ABB Relion RER615 Operating instructions

Type
Operating instructions
RELION® PRODUCT FAMILY
Grid Automation
REC615 and RER615
DNP3 Communication Protocol
Manual
Document ID: 1MRS758757
Issued: 2018-08-31
Revision: A
Product version: 2.0
© Copyright 2018 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure
would create a risk for harm to property or persons (including but not limited to
personal injuries or death) shall be the sole responsibility of the person or entity
applying the equipment, and those so responsible are hereby requested to ensure that
all measures are taken to exclude or mitigate such risks.
This product has been designed to be connected and communicate data and
information via a network interface which should be connected to a secure network.
It is the sole responsibility of the person or entity responsible for network
administration to ensure a secure connection to the network and to take the necessary
measures (such as, but not limited to, installation of firewalls, application of
authentication measures, encryption of data, installation of anti virus programs, etc.)
to protect the product and the network, its system and interface included, against any
kind of security breaches, unauthorized access, interference, intrusion, leakage and/or
theft of data or information. ABB is not liable for any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2014/35/EU). This
conformity is the result of tests conducted by ABB in accordance with the product
standard EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in
accordance with the international standards of the IEC 60255 series.
Table of contents
Section 1 Introduction.......................................................................3
This manual........................................................................................ 3
Intended audience.............................................................................. 3
Product documentation.......................................................................4
Product documentation set............................................................4
Document revision history............................................................. 4
Related documentation..................................................................5
Symbols and conventions...................................................................5
Symbols.........................................................................................5
Document conventions.................................................................. 5
Section 2 DNP3 overview.................................................................7
DNP3 standard................................................................................... 7
Documentation................................................................................... 7
Section 3 Vendor-specific implementation....................................... 9
Protocol server instances................................................................... 9
Connection to clients..................................................................... 9
Protocol server attachment to a client......................................... 10
Several identical client connections.............................................10
Protocol data mapping to server instances................................. 11
Link modes....................................................................................... 11
Serial link mode........................................................................... 11
TCP/IP mode............................................................................... 12
Communication setup.......................................................................12
Communication modes................................................................12
DNP3 layer acknowledgements, retries and timeouts.................12
Polled mode.................................................................................13
Unsolicited reporting mode..........................................................13
Communication supervision and diagnostics.............................. 14
Communication supervision status.........................................14
Diagnostic communication counters.......................................15
Data objects......................................................................................15
Readable data objects.................................................................15
Class events................................................................................ 16
Writable data objects................................................................... 17
Control relay output block parameters................................... 17
Direct operate and select before operate............................... 17
Command blockings...............................................................18
Accessing of non-protocol-mapped data..................................... 18
Table of contents
REC615 and RER615 1
Communication Protocol Manual
Standard data object types ..............................................................19
Binary inputs................................................................................19
Double point inputs......................................................................20
Analog inputs...............................................................................20
Counter objects........................................................................... 21
Binary outputs and control relay output block..............................21
Control modes........................................................................ 22
Accessing of physical outputs................................................ 22
Control feedback.................................................................... 22
Analog outputs.............................................................................22
Fault records.....................................................................................23
Ev-Upd type objects.................................................................... 23
Record type objects.....................................................................23
Time stamp for record type objects............................................. 24
Additional fault record implementation details............................. 24
Troubleshooting................................................................................25
Section 4 DNP3 parameters...........................................................27
Parameter list................................................................................... 27
Monitored data..................................................................................30
Section 5 Glossary......................................................................... 31
Table of contents
2 REC615 and RER615
Communication Protocol Manual
Section 1 Introduction
1.1 This manual
The communication protocol manual describes a communication protocol supported
by the protection relay. The manual concentrates on vendor-specific
implementations.
1.2 Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering the communication setup in a
substation from a protection relay's perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
1MRS758757 A Section 1
Introduction
REC615 and RER615 3
Communication Protocol Manual
1.3 Product documentation
1.3.1 Product documentation set
Planning &
purchase
Engineering
Installation
Commissioning
Operation
Maintenance
Decommissioning,
deinstallation & disposal
Quick start guide
Quick installation guide
Brochure
Product guide
Operation manual
Installation manual
Connection diagram
Engineering manual
Technical manual
Communication protocol manual
IEC 61850 Engineering guide
Point list manual
GUID-7414985D-2433-46E4-B77B-CCE64F6FC8D0 V2 EN
Figure 1: The intended use of documents during the product life cycle
Product series- and product-specific manuals can be downloaded
from the ABB Web site http://www.abb.com/relion.
1.3.2 Document revision history
Document revision/date
Product version History
A/2018-08-31 2.0 First release
Download the latest documents from the ABB Web site
http://www.abb.com/substationautomation.
Section 1 1MRS758757 A
Introduction
4 REC615 and RER615
Communication Protocol Manual
1.3.3 Related documentation
Name of the document Document ID
Modbus Communication Protocol Manual 1MRS758758
IEC 60870-5-101/104 Communication Protocol Manual 1MRS758756
IEC 61850 Engineering Guide 1MRS757809
Engineering Manual 1MRS757810
Installation Manual 1MRS757799
Operation Manual 1MRS758754
Technical Manual 1MRS758755
Product-specific point list manuals and other product series- and product-specific
manuals can be downloaded from the ABB Web site
http://www.abb.com/substationautomation.
1.4 Symbols and conventions
1.4.1 Symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence of
a hazard which could result in corruption of software or damage to
equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand
that under certain operational conditions, operation of damaged equipment may result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all warning and caution notices.
1.4.2 Document conventions
A particular convention may not be used in this manual.
1MRS758757 A Section 1
Introduction
REC615 and RER615 5
Communication Protocol Manual
Abbreviations and acronyms are spelled out in the glossary. The glossary also
contains definitions of important terms.
The example figures illustrate the IEC display variant.
Menu paths are presented in bold.
Select Main menu/Settings.
LHMI messages are shown in Courier font.
To save the changes in nonvolatile memory, select Yes and press
.
Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
Parameter values are indicated with quotation marks.
The corresponding parameter values are "On" and "Off".
Input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
Section 1 1MRS758757 A
Introduction
6 REC615 and RER615
Communication Protocol Manual
Section 2 DNP3 overview
2.1 DNP3 standard
The DNP3 protocol was developed by Westronic based on the early versions of the
IEC 60870-5 standard telecontrol protocol specifications. Now the protocol
specification is controlled by the DNP Users Group at
www.dnp.org.
The ISO/OSI based model supported by this protocol specifies physical, data link and
application layers only. This reduced protocol stack is referred to as EPA. However,
to support advanced RTU functions and messages larger than the maximum frame
length as defined by the IEC document 60870-5-1, the DNP3 data link is intended to
be used with a transport pseudo-layer. As a minimum, this transport layer implements
message assembly and disassembly services.
2.2 Documentation
This implementation of DNP3 is fully compliant with DNP3 Subset Definition Level
2, and contains significant functionality beyond Subset Level 2.
1MRS758757 A Section 2
DNP3 overview
REC615 and RER615 7
Communication Protocol Manual
8
Section 3 Vendor-specific implementation
3.1 Protocol server instances
The word "client" refers to the protocol master. The protection relay is
referred to as "server" or a slave device.
The protection relay can communicate with several protocol clients simultaneously.
Furthermore, it is possible to configure the protection relay to provide different
protocol data and data outlook for different clients. A protocol server communication
entity which is configured to operate against a specific master or client is called an
instance.
There are three server instance scenarios.
1. One client - One protocol instance - One protocol mapping. The protection relay
is intended to operate toward one protocol client. The default protocol data
mapping or data outlook can be modified freely.
2. Several clients - Several protocol instances - One protocol mapping. The
protection relay is intended to operate toward several protocol clients. All the
clients should be able to access exactly similar data or similar data outlook. The
default protocol mapping or data outlook can be modified freely.
3. Several clients - Several protocol instances - Several protocol mappings. The
protection relay is intended to operate toward several protocol clients. Some or all
of the clients may want to access protocol data in a different manner. For this
purpose, several protocol mappings derived from the default protocol mapping
need to be prepared.
3.1.1 Connection to clients
In the protection relay, it is possible to activate up to five protocol server instances. A
function block represents the protocol on the protection relay’s application
configuration level. The block is named DNPLPRT1...5, depending on the instance in
use. For each connected client, an instance has to be activated by dragging the function
block to the configuration in the PCM600 Application Configuration tool.
DNPLPRT
STATUS
GUID-536D5DBA-B53F-475B-AD7D-25515895935C V1 EN
Figure 2: Function block
1MRS758757 A Section 3
Vendor-specific implementation
REC615 and RER615 9
Communication Protocol Manual
By default, instance 1 is always instantiated in the protection relay, but needs to be set
“On” to be activated. Since the protection relay’s native IEC 61850 data model
restricts client limit to five, the protection relay can have only five client connections
in total, regardless of the protocols to which the clients belong. This includes the MMS
clients and other communication protocol clients.
Protocol instances are identified with numbers 1...5. There are different and unique
setting and monitoring parameters for each instance in the HMI menu. Instance
numbers can be freely used. However, it is recommended to use the instances in the
numerical order. For example, instance 1 is to be used if there is only one client
connection and instances 1 and 2 when there are two clients.
3.1.2 Protocol server attachment to a client
After its activation, an instance should be attached to the intended client.
If the client is in a serial connection, the instance must be attached to the intended
serial port.
In case of a TCP client, the instance must be first attached to the physical Ethernet port.
If there are several TCP client connections, the protection relay must be able to
distinguish between the clients. There are two setting parameters in an instance.
Client IP: When the client makes the TCP connection, its IP address is checked.
This instance is given to the client with this IP address. It is also possible to use
the address “0.0.0.0” if no client IP address is to be defined. In this case, the
client's IP address is ignored.
TCP port: This parameter can be used in conjunction with the Client IP address
setting, thus allowing only a certain IP address at a specific TCP socket port
number.
3.1.3 Several identical client connections
If several clients access the same protocol data, the client connections must still be
kept apart. Also the number of each instance used for each client must be noted so that
if there are problems with the communication, the line diagnostic data for instances
follows the same instance number rule.
In case of sequential event data transaction and a TCP client connection, it is essential
that a reconnecting client is given back the same instance to which it was attached
before disconnecting. This way, the event reading resumes from the point where the
client left off, provided that no event overflow has occurred while the client was
absent. If multiple client connections are used, the distinguishing between different
client connections must be ensured by using the Client IP and TCP port parameters.
Section 3 1MRS758757 A
Vendor-specific implementation
10 REC615 and RER615
Communication Protocol Manual
3.1.4 Protocol data mapping to server instances
There are two different type of data mappings for the protocol. The mappings are
identified and numbered, starting from one. This number is not related to the protocol
instance number.
In PCM600, it is necessary to always define the mappings to be edited or viewed.
Each protocol instance has the setting parameter Mapping select, which defines the
protocol mappings to be used by this instance. Several protocol instances can use the
same mapping. By default, the Mapping select parameter for all the instances is set to
use the mapping number one.
Reboot the protection relay after changing the mapping number.
3.2 Link modes
DNP3 can be configured to operate in serial or Ethernet mode. The operation mode is
configured with the Port parameter.
3.2.1 Serial link mode
DNP3 serial can be assigned to a serial communication port in the protection relay.
Serial communication ports are named COM1...COMn, depending on how many
serial ports the protection relay hosts.
DNP3 protocol ignores any parity setting in the COM settings group. DNP3 is defined
as an 8 bit/no parity protocol with a 16-bit CRC every 16 bytes. These characteristics
are automatically configured by the protection relay's software when a serial port is
taken into use by DNP3. However, some characteristics of the serial port must be set:
baud rate, serial mode (RS-232, RS-485 2/4-wire) and fiber mode. They are located in
the serial port settings.
Configuration/Communication/COMn/Fiber mode
Configuration/Communication/COMn/Serial mode
Configuration/Communication/COMn/Baud rate
For the serial port parameter settings and hardware setup, see the
technical manual.
1MRS758757 A Section 3
Vendor-specific implementation
REC615 and RER615 11
Communication Protocol Manual
The COM port connection type, optical ST or EIA-485 connection,
star or loop topology, idle state (light on or light off) and the bias and
bus termination are selected with the COM port jumpers.
3.2.2 TCP/IP mode
DNP3 TCP/IP link mode is supported by the protection relay.
The protection relay listens for a connection from a DNP3 client on port specified by
the user. Default values for TCP port number range from 20000...20004 depending on
instance number. A different port can be selected with the TCP Port parameter.
DNP3 TCP/IP link mode and UDP broadcast are supported by the protection relay.
UDP broadcast requires that there is an active TCP connection by the client.
Documentation on DNP3 TCP/IP communication is available on
www.dnp.org.
3.3 Communication setup
3.3.1 Communication modes
DNP3 communication can be set up in two alternative modes.
Polled mode, called also “polled report by exception”. In this mode the DNP3
client always initiates the transaction with a read or write request to the DNP3
server. The server must reply with a response message.
Unsolicited mode, called also “Unsolicited reporting mode”. In this mode the
DNP3 server may spontaneously send changed class events to the client. The
client can yet make additional read or write requests to the server.
By default, DNP3 operates in polled mode. Unsolicited reporting mode can be
activated with the UR mode parameter.
3.3.2 DNP3 layer acknowledgements, retries and timeouts
It is possible to set up acknowledgements on both DNP3 link layer and application
layer. The settings should be equal on both the client and the server sides of the
communication. The timeouts must be set so that the other side has enough time to
prepare a positive acknowledgement. If an acknowledgement is received after the
configured timeout, it is discarded.
Confirmations, retries and timeouts can be configured via parameters.
Section 3 1MRS758757 A
Vendor-specific implementation
12 REC615 and RER615
Communication Protocol Manual
Configuration/Communication/DNP3.0/DNP3.0n/Data link confirm
Configuration/Communication/DNP3.0/DNP3.0n/Data link confirm TO
Configuration/Communication/DNP3.0/DNP3.0n/Data link retries
Configuration/Communication/DNP3.0/DNP3.0n/App layer confirm
Configuration/Communication/DNP3.0/DNP3.0n/App confirm TO
DNP3 link layer acknowledgements should not be used in TCP/IP link mode, since the
DNP3 message transport (link) is then encapsulated and secured by the Ethernet
protocol.
Link layer acknowledgements are seldom used in serial mode. The application layer
acknowledgements also cover the link layer acknowledgements. This means that if the
application message was successfully delivered, then the link layer must also have
been successful. Furthermore, it is easier to perform a whole application layer
retransmission rather than link layer retransmissions. Otherwise the application layer
timeout must be prepared to cover all the timeouts and retransmissions performed by
the link layer.
3.3.3 Polled mode
In the polled mode the client station initiates a connection and polls periodically for
static data (Class 0), and events (Class 1/2/3) from the server. Data must be polled
frequently enough, to prevent event overflow. If event overflow takes place, this is
indicated in the IIN bits in the response message. This means that events have been
lost.
3.3.4 Unsolicited reporting mode
Unsolicited mode can be enabled in the relay by the UR mode parameter. The
operating principle is that the server sends event data spontaneously to the client.
When the unsolicited mode has been activated by the setting parameter, the client
station must activate UR reporting by Enable unsolicited Application function (20).
After activation the server begins sending Class 1/2/3 events spontaneously.
Client must acknowledge unsolicited events reported by the server to ensure the
communication is fully operative. If the server does not receive acknowledgement in
time, defined by the UR TO and App confirm TO parameters, it does a count of resends
defined by the parameter UR retries. If the client station does not respond
acknowledgement during the count of retries, the server goes to offline mode. This
means that spontaneous events are not sent for a period of time. The length of this
period is defined by the parameter UR offline interval, (default 15 minutes). If it is not
wanted that the server goes to offline mode, limitless retries can be achieved by setting
the UR retries to “65535”.
Class event reporting can be buffered in the unsolicited mode by setting the
parameters UR Class x Min event and UR Class x TO. The event parameter UR Class
x Min defines how many events must be buffered in the device before unsolicited
report is sent out. The UR Class x TO parameter in turn defines the minimum waiting
1MRS758757 A Section 3
Vendor-specific implementation
REC615 and RER615 13
Communication Protocol Manual
time the device buffers events before sending them out, after occurrence of an event.
These parameters are useful for controlling the flow of events from the device and
combining them into bigger reports.
Legacy master UR provides compatibility to some older DNP3 clients. When set to
disabled, the server follows the DNP3 standard, sending its first unsolicited message
after a connection has been established following relay reboot. The client is expected
to send the Enable/Disable Unsolicited messages command to the relay. When Legacy
master UR is enabled, the relay does not send the initial unsolicited message.
Unsolicited responses are sent without the need of the Enable Unsolicited command.
The client still needs to open a connection for the server to start sending unsolicited
messages.
Unsolicited reporting mode is not recommended in half-duplex (RS-485 2-wire mode
or optical ST mode) serial bus due to possibility of collisions in the serial bus.
Especially in a system where event reporting is frequent, collisions can cause failed
DNP3 requests/responses and thus retransmissions. If unsolicited mode is used,
application level confirmations should be enabled to ensure that transmission is
successful. In half-duplex serial bus, polled mode is recommended.
3.3.5 Communication supervision and diagnostics
3.3.5.1 Communication supervision status
The DNP3 protocol provides a link to a keep-alive mechanism which can be used in
both Ethernet (TCP/IP) and serial communication modes. When the client has
successfully established connection to the protection relay, keep-alive messages are
sent periodically by the client or protection relay, depending on which one has a lower
keep-alive interval setting. Keep-alive timer is also restarted by any normal DNP3
frame, so keep-alive messages are only being transmitted after a longer idle time
between frames. In the protection relay, the keep-alive timeout can be set with the Link
keep-alive (seconds) parameter.
Default value “0” means that no keep-alive messages are sent by the protection relay.
Keep-alive requests sent by the client are still responded to. If a keep-alive message is
not responded to, the connection is considered broken. In case of TCP/IP connection
the protection relay closes the associated TCP socket connection, and a new
connection must be initiated by the client.
The DNP3 link status (True/False) is updated in the Monitoring data Status, which
also can be also used in Application Configuration tool in PCM600 for additional
logic connection, for example, to a LED. DNP3 link status exists separately for each
DNP3 protocol instance. True (value 1) means that the connection is active. False
(value 0) means the connection has timed out. The status can be found via
Monitoring/Communication/DNP3.0/DNP3.0n/Status.
On Application Configuration tool level, the DNP3 protocol instance is represented
by a function block DNPLPRTn, where n is the protocol instance number 1…5.
Section 3 1MRS758757 A
Vendor-specific implementation
14 REC615 and RER615
Communication Protocol Manual
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

ABB Relion RER615 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI