Hamworthy Dorchester DR-LA Installation guide

Category
Water heaters & boilers
Type
Installation guide
NOTE:
THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE
INSTALLING, COMMISSIONING, OPERATING OR SERVICING EQUIPMENT
PUBLICATION NO. 500001137
ISSUE: “B”
AUGUST 2014
Dorchester DR-LA Range
of Hot Water Storage Heaters
Installation, Commissioning
and Maintenance Instructions
DORCHESTER DR-LA 30, 40, 45, 60, 75, 95, 110 Models
Open Flue, Direct Gas Fired Hot Water Storage Heaters
with Automatic Ignition
for Domestic Hot Water Installations
NATURAL GAS I LPG I
2H 3+
THIS WATER HEATER COMPLIES WITH ALL RELEVANT EUROPEAN DIRECTIVES.
THIS WATER HEATER IS FOR USE ON GROUP H NATURAL GAS (2 FAMILY) I ,
OR LPG (3 FAMILY) I . PLEASE ENSURE RELEVANT INFORMATION REQUIRED
WITHIN DOCUMENT IS FOUND RELATING TO GAS TO BE FIRED BEFORE
FIRING HEATER.
ND
RD
2H
3+
Instruction manual DR-LA 3
gis
Read this manual carefully Warning
Read this manual carefully before starting the water heater. Failure to read
the manual and to follow the printed instructions may lead to personal injury and
damage to the water heater.
Copyright © 2014
All rights reserved.
Nothing from this publication may be copied, reproduced and/or published by
means of printing, photocopying or by whatsoever means, without the prior
written approval of the supplier.
The supplier reserves the right to modify specifications stated in this manual.
Trademarks Any brand names mentioned in this manual are registered trademarks of their
respective owners.
Liability The supplier accepts no liability for claims from third parties arising from
unauthorised use, use other than that stated in this manual, and use other than
in accordance with the General Conditions registered at the Chamber of
Commerce.
Refer further to the General Conditions. These are available on request, free of
charge.
Although considerable care has been taken to ensure a correct and suitably
comprehensive description of all relevant components, the manual may
nonetheless contain errors and inaccuracies.
Should you detect any errors or inaccuracies in the manual, we would be
grateful if you would inform us. This helps us to further improve our
documentation.
More information If you have any comments or queries concerning specific aspects related to the
water heater, then please do not hesitate to contact the supplier.
In the event of problems with your gas, electricity or water supply connections,
please contact the supplier/installation engineer of your installation.
4Instruction manual DR-LA
gis
Instruction manual DR-LA 5
Table of contents
1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
1.1 About the appliance - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7
1.2 What to do if you smell gas- - - - - - - - - - - - - - - - - - - - - - - - - 7
1.3 Regulations and documents - - - - - - - - - - - - - - - - - - - - - - - - 7
1.4 Target groups - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8
1.5 Maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.6 Notation conventions- - - - - - - - - - - - - - - - - - - - - - - - - - - - 9
1.7 Overview of this document - - - - - - - - - - - - - - - - - - - - - - - - 10
2 Working principle of the water heater - - - - - - - - - - - - - 11
2.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11
2.2 General working principle of the water heater - - - - - - - - - - - - - - - 11
2.3 Water heater operating cycle - - - - - - - - - - - - - - - - - - - - - - - 12
2.4 Protection for the water heater - - - - - - - - - - - - - - - - - - - - - - 13
2.5 Safety of the installation - - - - - - - - - - - - - - - - - - - - - - - - - 13
3 Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
3.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
3.2 Packaging - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
3.3 Ambient conditions - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15
3.4 Technical specifications - - - - - - - - - - - - - - - - - - - - - - - - - 17
3.5 Installation diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - 22
3.6 Vented water connections - - - - - - - - - - - - - - - - - - - - - - - - 23
3.7 Unvented water connections - - - - - - - - - - - - - - - - - - - - - - - 24
3.8 Gas connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 25
3.9 Chimney flue- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 25
3.10 Electrical connection - - - - - - - - - - - - - - - - - - - - - - - - - - - 27
3.11 Checking the supply pressure and burner pressure - - - - - - - - - - - - 29
4 Conversion to a different gas category - - - - - - - - - - - - 33
4.1 Conversion to different gas category DR-LA 30 through 95 - - - - - - - - 34
4.2 Conversion to different gas category DR-LA 110 - - - - - - - - - - - - - 36
5 Filling - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
5.1 Filling unvented installations - - - - - - - - - - - - - - - - - - - - - - - 42
5.2 Filling vented installations - - - - - - - - - - - - - - - - - - - - - - - - 42
6 Draining - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
6.1 Draining unvented installations - - - - - - - - - - - - - - - - - - - - - - 44
6.2 Draining vented installations - - - - - - - - - - - - - - - - - - - - - - - 44
7 The control panel- - - - - - - - - - - - - - - - - - - - - - - - 45
7.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.2 Control panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.3 Explanation of icons - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.4 ON/OFF switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.5 Control thermostat - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
7.6 Burner control reset button - - - - - - - - - - - - - - - - - - - - - - - - 45
7.7 Flue gas thermostat reset button - - - - - - - - - - - - - - - - - - - - - 45
gis
Table of contents
6Instruction manual DR-LA
8 Status of the water heater - - - - - - - - - - - - - - - - - - - 47
8.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
8.2 Operating modes - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
8.3 Error conditions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 47
9 Starting the water heater - - - - - - - - - - - - - - - - - - - - 49
9.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
9.2 Starting the appliance - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
9.3 The appliance's heating cycle - - - - - - - - - - - - - - - - - - - - - - - 49
10 Shutting down - - - - - - - - - - - - - - - - - - - - - - - - - 51
10.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 51
10.2 Shut the appliance down for a brief period ('OFF' mode) - - - - - - - - - - 51
10.3 Isolating the appliance from the mains - - - - - - - - - - - - - - - - - - - 51
10.4 Shutting the appliance down for a long period - - - - - - - - - - - - - - - 51
11 Errors - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
11.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
11.2 Error conditions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 53
11.3 Troubleshooting table for general errors - - - - - - - - - - - - - - - - - - 54
11.4 Troubleshooting table - no hot water - - - - - - - - - - - - - - - - - - - 55
11.5 Troubleshooting table - 'insufficient hot water' - - - - - - - - - - - - - - - 57
12 Performing maintenance - - - - - - - - - - - - - - - - - - - - 59
12.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 59
12.2 Preparation for maintenance - - - - - - - - - - - - - - - - - - - - - - - 59
12.3 Water-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - 60
12.4 Gas-side maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 62
12.5 Finalising maintenance - - - - - - - - - - - - - - - - - - - - - - - - - - 62
13 Guarantee- - - - - - - - - - - - - - - - - - - - - - - - - - - - 63
14 Appendices - - - - - - - - - - - - - - - - - - - - - - - - - - - 65
14.1 Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 65
14.2 Electrical diagrams DR-LA - - - - - - - - - - - - - - - - - - - - - - - - 66
Instruction manual DR-LA 7
gis
1 Introduction
1.1 About the appliance This manual describes how to install, service and use the DR-LA appliance. The
DR-LA appliance is a gas-fired open boiler without fan. DR-LA appliances are
equipped with a flue gas backflow safeguard.
The DR-LA is an appliance of type B11BS.
The information in this manual applies to types: DR-LA 30, DR-LA 40,
DR-LA 45, DR-LA 60, DR-LA 75, DR-LA 95 and DR-LA 110.
The water heater has been manufactured and equipped in accordance with the
European standard for gas-fired storage water heaters for the production of
domestic hot water (EN 89). The water heaters are therefore compliant with the
European Directive for Gas Appliances, and are entitled to bear the CE mark.
Warning
Read this manual carefully before starting the water heater. Failure to read
the manual and to follow the printed instructions may lead to personal injury and
damage to the water heater.
1.2 What to do if you
smell gas
Warning
If you smell gas:
No naked flames! No smoking!
Avoid causing sparks! Do not use any electrical equipment or switch, i.e. no
telephones, plugs or bells!
Open windows and doors!
Shut off the mains gas supply valve!
Warn occupants and leave the building!
After leaving the building, alert the gas distribution company or your installation
engineer.
1.3 Regulations and
documents
Gas Safety Installations and Use Regulations 1998, (As amended). It is law
that all gas appliances are installed by competent persons, in accordance with
the above regulations. Failure to install appliances correctly could lead to
prosecution. It is in your own interest, and that of safety, to ensure that this law
is complied with.
The installation of the boiler MUST be in accordance with the relevant
requirements of the Gas Safety Regulations, Building Regulations, IEE
Regulations and the Water Supply (water fittings) Regulations.
0063
Introduction
8Instruction manual DR-LA
1gis
The installation should also be in accordance with any relevant requirements of
the HSE, local gas region and local authority and the relevant recommendations
of the following documents:
British Standards
BS 6891: Specification for installation of low pressure gas pipework of up to
28 mm (R1) in domestic premises (2nd family gas). For larger installations
see IGE/UP/2 below.
BS 6798: Specification for installation of gas-fired boilers of rated input not
exceeding 70 kW net.
BS 6644: Specification for installation of gas-fired hot water boilers of rated
inputs between 60 kW and 2 MW (2nd and 3rd family gases).
BS 6700: Specification for design, installation, testing and maintenance of
services supplying water for domestic use within buildings and their
curtilages.
BS EN 806-2: Specification for installations inside buildings conveying water
for human consumption. Part 2: Design.
BS 5546: Specification for installation of hot water supplies for domestic
purposes, using gas-fired appliances of rated input not exceeding 70 kW.
BS 5440: Installation and maintenance of flues and ventilation for gas
appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family
gases). Part 1: Flues. Part 2: Ventilation.
Institute of Gas Engineers and Managers Publications
IGE/UP/1 Soundness testing and purging of industrial and commercial gas
installations.
IGE/UP/1A Soundness testing and direct purging of small low pressure
industrial and commercial natural gas installations.
IGE/UP/2 Gas installation pipework, boosters and compressors on industrial
and commercial premises.
IGE/UP/10 Installation of gas appliances in industrial and commercial
premises. Part 1: flued appliances.
CIBSE Publications:- "CIBSE Guide"
Section B4 : Water Service Systems.
1.4 Target groups The three target groups for this manual are:
(end) users;
installation engineers;
service and maintenance engineers.
Symbols on each page indicate the target groups for whom the information is
intended. See the table.
Target group symbols
Symbol Target Group
(End) user
Installation engineer
Service and maintenance engineer
Instruction manual DR-LA 9
gis
Caution
This water heater is not intended for use by persons with reduced physical,
sensory or mental capacities, or who lack the necessary experience or
knowledge, unless the person responsible for their safety is supervising them or
has explained to them how the water heater should be used.
Caution
This water heater is not intended to be used by children. Always supervise
children, and ensure that they do not play with the water heater.
1.5 Maintenance A service should be carried out at least once a year, both on the water side and
on the gas side. Among other things, the service interval depends on the water
quality, the average burning time per day and the set water temperature.
Note
To determine the correct service interval, it is recommended to arrange for
the service and maintenance engineer to check the water heater on both the
water and gas side within three months following installation. Based on this
check, the best service interval can be determined.
Note
Regular maintenance extends the service life of the water heater.
Both the end user and the service and maintenance engineer are responsible
for regular maintenance. They will need to establish clear agreements on this.
Note
If the water heater is not regularly serviced, the warranty will become void.
1.6 Notation
conventions
The following notation is used in this manual:
Note
Important information.
Caution
Ignoring this information can lead to the water heater being damaged.
Warning
Failure to carefully read this information may lead to danger of personal
injury, and serious damage to the water heater.
Introduction
10 Instruction manual DR-LA
1gis
1.7 Overview of this
document
The table provides an overview of the contents of this document.
Contents of this document
Chapter Target groups Description
Working principle of the water
heater
This chapter describes the working principle of the
appliance.
Installation This chapter describes the installation activity to be
completed before you start the appliance for the first time.
Conversion to a different gas
category
This chapter describes how to convert the appliance to a
different gas category and/or family of gases.
Filling This chapter describes how to fill the appliance.
Draining This chapter describes how to drain the appliance.
The control panel This chapter describes the appliance's control panel, and
how to use it.
Status of the water heater This chapter describes the status (mode or condition) that
the water heater may have, and possible actions to take.
Starting the water heater This chapter describes how to start the water heater. The
general operating cycle of the water heater is also
described.
Shutting down This chapter describes how to decommission the water
heater for a brief or long period of time.
Errors This chapter is mainly intended for the installation
engineer and the service and maintenance engineer. It
describes appliance errors. A troubleshooting table of
possible features, causes and solutions is provided. End
users may also refer to this chapter for additional
information about the appliance.
Performing maintenance This chapter sets out the maintenance tasks to be carried
out.
Guarantee This chapter states the warranty terms and conditions.
Instruction manual DR-LA 11
gis
2 Working principle of
the water heater
2.1 Introduction This chapter covers the following topics:
General working principle of the water heater;
Water heater operating cycle;
Protection for the water heater;
Safety of the installation.
2.2 General working
principle of the water
heater
In this appliance, the cold water enters the bottom of the tank through the cold
water inlet (14). The heat of combustion is conducted to the water by the
combustion chamber (8) and heat exchanger (11). The heated tap water leaves
the tank through the hot water outlet (2). Once the appliance is completely filled
with water, it will constantly be under mains water pressure. When hot water is
drawn from the appliance, it is immediately replenished with cold water.
The gas required for combustion flows via the gas control valve (16) into the
manifold. Orifices are mounted in the manifold. The gas is injected into the
burner bars at pressure from these orifices (36). The burner bars together form
the burner tray. The injection of gas into the burner bars also draws in the
primary air required for combustion. The narrow opening in the orifice causes
the gas flow to accelerate. This in turn causes a partial vacuum. It is this partial
vacuum that draws in the air (the Venturi effect). Additional air is drawn in
through the opening in the burner tray.
The hot surface igniter (20) ensures ignition of the gas/air mixture.
The flue gases released by this combustion are led through the flue tubes (part
of 11). Flue baffles (part of 11) are mounted in the flue tubes. These retard the
flow of the flue gases, thereby increasing the thermal efficiency of the appliance.
The flue gases are vented from the appliance via the draught diverter (33).
A radiation shield/condensation tray (35) is mounted below the burner tray. This
prevents overheating of the floor area below the appliance, as well as serving
as a collection tray for condensation water.
The insulation layer (24) prevents heat loss. The inside of the tank is enamelled
to protect against corrosion. The anodes (9) offer extra protection.
Working principle of the water heater
12 Instruction manual DR-LA
2gis
Cut-away view of the water heater
2.3 Water heater
operating cycle
The entire appliance is controlled by the burner control (40) and the control
thermostat (41) or frost thermostat (44). The control thermostat and frost
thermostat both independently measure the water temperature (Twater). The
appliance's heating cycle is activated as soon as Twater falls below the specified
threshold value (Tset). The value of Tset depends on the selected appliance
operating mode (8.2 "Operating modes"). If the appliance is in the 'OFF' mode
(frost protection), then this value is determined by the frost thermostat
(threshold value = 20°C). If the appliance is in the 'ON' mode, then the threshold
value is selectable via the control thermostat (± 40°C to ± 70°C).
As soon as Twater falls below Tset, the relevant thermostat (control or frost) will
close, and the burner control will register demand. The gas control valve (16) is
opened, and the gas is mixed with air. This mixture is ignited by the hot surface
igniter (20) and the water is heated. As soon as Twater gets higher than Tset, the
thermostat opens again. The demand will cease, and the burner control will stop
the heating cycle.
The thermostats have a certain margin both when closing and opening. We refer
to this margin as the hysteresis. The hysteresis cannot be adjusted.
Legend
Unused numbers are not
applicable
2. hot water outlet
6. control panel
8. combustion chamber
9. anode
10. tank
11. heat exchanger
12. inspection and cleaning
opening
14. cold water inlet
15. drain valve
16. gas control valve
20. hot surface igniter
21. flame probe
22. chimney pipe
24. insulation layer
33. draught diverter
34. flue gas sensor
35. radiation shield/
condensation tray
36. bar burners/burner tray
37. flue gas thermostat
38. safety thermostat sensor
39. high-limit thermostat sensor
40. burner control
41. control thermostat
42. high-limit thermostat
43. safety thermostat
44. frost thermostat
45. control thermostat sensor
46. frost thermostat sensor
22
39
46
2
40
38
45
6
41
42
43
44
20
21
14
36
11
33
9
37
34
24
10
12
8
15
35
16
IMD-0133 R2
Instruction manual DR-LA 13
gis
2.4 Protection for the
water heater
2.4.1 Introduction
The burner control monitors the water temperature by means of thermostats
and ensures safe combustion. This takes place using:
the Water temperature protection;
the Flue gas backflow safeguard;
the Flame probe.
2.4.2 Water temperature protection
By means of the frost, high-limit and safety thermostats, the burner control
monitors three temperatures that are important for safety. The table explains the
working principle of the thermostats with sensors.
Temperature protection
2.4.3 Flue gas backflow safeguard
The flue gases are discharged to the outside via the draught diverter (33) and
the flue (22). To prevent the flue gases from flowing back into the boiler room,
the discharge ducting is monitored by a feature called the Thermal Reflux
Safeguard (TRS). This uses a flue gas thermostat (37) with a flue gas
thermostat sensor (34) that are located in the draught diverter. Under normal
circumstances this sensor will register the ambient temperature.
However, if the chimney is not drawing sufficiently (for example, due to a
blockage in the chimney), the flue gases will 'reflux' and flow back past the flue
gas thermostat sensor. The sensor will then detect an excessive temperature
and the flue gas thermostat will open. The demand will cease, and the burner
control will immediately stop the heating cycle. The flue gas thermostat will also
lock out. It must be manually reset before the appliance can resume operation .
2.4.4 Flame probe
To ensure that no gas can flow when there is no combustion, the water heater
is fitted with a flame probe (21). The burner control uses the ionisation-detecting
properties of this probe for flame detection. The burner control closes the gas
valve the instant it determines that there is a gas flow but no flame is present.
2.5 Safety of the
installation
In addition to the appliance's standard built-in safety monitoring, the appliance
must also be protected by an expansion vessel, expansion valve, pressure
reducing valve, non-return valve and a T&P valve.
The use of an expansion vessel, expansion valve and/or pressure reducing
valve depends on the type of installation: unvented or vented.
Protection Description
Frost thermostat When the frost thermostat sensor (46) measures a temperature of 20°C or
less, the heating cycle (2.3 "Water heater operating cycle") will start.
High-limit thermostat When the high-limit thermostat sensor (39) measures a temperature higher
than 84°C, the high-limit thermostat will open. The heat demand is terminated
and the burner control halts the heating cycle until the high-limit thermostats
close once more. At that moment the burner control will reset the appliance and
the heating cycle will restart. The high-limit safeguard serves to prevent
overheating and/or excessive formation of scale in the appliance.
Safety thermostat When the safety thermostat sensor (38) measures a temperature higher than
93°C, the safety thermostat will open. The heat demand is terminated and the
burner control will immediately halt the heating cycle. The burner control will go
into a lockout error state. This must be manually reset before the appliance can
resume operation.
Working principle of the water heater
14 Instruction manual DR-LA
2gis
2.5.1 Inlet combination and pressure-reducing valve
In addition to the appliance's standard built-in safety monitoring, the appliance
must also be protected by an expansion vessel, expansion valve, pressure
reducing valve, non-return valve and a T&P valve.
The use of an expansion vessel, expansion valve and/or pressure reducing
valve depends on the type of installation: unvented or vented.
2.5.2 Unvented installation
With an unvented installation, an expansion valve valve and expansion vessel
prevent the buildup of excessive pressure in the tank. This prevents damage
being caused to the enamelled coating (in the appliance) or to the tank. A non-
return valve prevents excessive pressure buildup in the water supply system.
This valve also prevents water from flowing backwards from the tank into the
cold water supply system. The pressure reducing valve protects the installation
against an excessively high water supply pressure (> 8 bar). These components
are fitted to the cold water pipe (3.6 "Vented water connections").
2.5.3 Vented installation
With vented installation, excess pressure is taken up by the open cold water
head tank. The head height of the tank determines the working pressure in the
water heater, which may not exceed 8 bar. The installation must also be fitted
with a vent pipe from the hot water pipe (3.6.3 "Hot water side"), which opens
into the cold water tank.
2.5.4 T&P valve
A T&P valve is only mandatory in an unvented installation. However,
Hamworthy also recommends the use of a T&P valve in vented installations.
A T&P (Temperature and Pressure Relief) valve monitors the pressure in the
tank and the water temperature at the top of the tank. If the pressure in the tank
becomes excessive (> 10 bar) or the water temperature is too high (> 97°C), the
valve will open. The hot water can now flow out of the tank. Because the
appliance is under water supply pressure, cold water will automatically flow into
the tank. The valve remains open until the unsafe situation has been rectified.
The appliance is fitted standard with a connecting point for a T&P
valve (3.7.3 "Hot water side").
Instruction manual DR-LA 15
is
3 Installation
Warning
The installation should be carried out by a competent person in compliance
with the general and locally applicable regulations imposed by the gas, water
and power supply companies and the fire service.
The water heater may only be installed in a boiler room that complies with the
requirements stated in national and local ventilation
regulations (1.3 "Regulations and documents").
3.1 Introduction This chapter describes the installation activities to be carried out before the
appliance may be started up (9 "Starting the water heater"), in particular:
• Packaging;
Ambient conditions;
Technical specifications;
Vented water connections;
Unvented water connections;
Gas connection;
Chimney flue;
Electrical connection;
Checking the supply pressure and burner pressure.
For a possible conversion to a different gas category, see
conversion (4 "Conversion to a different gas category").
3.2 Packaging To avoid damaging the water heater, remove the packaging carefully.
We recommend unpacking the water heater at or near its intended location.
Caution
The water heater may only be manoeuvred in an upright position. Take care
that the water heater is not damaged after unpacking.
3.3 Ambient conditions Caution
The water heater may not be used in rooms where chemical substances are
stored or used due to the risk of explosion, and corrosion of the water heater.
Some propellants, bleaching agents and degreasing agents etc. disperse
vapours that are explosive and/or cause accelerated corrosion. If the water
heater is used in a room in which such substances are present, the warranty will
be void.
DR-LA appliances are open appliances and may only be installed in an open
boiler room. They are type B11BS.
3.3.1 Air humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. The table
shows the ambient conditions that must be adhered to for correct functioning of
the electronics present in the appliance to be guaranteed.
Air humidity and ambient temperature specifications
Air humidity and ambient temperature
Air humidity max. 93% RH at +25°C
Ambient temperature functionality: 0 < T < 60°C
Installation
16 Instruction manual DR-LA
3is
3.3.2 Maximum floor load
Allow for the appliance's weight and the maximum floor load; refer to the table.
3.3.3 Water composition
The appliance is intended for heating drinking water. The drinking water must
comply with the regulations governing drinking water for human consumption.
The table gives an overview of the specifications.
Water specifications
Note
If the water specifications deviate from those stated in the table, then the
tank protection cannot be guaranteed (13 "Guarantee").
3.3.4 Working clearances
For access to the appliance, it is recommended that the following clearances
are observed (see figure):
AA: around the appliance's control column and cleaning openings: 100 cm.
BB: all sides of the appliance: 50 cm.
Above the appliance (room to replace the anodes):
- 100 cm if using fixed anodes, or
- 50 cm if using flexible anodes.
If the available clearance is less than 100 cm, flexible magnesium anodes
may be ordered.
Note
When installing the appliance, be aware that any leakage from the tank
and/or connections can cause damage to the immediate environment or floors
below the level of the boiler room. If this is the case, the appliance should be
installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at least
5cm deep with a length and width at least 5cm greater than the diameter of the
appliance.
Weight of the appliance filled with water
DR-LA 30 DR-LA 40 DR-LA 45 DR-LA 60 DR-LA 75 DR-LA 95 DR-LA 110
504 kg 578 kg 507 kg 573 kg 522 kg 523 kg 581 kg
Water composition
Hardness
(alkaline earth ions)
> 1.00 mmol/l:
German hardness> 5.6° dH
French hardness > 10.0° fH
English hardness > 7.0° eH
•CaCO
3 > 100 mg/l
Conductivity > 125 µS/cm
Acidity (pH value) 7.0 < pH value < 9.5
Instruction manual DR-LA 17
is
Working clearances
3.4 Technical
specifications
The water heater is supplied without accessories. Check the
dimensions (3.4 "Technical specifications"), gas data (3.4.3 "Gas data") and
other specifications (3.4.2 "General and electrical specifications") of any
accessories you plan to use.
AA
AA
AA
IMD-0262 R2
Installation
18 Instruction manual DR-LA
3is
3.4.1 Dimensions of the water heater
Plan and elevation of the water heater
Legend
See the table.
10º
37º 45º
F
E
A
D
H
G
B
M
R
K
P
S
N
J
6
1
3
4
6
2
5
IMD-0135 R2
Instruction manual DR-LA 19
is
Dimensions (all measurements in mm unless otherwise indicated)
Size Description DR-LA 30 DR-LA 40 DR-LA 45 DR-LA 60 DR-LA 75 DR-LA 95 DR-LA 110
A Total height 1900 2100 1900 2040 2000 2025 2085
W Height of top of appliance 1760 1960 1760 1900 1795 1810 1870
D Appliance diameter 710 710 710 710 710 710 710
E Depth 800 800 800 800 800 800 800
F Width 1100 1100 1100 1100 1105 1105 1105
G Diameter of flue gas
discharge
150 150 180 180 225 225 225
H Heart appliance / heart
chimney flue
660 660 660 660 675 675 675
J Height of chimney flue 1840 2040 1840 1980 1935 1950 2010
K Height of gas connection 400 400 400 340 400 340 205
M Height of cold water supply 565 565 565 505 575 590 650
N Height of hot water outlet 1605 1810 1605 1750 1640 1655 1715
P Height of cleaning opening 730 730 730 670 740 765 855
R Height of drain valve
connection
500 515 500 455 525 540 595
S Height of T&P valve
connection
1550 1760 1550 1700 1595 1600 1660
1 Cold water supply
connection (male)
R11/2R11/2R11/2R11/2R11/2R11/2R11/2
2 Hot water outlet connection
(female)
Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2
3 Gas control valve
connection (female)
Rp3/4Rp3/4Rp3/4Rp3/4Rp3/4Rp3/4Rp1
4 Drain valve connection
(female)
Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2Rp11/2
5 T&P valve connection
(internal)
1 - 11.5
NPT
1 - 11.5
NPT
1 - 11.5
NPT
1 - 11.5
NPT
Rp11/2Rp11/2Rp11/2
6 Cleaning/inspection
opening
Ø 100 Ø 100 Ø 100 Ø 100 Ø 100 Ø 100 Ø 100
Installation
20 Instruction manual DR-LA
3is
3.4.2 General and electrical specifications
General and electrical specifications
DESCRIPTION Unit DR-LA 30 DR-LA 40 DR-LA 45 DR-LA 60 DR-LA 75 DR-LA 95 DR-LA 110
Volume litres 324 374 312 351 291 265 264
Maximum operating
pressure
bar8888888
Empty weight kg 195 221 209 238 244 270 329
Heating-up time
ΔT=45°C
minutes 32 28 20 18 13 9 8
Number of anodes - 2 2 2 3 3 4 4
Number of bar
burners/orifices
- 3457796
Number of flue
tubes/flue baffles
- 5679121617
Electrical power
consumption
W 30303030303060
Supply voltage
(-15% +10% VAC)
volts 230 230 230 230 230 230 230
Mains frequency Hz (± 1Hz) 50 50 50 50 50 50 50
IP class - 30 30 30 30 30 30 30
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68