Beckett CF2300 Oil Burner Owner's manual

Type
Owner's manual
R.W. Beckett Corporation
P.O. Box 1289
Elyria, Ohio 44036
(800)645-2876 • FAX (440)327-1064
Add Control for Lo/Hi/Lo Operation &
Add a Low Fire Hold Aquastat.
SAVE
ENERGY
& PROTECT
YOUR BOILER.
140° F
L4006B
or
L6006A
(Limit
Switch)
155° F
160° F
170° F
10° Dif.
L4006A
180° F
25° Dif.
L4006A
or
L4081A
(Low Side)
220° F
L4006E
or
L4081A
(High Side)
140° F
L4006B
or
L6006A
(Limit
Switch)
3 PSI Set
3 PSI Dif.
PA404A
(Instead of
L404F)
4 PSI
5 PSI Set
1 PSI Dif.
L404F
6 PSI Set
3 PSI Dif.
L404F
10 PSI Set
L4079B
High Limit
turns burner off
if operating control fails -
Manual Reset Required.
Operating Control turns
burner off (Setpoint)
High/Low Control switches
to low fire rate on pressure or
temperature rise.
High/Low Control switches
to high fire rate on pressure or
temperature fall.
Operating Control starts burner
on pressure or temperature fall
(Setpoint minus differential)
Low Fire Hold Aquastat
releases burner from low fire
rate on warm-up from cold.
Typical Honeywell Control
Device and Settings
Function
Steam
RM7897C
JR1 *
6
7
10
8
9
F
G
21
4
L2
DETECTOR
TRANS
GV1
GV2
LFHA
H/L
LFHS
1
2
3
A
LA
DM
2
1
5
6
N
2
3
4
LA
MC
HIGH FIRE ON
MOTOR
MC
L1 L2
LINE VOLTAGE SERVICE 120V 60 Hz
FROM FUSED DISCONNECT
SUPPLIED BY INSTALLER
HIGH GAS
PRESSURE
LOW GAS
PRESSURE
LWCO-P
LWCO-S
HIGH
LIMIT
OPERATING
CONTROL
L
B
K
D
E
B
B
K
D
K
H
J
M
C
A
A
A
A
A
BK
BK
BL
OR
OR
0 1
P
5
SWITCH
AIR PROVING
G GG
L
A
20
Hot Water
PSI
°F
Typical Wiring Schematic
R.W. Beckett Corporation Form 61682 R02, Printed in the USA 01/09
  • Page 1 1
  • Page 2 2

Beckett CF2300 Oil Burner Owner's manual

Type
Owner's manual