technical specifications - - - - - - - - - - - - - - - - - - - - - - - - - 20
3.5 Installation diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - 22
3.6 Water connections, Unvented - - - - - - - - - - - - - - - - - - - - - - 24
3.6.1 Cold water side - - - - - - - - - - - - - - - - - - - - - - - - 24
3.6.2 Top to bottom recirculating pump - - - - - - - - - - - - - - - 24
3.6.3 Hot water side- - - - - - - - - - - - - - - - - - - - - - - - - 24
3.6.4 Circulation pipe - - - - - - - - - - - - - - - - - - - - - - - - 24
3.6.5 Condensation drainage - - - - - - - - - - - - - - - - - - - - 24
gis
4Instruction Manual DR-FC
gis
3.7 Water connections, Vented - - - - - - - - - - - - - - - - - - - - - - - - 25
3.7.1 Cold water side- - - - - - - - - - - - - - - - - - - - - - - - - 25
3.7.2 Top to bottom recirculating pump - - - - - - - - - - - - - - - - 25
3.7.3 Hot water side - - - - - - - - - - - - - - - - - - - - - - - - - 25
3.7.4 Circulation pipe- - - - - - - - - - - - - - - - - - - - - - - - - 25
3.7.5 Condensation drainage - - - - - - - - - - - - - - - - - - - - - 25
3.8 Gas connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 25
3.9 Air supply and flue gas discharge - - - - - - - - - - - - - - - - - - - - - 26
3.9.1 Concentric wall flue terminal C13 - - - - - - - - - - - - - - - - 27
3.9.2 Concentric roof flue terminal C33 - - - - - - - - - - - - - - - - 28
3.10 Electrical connections - - - - - - - - - - - - - - - - - - - - - - - - - - - 29
3.10.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - 29
3.10.2 Preparation- - - - - - - - - - - - - - - - - - - - - - - - - - - 29
3.10.3 Mains power - - - - - - - - - - - - - - - - - - - - - - - - - - 30
3.10.4 Isolating transformer - - - - - - - - - - - - - - - - - - - - - - 31
3.10.5 program-controlled pump - - - - - - - - - - - - - - - - - - - - 31
3.10.6 Extra ON mode switch (’Tank ON’) - - - - - - - - - - - - - - - 31
3.10.7 Connecting extra error signal (’Alarm OUT’) - - - - - - - - - - - 31
3.11 Checking the supply pressure and burner pressure - - - - - - - - - - - - 32
3.12 Conversion to a different gas category - - - - - - - - - - - - - - - - - - - 35
3.12.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - 35
4 Filling and draining - - - - - - - - - - - - - - - - - - - - - - - 37
4.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 37
4.2 Filling the water heater - - - - - - - - - - - - - - - - - - - - - - - - - - 37
4.2.1 Filling unvented installations - - - - - - - - - - - - - - - - - - 37
4.2.2 Filling vented installations- - - - - - - - - - - - - - - - - - - - 37
4.3 Draining the water heater - - - - - - - - - - - - - - - - - - - - - - - - - 39
4.3.1 Draining unvented installations - - - - - - - - - - - - - - - - - 39
4.3.2 Draining vented installations - - - - - - - - - - - - - - - - - - 39
5 The control panel - - - - - - - - - - - - - - - - - - - - - - - - 41
5.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
5.2 Overview - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
5.3 Explanation of the icons - - - - - - - - - - - - - - - - - - - - - - - - - - 42
5.4 Control panel ON/OFF switch - - - - - - - - - - - - - - - - - - - - - - - 42
5.5 Navigation buttons - - - - - - - - - - - - - - - - - - - - - - - - - - - - 42
5.6 PC connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
6 Status of the water heater - - - - - - - - - - - - - - - - - - - 45
6.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
6.2 Operating modes - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
6.3 Error conditions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 46
6.4 Service condition - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
6.5 Anode protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
7 Starting up and shutting down - - - - - - - - - - - - - - - - - 49
7.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
7.2 Starting up - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
7.3 Shutting down- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 50
7.3.1 Shut the water heater down for a brief period (’OFF mode’) - - - 50
7.3.2 Isolate the water heater from the power supply - - - - - - - - - 50
7.3.3 Shut the water heater down for a longer period - - - - - - - - - 51
Instruction Manual DR-FC 5
gis
7.4 The water heater’s heating cycle - - - - - - - - - - - - - - - - - - - - - 51
8 Main menu - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
8.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
8.2 Notational convention for menu-related instructions - - - - - - - - - - - - 53
8.3 Switching into ’ON mode’- - - - - - - - - - - - - - - - - - - - - - - - - 54
8.4 Setting the water temperature - - - - - - - - - - - - - - - - - - - - - - 54
8.4.1 Setting the water temperature via SETPOINT menu - - - - - - 54
8.4.2 Setting water temperature during ON mode - - - - - - - - - - 54
8.5 Week program - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 55
8.5.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - 55
8.5.2 Starting up and shutting down the week program- - - - - - - - 55
8.5.3 Changing the water heater’s standard week program- - - - - - 55
8.5.4 Adding times to a week program - - - - - - - - - - - - - - - - 57
8.5.5 Deleting times from a week program - - - - - - - - - - - - - - 58
8.6 Extra period - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 60
8.6.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - 60
8.6.2 Programming an extra period - - - - - - - - - - - - - - - - - 60
8.7 Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 61
8.7.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - 61
8.7.2 Setting menu language - - - - - - - - - - - - - - - - - - - - 61
8.7.3 Setting day and time- - - - - - - - - - - - - - - - - - - - - - 62
8.7.4 Displaying water heater specifications - - - - - - - - - - - - - 62
9 Service program - - - - - - - - - - - - - - - - - - - - - - - - 65
9.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 65
9.2 Setting the hysteresis - - - - - - - - - - - - - - - - - - - - - - - - - - 65
9.3 Displaying the error history - - - - - - - - - - - - - - - - - - - - - - - - 65
9.4 Displaying the water heater history - - - - - - - - - - - - - - - - - - - - 66
9.5 Display the selected water heater - - - - - - - - - - - - - - - - - - - - 66
9.6 Setting the pump on/off - - - - - - - - - - - - - - - - - - - - - - - - - 66
9.7 Setting the service interval - - - - - - - - - - - - - - - - - - - - - - - - 66
9.8 Setting the display contrast- - - - - - - - - - - - - - - - - - - - - - - - 67
9.9 Setting the backlight time- - - - - - - - - - - - - - - - - - - - - - - - - 67
9.10 Setting the display scroll speed- - - - - - - - - - - - - - - - - - - - - - 67
10 Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - 69
10.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 69
10.2 Troubleshooting table for general errors - - - - - - - - - - - - - - - - - 70
10.3 Troubleshooting table for anode protection - - - - - - - - - - - - - - - - 73
10.4 Troubleshooting table for displayed errors - - - - - - - - - - - - - - - - 74
11 Maintenance frequency - - - - - - - - - - - - - - - - - - - - 85
11.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 85
11.2 Determining service interval - - - - - - - - - - - - - - - - - - - - - - - 85
12 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 87
12.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 87
12.2 Preparation for maintenance - - - - - - - - - - - - - - - - - - - - - - - 87
12.3 Water-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - 89
12.3.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - 89
12.3.2 Checking the anodes - - - - - - - - - - - - - - - - - - - - - 89
12.3.3 Descaling and cleaning the heater - - - - - - - - - - - - - - - 89
12.3.4 Cleaning condensation water discharge - - - - - - - - - - - - 89
6Instruction Manual DR-FC
gis
12.4 Gas-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 90
12.4.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - 90
12.4.2 Cleaning the burner - - - - - - - - - - - - - - - - - - - - - - 90
12.4.3 Cleaning the orifice - - - - - - - - - - - - - - - - - - - - - - - 90
12.4.4 Cleaning heat exchanger - - - - - - - - - - - - - - - - - - - - 90
12.5 Finalising maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 90
A Appendices - - - - - - - - - - - - - - - - - - - - - - - - - - - 91
A.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 91
A.2 Electrical diagram DR-FC - - - - - - - - - - - - - - - - - - - - - - - - - 92
A.3 Week program card - - - - - - - - - - - - - - - - - - - - - - - - - - - - 93
About the water heater
Instruction Manual DR-FC 7
gis
1 Introduction
1.1 About the water
heater
This manual describes how to install, service and use the DR-FC water heater.
The DR-FC water heater is a condensing room-sealed water heater with a fan
in the air intake. A concentric chimney connector is fitted standard to the water
heater. Alternatively, the water heater can be connected using a parallel system.
Installation types possible with this water heater are C13, C33, and C53. The
information in this manual is applicable to types: DR-FC 80 and DR-FC 95.
The manner of construction and features of the water heater are in conformance
with the European standard for gas-fired storage water heaters for the
production of domestic hot water (EN 89). The water heaters are compliant with
the European Directive for Gas Water heaters, and have the right to bear the
CE mark.
Warning
Read this manual carefully before starting up the water heater. Failure to
read the manual and to follow the printed instructions may lead to personal
injury and damage to the water heater.
1.2 What to do if you
smell gas Warning
Whenever there is a smell of gas:
No naked flames! No smoking!
Avoid causing sparks! Do not use any electrical equipment or switch, i.e. no
telephones, plugs or bells!
Shut off the mains gas supply!
Open windows and doors!
Warn occupants and leave the building!
After leaving the building, alert the gas distribution company or installer.
1.3 Regulations and
documents
Gas Safety Installations and Use Regulations 1998, (As amended). It is law
that all gas appliances are installed by competent persons, in accordance with
the above regulations. Failure to install appliances correctly could lead to
prosecution. It is in your own interest, and that of safety, to ensure that this law
is complied with.
The installation of the boiler MUST be in accordance with the relevant
requirements of the Gas Safety Regulations, Building Regulations, IEE
Regulations and the Water Supply (water fittings) Regulations.
The installation should also be in accordance with any relevant requirements of
the HSE, local gas region and local authority and the relevant recommendations
of the following documents:
British Standards
•BS 6891: Specification for installation of low pressure gas pipework of up to
28 mm (R1) in domestic premises (2nd family gas). For larger installations
see IGE/UP/2 below.
0063
gis
Introduction
8Instruction Manual DR-FC
1gis
•BS 6798: Specification for installation of gas-fired boilers of rated input not
exceeding 70 kW net.
•BS 6644: Specification for installation of gas-fired hot water boilers of rated
inputs between 60 kW and 2 MW (2nd and 3rd family gases).
•BS 6700: Specification for design, installation, testing and maintenance of
services supplying water for domestic use within buildings and their
curtilages.
•BS EN 806-2: Specification for installations inside buildings conveying water
for human consumption. Part 2: Design.
•BS 5546: Specification for installation of hot water supplies for domestic
purposes, using gas-fired appliances of rated input not exceeding 70 kW.
•BS 5440: Installation and maintenance of flues and ventilation for gas
appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family
gases). Part 1: Flues. Part 2: Ventilation.
Institute of Gas Engineers and Managers Publications
• IGE/UP/1 Soundness testing and purging of industrial and commercial gas
installations.
• IGE/UP/1A Soundness testing and direct purging of small low pressure
industrial and commercial natural gas installations.
• IGE/UP/2 Gas installation pipework, boosters and compressors on industrial
and commercial premises.
• IGE/UP/10 Installation of gas appliances in industrial and commercial
premises. Part 1: flued appliances.
CIBSE Publications:- "CIBSE Guide"
Section B4 : Water Service Systems.
1.4 Target groups The three target groups for this manual are:
• (end) users;
•installers;
• service and maintenance engineers
Symbols on each page indicate the target groups for whom the information is
intended. See Table 1.1.
Table 1.1 Target group symbols
Symbol Target group
g(End) user
iInstaller
sService and maintenance engineer
Maintenance
Instruction Manual DR-FC 9
gis
1.5 Maintenance A service should be carried out at least once a year, both on the water side and
on the gas side. Maintenance frequency depends, among other things, on the
water quality, the average burning time per day and the set water temperature.
nRemark
To determine the correct maintenance frequency, it is recommended to
arrange for the service and maintenance engineer to check the water heater
on both the water and gas side, three months after installation. Based on this
check, the best maintenance frequency can be determined.
nRemark
Regular maintenance extends the service life of the water heater.
Both the end user and the service and maintenance engineer are responsible
for regular maintenance. They will need to establish clear agreements on this.
nRemark
If the water heater is not regularly maintained, the warranty will become void.
1.6 Forms of notation The following notation is used in this manual:
nRemark
Important information
cNote
Ignoring this information can lead to the water heater being damaged.
Warning
Failure to carefully read this information may lead to danger of personal
injury, and serious damage to the water heater.
Introduction
10 Instruction Manual DR-FC
1gis
1.7 Overview of this
document
Table 1.2 provides an overview of the contents of this document.
Table 1.2 Contents of document
Chapter Target groups Description
2 Functioning of the water
heater gis This chapter describes how the water heater functions.
3Installation is This chapter describes the installation activity to be completed
before you actually start up the water heater. Instructions are
also provided for the installation and/or service and
maintenance engineer on converting the water heater to other
types of gas.
4 Filling and draining gis This chapter describes how to fill and drain the water heater.
5 The control panel gis This chapter describes the general control of the water heater
using the display.
6 Status of the water heater gis This chapter describes the status (mode or condition) that the
water heater may have, and possible actions to take.
7 Starting up and shutting
down gis This chapter describes how to start up the water heater, and
how to shut it down for a brief or long period of time. The
general heating cycle of the water heater is also described.
8 Main menu gis Describes the main menu of the display. This is the actual
menu for the user, however the installer and service and
maintenance engineers will also need to use this menu.
9 Service program is Describes the service menu. It is mainly intended for the
installer and service and maintenance engineers. End users
may also refer to this chapter for additional information about
the water heater.
10 Troubleshooting gis This chapter is mainly intended for the installer and the service
and maintenance engineer. It describes water heater errors.
These errors are indicated on the display. A troubleshooting
table of possible causes and solutions is provided. End users
may also refer to this chapter for additional information about
the water heater.
11 Maintenance frequency gs This chapter describes how to determine the optimum
frequency at which to carry out maintenance. Both the end
user and the service and maintenance engineer are
responsible for regular maintenance. They need to reach clear
agreement on this.
nRemark
If the water heater is not regularly maintained, the warranty
will become void.
12 Maintenance sThis chapter sets out the maintenance tasks to be carried out
during a service.
Introduction
Instruction Manual DR-FC 11
gis
2 Functioning of the
water heater
2.1 Introduction Topics covered in this chapter:
•Functional description of the water heater;
•The water heater’s heating cycle;
•Protection for the water heater;
•Safety of the installation.
gis
Functioning of the water heater
12 Instruction Manual DR-FC
2gis
2.2 Functional
description of the
water heater
Figure 2.1 shows a cut-away view of the water heater.
In this water heater, the cold water enters the bottom of the tank via the cold
water inlet (18). The tap water, heated by the combustion chamber (11) and
heat exchanger (29), leaves the tank through the hot water outlet (3). Once the
water heater is completely filled with water, it remains constantly under water
supply pressure. As hot water is drawn from the water heater, cold water is
immediately added.
The water heater is equipped with a gas/air premix burner (15). The air is drawn
in through the fan (12). The gas is added via the gas control (26) on the intake
side of the fan. The gas/air mixture is then blown into the burner. Thanks to the
modulated supply of gas and air, the optimum gas/air mixture is always
achieved.
Legend
(1) top cover
(2) mains choke
(3) hot water outlet
(4) control panel
(5) EMC filter
(6) frequency controller
(7) temperature sensor T1
(8) control panel
(9) potentiostat
(10) electrical connection block
(11) combustion chamber
(12) fan
(13) hot surface igniter
(14) flame probe
(15) burner
(16) inspection and cleaning
opening
(17) drain valve
(18) cold water inlet
(19) temperature sensor T2
(20) insulation layer
(21) pallet
(22) automatic air bleed
(23) circulation pump
(24) air supply hose
(25) pressure switch
(26) gas control
(27) anode
(28) tank
(29) heat exchanger
(30) chimney pipe
(31) siphon
IMD-0399
Figure 2.1 Cut-away view of the water heater
(1)
(3)
(10)
(8)
(25)
(4)
(7)
(11) (27)
(28)
(29)
(16)
(19)
(18)
(17)
(26)
(15)
(12)
(13)
(14) (30)
(31)
(20)
(21)
(6)
(9)
(23)
(24)
(2)
(5)
(22)
The water heater’s heating cycle
Instruction Manual DR-FC 13
gis
Through the special design of the heat exchanger (29), the flue gases are first
led downwards via the combustion chamber, then upwards again via the heat
exchanger, then once more downwards beside the water in the tank. In this
process, the flue gases gradually become cooler. Because the cooled flue
gases flow alongside the cold water lower down in the tank, they start to
condense. This condensation causes latent heat energy to be released, which
is transferred to the cooler water, and thereby increases the performance of the
unit. The condensate yielded by this process is discharged via the siphon (31).
The insulation layer (20) prevents heat loss. The inside of the tank is enamelled
to protect against corrosion. The two electrical low-maintenance anodes (27)
provide additional protection against corrosion.
For use during maintenance, the water heater has a inspection and cleaning
opening (16).
2.3 The water heater’s
heating cycle
The entire water heater is controlled (and monitored) by the control panel (4).
The temperature sensor T1 (7) (in the top of the tank (28)) and the temperature
sensor T2 (19) (lower down in the tank) measure the water temperature. The
continuous pump, standard in these water heaters, prevents excessive water
temperature differences within the water heater. The temperatures observed by
T1 and T2 are signaled to the control panel. Based on these two observations,
the control panel calculates a net water temperature: Tnet. The value of Tnet lies
between the temperatures measured at the top and bottom of the tank. As soon
as Tnet falls below the set water temperature (Tset), the control panel registers a
‘heat demand’. The gas control (26) is opened, and the gas is mixed with air.
This mixture is ignited by the hot surface igniter (13) and the water becomes
heated. As soon as Tnet rises above Tset, the heat demand ends, and the control
panel stops the heating cycle.
Both when registering and ending the heat demand, the control panel assumes
a certain margin. We refer to this margin as the hysteresis (see paragraph
’9.2 Setting the hysteresis’).
2.4 Protection for the
water heater
The control panel monitors the water temperature and ensures safe
combustion. This is achieved by:
•the Water temperature protection;
•the Gas control;
•the Fan;
•the Pressure switch;
•the Flame probe.
Functioning of the water heater
14 Instruction Manual DR-FC
2gis
2.4.1 Water temperature protection
Using temperature sensor T1 (7) and temperature sensor T2 (19), the control
panel monitors three temperatures which are important for safety. Table 2.1
explains the functioning of the temperature sensors.
2.4.2 Gas control
The control panel opens the gas control so that gas can be supplied to the
burner. As a safety measure, the gas control has two valves. Both valves shut
off the gas supply.
2.4.3 Fan
The fan, controlled by the frequency controller (6), provides an optimum air
supply when there is a heat demand. A safety aspect is that the fan ensures that
any gases present in the combustion chamber get removed, both before and
after combustion. We refer to this as pre- and post-purge.
2.4.4 Pressure switch
The pressure switch ensures the discharge of flue gases and the supply of
incoming air during the pre-purge and normal running of the water heater. The
standard position of the pressure switch is open. When sufficient pressure
differential is reached, the pressure switch closes. However, in the event of a
fault, the pressure switch will be tripped open, and the heating cycle will be
interrupted.
Table 2.2 shows the trip point per water heater.
nRemark
The trip point of the pressure switch is not adjustable.
Table 2.1 Temperature protection
Protection Description
Against frost
(T1 < 5°C or T2 < 5°C)
The frost protection cuts in. The water is heated to 20°C.
For maximum water temperature
(T1 > 85°C or T2 > 85°C)
The high-limit safeguard serves to prevent overheating and/or excessive
formation of scale in the water heater. Should the high-limit safeguard be
activated, the heating is halted. This causes the water in the tank to cool down.
Once the water has cooled sufficiently (T1 < 78 °C), the control panel resets
the water heater.
For extra safety
(T1 > 93°C or T2 > 93°C)
A lockout error of the water heater controller takes place. The controller must
be manually reset before the water heater can resume operation (see
paragraph ’6.3 Error conditions’). The reset may only be performed once T1 <
78°C.
Table 2.2 Pressure switch trip points
Water
heater
Pressure differential [Pa]
Closing Opening
DR-FC
80
> 395 < 365
DR-FC
95
> 525 < 495
Safety of the installation
Instruction Manual DR-FC 15
gis
2.4.5 Flame probe
To ensure that no gas can flow when there is no combustion, an flame probe
has been fitted. The control panel uses this rod for flame detection, by means
of ionisation detection. The control panel cuts in, the instant it detects that there
is a gas flow but no flame.
2.5 Safety of the instal-
lation
2.5.1 Unvented installation
With an unvented installation, a expansion valve and expansion vessel prevent
excessive pressure in the tank. This prevents damage being caused to the
enamelled coating (in the water heater) or to the heater. A non-return valve
prevents excessive pressure in the water supply system. This valve also
prevents water from flowing backwards from the tank into the cold water supply
system. The pressure reducing valve protects the installation against an
excessively high water supply pressure. These components are fitted to the cold
water pipe. See paragraph ’3.6.1 Cold water side’.
2.5.2 Vented installation
With a vented installation, excess pressure is taken up by the open water tank.
The level of the water tank determines the maximum working pressure in the
heater, which may not exceed 8 bar. The installation must also be fitted with an
open vent from the hot water pipe, which discharges into a tundish. See
paragraph ’3.6.3 Hot water side’.
2.5.3 T&P valve
A T&P valve is mandatory in an ‘unvented’ installation.
A T&P valve monitors the pressure in the heater, and the water temperature at
the top of the heater. If the pressure in the heater becomes excessive (>7 bar)
or the water temperature is too high (>97°C), the valve will open. The hot water
will immediately flow out of the heater. Because the water heater is under water
supply pressure, cold water will automatically flow into the heater. The valve
remains open until the unsafe situation has been averted. A connecting point for
a T&P valve is standard on the water heater. See paragraph ’3.6.3 Hot water
side’.
2.6 Options The heaters can be supplied with the following additional variations, either
ready fitted or for site fitting:
2.6.1 LPG
The heaters can be supplied adjusted for use on propane or butane, see section
3.12. It is most important that the heater is correctly adjusted for the gas to be
fired.
2.6.2 Unvented Supply
The heaters can be supplied with a purpose designed and sized unvented kit
comprising pressure reducing valve, non-return valve, expansion vessel,
expansion relief valve and pressure/temperature relief valve, to enable the
heater to be coupled directly to the mains water. For details see 2.5.1, 2.5.3 and
3.6.
2.6.3 Top to Bottom Circulation
In order to give enhanced temperature control to aid compliance with the HSE
guidance and the DHss Code of Practice for 'The Control of Legionellae in
Health Care Premises', a pump circulation kit can be supplied comprising 230
volt single phase pump, non-return valve, pipe work and sufficient fittings to
contact between the hot water flow and the bottom connection. For details see
section 3.5 of this manual.
Functioning of the water heater
16 Instruction Manual DR-FC
2gis
Introduction
Instruction Manual DR-FC 17
is
3 Installation
Warning
The installation should be carried out by an approved installer in compliance
with the general and local regulations imposed by the gas, water and power
supply companies and the fire service.
The water heater may only be installed in a room which complies with the
requirements stated in national and local ventilation regulations.
Refer also to paragraph ’1.3 Regulations and documents’.
3.1 Introduction This chapter describes the installation activities to be carried out before the
water heater may be started up, namely:
•Packaging;
•Environmental conditions;
•Technical specifications;
•Water connections, Unvented;
•Water connections, Vented;
•Gas connection;
•Air supply and flue gas discharge;
•Electrical connections;
•Checking the supply pressure and burner pressure;
•Conversion to a different gas category.
nRemark
Starting up the water heater is described in chapter ’7 Starting up and
shutting down’.
3.2 Packaging To avoid damaging the water heater, remove the packaging carefully.
We recommend unpacking the water heater at or near its intended location.
cNote
The water heater may only be manoeuvred in an upright position. Take care
that the water heater is not damaged after unpacking.
3.3 Environmental
conditions The DR-FC water heater is a room-sealed water heater. Installation types
possible with this water heater are C13, C33, and C53. This makes it possible
to install the water heater in either a closed or an open boiler room.
is
Installation
18 Instruction Manual DR-FC
3is
3.3.1 Humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. Table 3.1
shows the environmental conditions that must be adhered to, for correct
functioning of the electronics present in the water heater to be guaranteed.
3.3.2 Maximum floor loading
In connection with the water heater’s weight, take account of the maximum floor
loading, see Ta b le 3. 2 .
Table 3.1 Humidity and ambient temperature specifications
Humidity and ambient temperature
Humidity max. 93% RH at +25°C
Ambient temperature Functional: 0 ≤ t ≤ 50°C
Table 3.2 Weight specifications related to maximum floor loading
Weight of the water heater filled with water
DR-FC 80, DR-FC 95 893 kg
Environmental conditions
Instruction Manual DR-FC 19
is
3.3.3 Working clearances
For access to the water heater it is recommended that the following
clearances are observed (see Figure 3.1):
• AA: around the water heater’s control column and cleaning openings: 100
cm.
• BB: around the water heater itself: 50 cm.
nRemark
When installing the water heater, be aware that any leakage from the tank
and/or connections can cause damage to the immediate environment or
floors below the level of the boiler room. If this is the case, then the water
heater should be installed above a wastewater drain or in a suitable metal
leak tray.
The leak tray must have an appropriate wastewater drain and must be at
least 5 cm deep with a length and width at least 5 cm greater than the
diameter of the water heater.
Figure 3.1 Working clearances
BB
AA
AA
IMD-0227
Installation
20 Instruction Manual DR-FC
3is
3.4 Technical specifica-
tions
The water heater is supplied without accessories. Check the dimensions and
other specifications for the accessories to be used, based on Figure 3.2 and
tables Tab le 3 .3 through Ta ble 3 . 6.
Figure 3.2 Plan and elevation of the water heater
IMD-0400
Table 3.3 Dimensions
Dimensi
on
Description Unit DR-FC 80 DR-FC 95
A Total height mm 2100 2100
D Water heater diameter mm 845 845
E Depth mm 1000 1000
FWidth mm 900 900
GDiameter of air supply/flue gas discharge mm 130/200 130/200
K Height of gas connection mm 1845 1845
M Height of cold water supply connection mm 225 225
Technical specifications
Instruction Manual DR-FC 21
is
N Height of hot water outlet connection mm 2050 2050
P Height of cleaning and inspection opening mm 290 290
R Height of drain valve mm 225 225
S Height of T&P valve mm 1415 1415
W Height of condensation drainage connection mm 260 260
X Height of air supply connection mm 1830 1830
1 Cold water supply connection - R 11/2
2 Hot water outlet connection - R 11/2
3 Gas control connection - Rp 3/4
4 Drain valve connection - 3/4"
5 T&P valve connection - 1-11.5 NPT
6 Cleaning/inspection opening mm 95 x 70
7 Condensation drainage connection - Rp 1
Table 3.4 Gas data II2H3P
Description Unit DR-FC 80 DR-FC 95
Specifications for natural gas 2H: G20 - 20 mbar
Orifice diameter mm 7.00 7.60
(1) = flat sealing plate
(2) = burner pressure regulator
1 or 2 2 2
Nominal load (gross) kW 85.0 103.5
Nominal output kW 80.3 97.9
Supply pressure mbar 20 20
Burner pressure mbar 7.0 6.5
Gas consumption (1) m3/h 8.3 10.1
Specifications for LP gas 3P: G31 - 37 mbar (propane)
Orifice diameter mm 5.00 5.40
(1) = flat sealing plate
(2) = burner pressure regulator
1 or 2 2 2
Nominal load (gross) kW 83.2 101.2
Nominal output kW 80.3 97.8
Supply pressure mbar 37 37
Table 3.3 Dimensions
Dimensi
on
Description Unit DR-FC 80 DR-FC 95
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94

Hamworthy Dorchester DR-FC 80-95 Installation guide

Category
Water heaters & boilers
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI