York YCWL Water Cooled Scroll Chiller User guide

Type
User guide
MODEL YCRL
REMOTE CONDENSER SCROLL LIQUID CHILLER
STYLE A
50 Through 170 Tons
175 Through 597 Kw
60Hz
R-410a
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
2
Nomenclature
Products are produced at a
facility whose quality-
management systems are
ISO9001 certified.
Approvals
ASME Boiler and Pressure Vessel Code –Section Vlll Division 1
c/U.L. – Underwriters Laboratory
ASHRAE 15 – Safety Code for Mechanical Refrigeration
ASHRAE Guideline 3 – Reducing Emission of Halogenated Refrigerants in Refrigeration and Air Conditioning
Equipment and Systems
N.E.C. – National Electrical Code
OSHA – Occupational Safety and Health Act
Performance data provided in this document was created in accordance with Johnson Controls software: YORKworks version
15.01 and DXCHILL version 6.16.
VOLTAGE CODE
17 = 200/3/60
28 = 230/3/60
46 = 380/3/60
50 = 380-415/3/50
58 = 575/3/60
YCRL 0118 S E 46 X A
STARTER
X = Across The Line Start
REFRIGERANT
R-410A
DESIGN
SERIES
UNIT DESIGNATOR
H = High Efficiency
S = Standard Efficiency
MODEL #
UNIT TYPE
YORK Water Cooled
Scroll Compressor
Condenser Unit
0064
0074
0084
0096
0118
0126
0156
0177
0198
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
3
Table of Contents
EQUIPMENT OVERVIEW ........................................................................................................................................ 5
MICROPROCESSOR CONTROLS ......................................................................................................................... 7
ACCESSORIES AND OPTIONS ........................................................................................................................... 10
REFRIGERANT FLOW DIAGRAM ........................................................................................................................ 12
DESIGN PARAMETERS ....................................................................................................................................... 13
SELECTION DATA ................................................................................................................................................. 15
UNIT COMPONENTS ............................................................................................................................................ 20
APPLICATION DATA ............................................................................................................................................. 22
RATINGS ................................................................................................................................................................ 24
PHYSICAL DATA ................................................................................................................................................... 26
ISOLATOR SELECTION DATA ............................................................................................................................. 27
ISOLATOR INFORMATION ................................................................................................................................... 28
SOUND DATA ........................................................................................................................................................ 31
UNIT DIMENSIONS ............................................................................................................................................... 32
SINGLE POINT ELECTRICAL DATA .................................................................................................................... 36
DUAL POINT ELECTRICAL DATA ....................................................................................................................... 38
ELECTRICAL NOTES ........................................................................................................................................... 40
GROUND WIRE SIZING ........................................................................................................................................ 41
TYPICAL CONTROL PANEL WIRING .................................................................................................................. 42
CUSTOMER WIRING INFORMATION .................................................................................................................. 46
GUIDE SPECIFICATIONS ..................................................................................................................................... 48
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
4
THIS PAGE INTENTIONALLY LEFT BLANK.
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
5
YORK YCRL Remote Condenser Liquid Chillers provide chilled water for all air condition-
ing applications that use central station air handling or terminal units. They are self-con-
tained and are designed for indoor (new or retrofit) installation. Each unit includes hermet-
ic scroll compressors, a liquid evaporator, and a user-friendly, diagnostic Microcomputer
Control Center all mounted on a rugged steel base. Remote condensers (model VDC) are
available separately from Johnson Controls. The units are produced at an ISO 9001 reg-
istered facility. The YCRL chillers are rated in accordance with AHRI Standard 550/590.
GENERAL
The chiller will be completely assembled with all interconnecting refrigerant piping and
internal wiring, ready for field connection to a remote condenser.
The unit will be pressure-tested, evacuated, and charged with a nitrogen holding charge,
and York ‘V’ (POE) synthetic oil.
The unit can be covered with an optional overspray coat of Caribbean Blue enamel. Units
are designed in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15
Safety Code for Mechanical Refrigeration. All units are produced at an ISO 9001 reg-
istered facility. All YCRL condensing units are rated in accordance with AHRI Standard
550/590 at AHRI conditions.
COMPRESSORS
The chiller has suction-gas cooled, hermetic, scroll compressors. The YCRL’s compres-
sors incorporate a compliant scroll design in both the axial and radial direction. All rotating
parts are statically and dynamically balanced. A large internal volume and oil reservoir
provides greater liquid tolerance. Compressor crankcase heaters are also included for
extra protection against liquid migration. All compressors are mounted on isolator pads to
reduce transmission of vibration to the rest of the unit.
REFRIGERANT CIRCUIT
Two independent refrigerant circuits will be furnished on each unit. All piping will be cop-
per with brazed joints. The liquid line will include: a shutoff valve with charging port; sight-
glass with moisture indicator; thermal expansion valve; solenoid valve; and high-absorp-
tion removable-core filter drier. The entire suction line and the liquid line between the
expansion valve and the cooler will be insulated with flexible, closed-cell, foam insulation.
POWER AND CONTROL PANELS
All controls and motor starting equipment necessary for unit operation shall be factory
wired and function tested. The panel enclosures shall be designed to NEMA 1 (IP 32) and
manufactured from powder-painted galvanized steel.
The Power and Control Panel shall be divided into a power section for each electrical
system, a common input section and a control section.
Equipment Overview
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
6
Each power panel shall contain: compressor starting contactors, control circuit serving
compressor capacity control, compressor contactor coils, and compressor motor over-
loads. The compressor motor overloads contain current transformers which sense each
phase, as an input to the microprocessor, to protect the compressor motors from damage
due to low input current, high input current, unbalanced current, single phasing, phase
reversal, and compressor locked rotor.
The common input section shall contain the control supply transformer providing 115V,
customer relay board and control circuit switch disconnect/emergency stop device.
Equipment Overview (Cont'd)
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
7
MICROPROCESSOR CONTROLS
The control section shall contain: On/Off rocker switch, microcomputer keypad and dis-
play, microprocessor board, I/O expansion board, relay boards, and 24V fused power
supply board.
The control display shall include: TFT Display with Light Emitting Diode backlighting for
outdoor viewing:
Two display lines
Twenty characters per line
Color coded 12-button non-tactile keypad with sections for
Display/Print of typical information:
Chilled liquid temperatures
System pressures (each circuit)
Operating hours and starts (each compressor)
Print calls up to the liquid crystal display:
Operating data for the systems
History of fault shutdown data for up to the last six fault shutdown conditions
An RS-232 port, in conjunction with this press-to-print button, is provided to permit
the capability of hard copy print-outs via a separate printer (by others).
Entry section to:
ENTER setpoints or modify system values
Setpoints updating can be performed to:
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Number of compressors
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Anti-coincident timer (delay compressor starts)
Microprocessor Controls
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
8
Unit section to:
Set time
Set unit options
The microprocessor control center is capable of displaying the following:
Return and leaving chilled liquid temperature
Low leaving liquid temperature cutout setting
English or Metric data
Suction pressure cutout setting
Each system suction pressure
Discharge pressure
Liquid Temperature Reset via a Building Automation System via a 4-20 milliamp input
or a 0-10 VDC input
Anti-recycle timer status for each system
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control
Lead system denition
Compressor starts & operating hours (each compressor)
Status of hot gas valves (if supplied)
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load & unload timer status
Microprocessor Controls (Cont'd)
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
9
The standard controls shall include: automatic pumpdown, run signal contacts, demand
load limit form external building automation system input, remote reset liquid temperature
reset input, unit alarm contacts, chilled liquid pump control, automatic reset after power
failure, automatic system optimization to match operating conditions.
The operating program software shall be stored in nonvolatile memory (EPROM) to elimi-
nate chiller failure due to AC power failure. Programmed setpoints are retained in lithium
battery-backed regulated time clock (RTC) memory for 5 years minimum.
COMMUNICATIONS
Native communication capability for BACnet (MS/TP) and Modbus
Optional communciation available for N2 and LON via eLink option
Microprocessor Controls (Cont'd)
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
10
Accessories and Options
All accessories and options are factory mounted unless otherwise noted.
POWER OPTIONS
Single Point Supply Terminal Block – The standard power wiring connection on all mod-
els is a single point power connection to a factory provided terminal block. Components
included are the enclosure, terminal–block and interconnecting wiring to the compressors.
Separate external protection must be supplied, by others, in the incoming power wiring.
Single Point Circuit BreakerAn optional unit mounted circuit breaker with external,
lockable handle (in compliance with N.E.C. Article 440–14), can be supplied to isolate the
power voltage for servicing.
Multiple Point Circuit Breaker – Optional multiple point supply with independent system
circuit breakers and locking external handles (in compliance with Article 440–14 of N.E.C.)
can be factory supplied.
Control Transformer – Converts unit power voltage to 115–1–60 (0.5 or 1.0 KVA capac-
ity). Factory mounting includes primary and secondary wiring between the transformer
and the control panel.
CONTROLS OPTIONS
Language LCD And Keypad – Standard display language and keypad is in English.
Spanish, French, German, and Italian are available as an option.
HEAT EXCHANGER OPTIONS
Flow SwitchAn optional flow switch can be factory supplied for the evaporator. Vapor–
proof SPDT, NEMA 3R switch, 150 PSIG (10.3 bar) DWP, 20°F to 250°F (–29°C to 121°C)
with 1” NPT (IPS) connection for upright mounting in horizontal pipe. The flow switch or its
equivalent must be furnished with each unit. (Field Mounted)
Differential Pressure SwitchAn alternative option to the paddle–type flow switch. 3–45
PSIG (0.2–3 bar) range with ¼” NPTE pressure connections. (Field Mounted)
Pressure Vessel Codes – Evaporator is supplied (Standard) in conformance with the
A.S.M.E. pres sure codes.
Flanges (ANSI/AWWA C–606 Couplings Type) – Consists of (2) flange adapters for
grooved end pipe on evaporator (note: the 0064HE units do not include evaporator flang-
es). Standard 150 PSIG (10.3 bar). (Field Kit, matching pipe flange by contractor.)
Double Thick Insulation – Doubled thickness (totalling 1–1/2” or 38mm) insulation pro-
vided on the evaporator
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
11
CHILLER OPTIONS
Final Paint Overspray – Overspray painting of unit after assembly.
Service Isolation Valve – Service suction isolation valve added to unit per system in ad-
dition to the standard discharge service valve.
Hot Gas By-Pass – Permits continuous, stable operation at capacities below the mini-
mum step of compressor unloading to as low as 5% capacity (depending on both the
unit and operating conditions) by introducing an artificial load on the evaporator. Hot gas
by–pass is installed on only refrigerant system #2 on two–circuited units.
Compressor Acoustic Sound Blanket – Each compressor is individually enclosed by
an acoustic sound blanket. The sound blankets are made with one layer of acoustical
absorbent textile fiber of 5/8” (15mm) thickness; one layer of anti–vibrating heavy mate-
rial thickness of 1/8” (3mm). Both are closed by two sheets of welded PVC, reinforced for
temperature and UV resistance.
VIBRATION ISOLATION
Rubber Isolators – Recommended for normal in stallations. Provides very good perfor-
mance in most applications for the least cost. (Field Installed)
1” Spring Isolators – Level adjustable, spring and cage type isolators for mounting under
the unit base rails. 1” nominal deflection may vary slightly by ap plication. (Field Installed)
2” Spring Isolators – Restrained Spring–Flex Mount ings incorporate a rugged welded
steel housing with vertical and horizontal limit stops. Housings designed to withstand a
minimum 1.0g accelerated force in all directions to 2”. Level adjustable, deflection may vary
slightly by application. (Field Installed)
Accessories and Options (Cont'd)
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
12
Refrigerant Flow Diagram
Low-pressure liquid refrigerant enters the evaporator tubes and is evaporated and super-
heated by the heat energy absorbed from the chilled liquid passing through the evapora-
tor shell. Low-pressure vapor enters the compressor where pressure and superheat are
increased. High-pressure vapor is passed through a remote condenser where heat is
rejected to the air flow passing through the coil. The fully condensed and subcooled liquid
leaves the condenser and enters the expansion valve, where pressure reduction and fur-
ther cooling take place. The low pressure liquid refrigerant then returns to the evaporator.



FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
13
Design Parameters
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact the nearest Johnson Controls Ofce for application requirements.
2. For leaving water temperature higher than 50°F (10°C), contact the nearest Johnson Controls Ofce for application guidelines.
DESIGN PARAMETERS
YCRL
EVAPORATOR FLOW
(GPM)
LEAVING
EVAPORATOR
WATER TEMP. °F (C°)
MIN SAT.
DISCH.
TEMP. °F
(C°)
MAX. SAT
DISCH
TEMP °F
(C°)
EQUIPMENT ROOM
TEMP. °F (C°)
MIN MAX MIN
1
MAX
2
MIN MAX MIN MAX
0064HE 100 355 40 50 80 130 40 115
0074HE 140 625 40 50 80 130 40 115
0084HE 140 625 40 50 80 130 40 115
0096HE 150 625 40 50 80 130 40 115
0118HE 140 625 40 50 80 130 40 115
0126HE 200 650 40 50 80) 130 40 115
0156HE 200 650 40 50 80 130 40 115
0177SE 200 650 40 50 80 130 40 115
0198SE 200 650 40 50 80 130 40 115
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
14
EVAPORATOR YCRL
A 0064HE
B 0074HE, 0084HE, 0118HE,
C 0096HE
D 0126HE, 0156HE, 0177SE, 198SE
1.0
10.0
100.0
10 100 1000
C
B
D
A
YCRL Evaporator Pressure Drop (English)
Water Flow Rate (GPM)
Pressure Drop (ft. H
2
O)
LD18634
1.0
10.0
100.0
1000.0
1.0 10.0 100.0
D
B
A
C
YCRL Evaporator Pressure Drop (SI)
Water Flow Rate (l/s)
Pressure Drop (kPa)
LD18635
Design Parameters (Cont'd)
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
15
GUIDE TO SELECTION
Complete water chilling capacity ratings for YORK YCRL condensing units are shown on
the following pages to cover the majority of job requirements. For any application beyond
the scope of this Engineering Guide, consult your nearest Johnson Controls office.
SELECTION RULES
1. Ratings - All YCRL ratings are in accordance with AHRI Standard 550/590, at the AHRI
standard condi tions. Ratings not at standard AHRI conditions are rated in accordance
with AHRI rating procedures. These ratings may be interpolated but extrapolated.
2. Cooling Water Quantity - Ratings are based on 10ºF chilled water range with the
evaporator at sea level. Use the chilled water correction factors (below) for other
ranges except as limited by water pressure drop, minimum or maximum water ows
for the evaporator.
3. Fouling Factors – Ratings are based on 0.0001 evaporator fouling factor. For other
fouling factors, consult the table below or contact your Johnson Controls represen-
tative.
EVAPORATOR CORRECTION FACTORS
FF=TEMP SPLIT
0.00010 0.00025
TONS COMPR KW TONS COMPR KW
6 0.976 0.996 0.969 0.997
8 0.990 0.999 0.960 0.996
10 1.000 1.000 0.991 0.999
12 1.009 1.001 0.999 1.000
14 1.017 1.002 1.007 1.001
4. Ethylene Glycol Correction Factors – The following factors are to be applied to
the standard ratings for units cooling ethylene glycol.
ETHYLENE GLYCOL
%WEIGHT TONS
COMPR
KW
GPM
PRESS
DROP
FREEZE
POINT
10 0.993 1.002 1.029 1.095 26
20 0.980 1.004 1.040 1.191 18
30 0.964 1.007 1.055 1.302 7
40 0.945 1.009 1.071 1.435 -8
50 0.922 1.013 1.091 1.599 -29
5. Propylene Glycol Correction Factors – The following factors are to be applied to
the standard ratings for units cooling propylene glycol.
PROPYLENE GLYCOL
%WEIGHT TONS
COMPR
KW
GPM
PRESS
DROP
FREEZE
POINT
10 0.985 1.002 1.003 1.078 28
20 0.968 1.005 1.000 1.157 19
30 0.937 1.008 0.992 1.288 9
40 0.898 1.012 0.982 1.414 <1
50 0.862 1.019 0.985 1.605 -28
Selection Data
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
16
Selection Data (Cont'd)
METHOD OF SELECTION
If the duty requires a 10ºF (6°C) range on the evaporator, see “Ratings”. For water ranges
other than 10ºF (6°C), use the following procedure. Line sizes can be determined by re-
viewing York DX Piping Guide 050.40-ES2.
1. Determine capacity required from the following formula:
Capacity (Tons) =
GPM x Chilled Water Range (°F)
24
2. After applying any fouling factor corrections, the actual condenser heat rejection
may be determined as follows:
Heat Rejection (MBH) =
Heat Rejection (Btuh)
1000
= (Tons x 12) = (kW x 3.415)
3. Size condenser using manufacturer’s recommendations.
SAMPLE SELECTION
Water Cooled Chiller (YCRL)
GIVEN – Chill 200 GPM of water from 56ºF to 44ºF and 0.0001 evaporator fouling factor
with 125°F saturated discharge temperature.
FIND – The required unit size capacity, kW, EER, and water pressure drop, and the con-
denser MBH heat rejection.
SOLUTION:
1. Chilled water range = 56ºF - 44ºF = 12ºF and correction factors are 1.009 for Tons
and 1.001 for kW for the evaporator.
Capacity (Tons) =
GPM x Chilled Water Range (°F)
24
=
200 x 12
= 100TR
24
2. From the rating, a model YCRL0118HE has a capacity range required. For the
evaporator leaving water temperature of 44ºF and a saturated discharge tempera-
ture of 125°F, the unit capacity rating table indicates:
Tons = 101.7
KW = 110.0
EER = 11.1
Correcting for the 12ºF chilled water range:
Tons = 101.7 x 1.009 = 102.6 TR
KW = 110.0 x 1.001 = 110.1 kW
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
17
Selection Data (Cont'd)
3. Determine the average full load kW and EER at 100 Tons
100
x (110.1) = 107.3
102.6
EER =
Tons x 12
=
100 x 12
= 112
kW 107.3
4. Determine the condensing Heat rejection as follows:
Heat Rejection (MBH) = (Tons x 12) + (kW x 3.415)
= (102.6 x 12) + (110.1 x 3.415)
= 1231.2 + 376.0
= 1607.2
5. From "Pressure Drop Curves" on page 17, locate the pressure drops with 200 GPM
through the evaporator of the Model YCRL118HE:
Evaporator Pressure Drop at 200 GPM = 8 ft
The unit is suitable.
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
18
Selection Data (Cont'd)
REFRIGERANT PIPING
General – When the unit has been located in its final position, the unit piping may be con-
nected. Normal installation precautions should be observed in order to receive maximum
operating efficiencies. System piping should conform to the York DX Piping Guide form
050.40-ES2 or ASHRAE refrigeration handbook guidelines. All piping design and instal-
lation is the responsibility of the user.
JOHNSON CONTROLS ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM
OPERATION OR FAILURES DUE TO IMPROPER PIPING OR PIPING DESIGN.
All filter driers, sight glasses, expansion valves and liquid line solenoid valves are fac-
tory installed on each refrigerant circuit. Interconnecting refrigerant piping and refrigerant
charge are supplied and installed by others.
Table 1 lists refrigerant line connections sizes per unit model number.
TABLE 1 - YCRL LINE CONNECTION SIZES
YCRL
LIQUID LINE
SYSTEM 1, IN.
LIQUID LINE
SYSTEM 2, IN.
DISCHARGE LINE
SYSTEM 1, IN.
DISCHARGE LINE
SYSTEM 2, IN.
0064HE 7/8 7/8 1-3/8 1-3/8
0074HE 1-1/8 7/8 1-5/8 1-3/8
0084HE 1-1/8 1-1/8 1-5/8 1-5/8
0096HE 1-1/8 1-1/8 1-3/8 1-3/8
0118HE 1-1/8 1-1/8 1-5/8 1-5/8
0126HE 1-1/8 1-1/8 2-1/8 2-1/8
0156HE 1-1/8 1-1/8 2-1/8 2-1/8
0177SE 1-1/8 1-1/8 2-1/8 2-1/8
0198SE 1-1/8 1-1/8 2-1/8 2-1/8
REFRIGERANT LINE SIZING
Refrigerant piping systems must be designed to provide practical line sizes without exces-
sive pressure drops, prevent compressor oil from being “trapped” in the refrigerant piping,
and ensure proper flow of liquid refrigerant to the thermal expansion valve. Be sure to
review form 050.40-ES2. Considerations should be given to:
1. Discharge line pressure drop due to refrigerant ow.
2. Discharge line refrigerant velocity for oil return.
3. Liquid line pressure drop due to refrigerant ow.
4. Liquid line pressure drop (or gain) due to vertical rise of the liquid line.
To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line
pressure drop should never exceed 40 PSIG (2.8 barg). Refrigerant vapor in the liquid line
will measurably reduce valve capacity and poor system performance can be expected.
To allow adequate oil return to the compressor, discharge risers should be sized for a
minimum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to
ensure oil return up the suction riser.
FORM 150.27-EG1 (1115)
JOHNSON CONTROLS
19
Selection Data (Cont'd)
Chiller Below Condenser – On a system where the chiller is located below the condens-
er, the discharge line must be sized for both pressure drop and oil return. In some cases
a double discharge riser must be installed to ensure reliable oil return at reduced loads.
Condenser Below Chiller – When the condenser is located below the chiller, the liquid
line must be designed for both friction loss and static head loss due the vertical rise. The
value of static head loss of 5 PSI/ft. (3.4 kPa/30 cm) must be added to the friction loss
pressure drop in addition to all pressure drops due to driers, valves, etc.
OIL TRAPS
All horizontal discharge lines should be pitched at least 1/4” per foot (2 cm/m) in the direc-
tion of the refrigerant flow to aid in the return of oil to the chiller. All discharge lines with
a vertical rise exceeding 3 feet (.91 meters) should have a “P” trap at the bottom and top
of the riser. Discharge lines with a vertical rise exceeding 25 feet (7.6 meters) should be
trapped every 15 feet (4.6 meters).
REFRIGERANT CHARGE
The chiller is charged and shipped with a dry nitrogen holding charge. The operating
charge for the chiller, remote condenser and refrigerant piping must be weighed in after all
refrigerant piping is installed, leak checked, and evacuated. Final adjustment of refriger-
ant charge should be verified by subcooling values (refer to IOM section on Pre-Startup
for checking subcooling).
REFRIGERANT PIPING REFERENCE
For more details, refer to ASHRAE Refrigeration Handbook, Chapter 2.
TABLE 2 - YCRL CHILLER CHARGES
YCRL
TOTAL HFC-410A CHARGE,
LBS
PER SYSTEM, LBS
0064HE 34 17
0074HE 40 20
0084HE 82 41
0096HE 106 53
0118HE 90 45
0126HE 126 63
0156HE 126 63
0177SE 122 63/59
0198SE 126 63
JOHNSON CONTROLS
FORM 150.27-EG1 (1115)
20
Unit Components
SINGLE SPEED SCROLL
COMPRESSORS
POWER PANEL
EVAPORATOR
FORMED STEEL
BASE RAILS
LIQUID LINE
STUB-OUT
FILTER
DRIERS
LIQUID
LINE
SOLENOID
VALVE
CONTROL PANEL
WITH KEYPAD AND
DISPLAY
SIGHT
GLASS
TXV
VALVE
ISOLATION VALVES
(OPT)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54

York YCWL Water Cooled Scroll Chiller User guide

Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI