  • Hello! I am an AI chatbot trained to assist you with the Roger MCX402-BRD Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Roger Access Control System
MCX402-BRD I/O expander
Operating Manual
Product version: 1.0
Firmware version: 1.0.2.255
Document version: Rev. C
MCX402-BRD Operating Manual 08.10.2020
2/11
Design and application
The MCX402-BRD is I/O expander dedicated to the RACS 5 system. The device is connected to MC16
access controller to provide control of 1 or 2 doors with Wiegand or PRT (RACS CLK/DTA) readers but in
case of PRT readers new firmware must be uploaded to the expander. The expander offers eight NO/NC
inputs, two relay outputs, two transistor outputs, 1.0A main power supply output and 0.2 auxiliary power
supply output. All outputs of the expander are protected against overload. MCX402-BRD is supplied from
18VAC and it offers 13.8VDC at AUX and TML outputs to supply all door devices including door lock and
readers. The expander can be equipped with backup battery.
The expander is offered individually as electronic module or as a component of MCX402-1-KIT for read-
in/out door control or as a component of MCX402-2-KIT for two read-in doors control.
In case of upgrade from RACS 4 to RACS 5 system, PR411 and PR402 controllers can be converted into
MCX402 expanders by upload of new firmware.
Characteristics
RS485 interface for communication with MC16 access controller
Wiegand 26-66bit interface for communication with two readers of third party
RACS CLK/DTA interface for communication with two PRT series readers
8 inputs NO/NC
Relay output NO/NC 1,5A/30V
Relay output NO/NC 5A/230VAC
2 transistor outputs 1A/15VDC
Power output 13.8VDC/1.0A
Power output 13.8VDC/0.2A
18VAC, 12VDC or 24VDC power supply
Battery charging with 0.3A current
Protection against full battery discharge
Reporting of power supply status to access controller
Fig. 1 General concept of MCX402-BRD application
MCX402-BRD Operating Manual 08.10.2020
3/11
Fig. 2 MCX402-BRD application in single read-in/out door control (A) and two read-in doors control (B)
Power supply and backup battery
MCX402-BRD expander is designed for power supply from 230VAC/18VAC/40VA transformer and then it
offers 13.8VDC power outputs (AUX, TML) for external devices. Optionally the expander can be supplied
from 12VDC or 24VDC but in case of 12VDC the backup battery cannot be directly connected to the
expander thus the emergency power supply must be provided by external PSU.
Note: Expander cannot be started using only power supply from backup battery.
Fig. 3 MCX402-BRD supply from 18VAC
MCX402-BRD Operating Manual 08.10.2020
4/11
Fig. 4 MCX402-BRD supply from 12VDC or 24VDC
Connection to RS485 communication bus
MCX402-BRD is an addressable device and it must be connected to RS485 communication bus of the
controller where MCT readers and other MCX expanders are usually also operated. Prior to connection, the
expander must be assigned unoccupied address in range of 100-115. Any topology of communication bus
can be used (e.g. star, tree). The matching resistors (terminators) connected at the ends of transmitting
lines are not required. In most cases communication works with any signal cable e.g. U/UTP cat.5. All
devices connected to the same bus should have GND terminals connected. The RS485 communication
standard in RACS 5 system guarantees proper communication in a distance of up to 1200 meters as well as
high resistance to interferences.
IN1-IN8 inputs
The expander offers 8 inputs IN1-IN8 which can be configured as NO or NC. Electric parameters of all
inputs are configured within low level configuration by means of RogerVDM software. Inputs are assigned
with functions using VISO management software.
IO1 and IO2 outputs
The expander offers two open collector type transistor outputs IO1 and IO2. Output polarity can be
configured as normal or reversed. Output with normal polarity represents high impedance in normal state
and is shorted to ground when triggered. Output with reversed polarity operates with inverted logic. It is
shorted to ground in normal state and represents high impedance when triggered. The configuration of
output polarity is done within low level configuration using RogerVDM software. By default, outputs are
configured with normal polarity. Outputs are assigned with functions using VISO management software.
REL1 and REL2 outputs
The expander offers two relay outputs REL1 and REL2. Each relay offers NO/NC terminals and REL1 is
30V/1.5A rated while REL2 is 230VAC/5A rated. In case of power outage both relays remain in the off state.
Outputs are assigned with functions using VISO management software.
AUX power output
AUX power supply output is dedicated to supply door lock, alarm signalling device and other door related
devices. The terminal AUX is protected with 1.0A electronic fuse.
TML power output
TML power supply output is dedicated to supply readers at doors. The terminal TML+ is protected with 0.2A
electronic fuse.
Door control
The expander offers power supply at door and enables the operation of PRT (RACS CLK/DTA) or Wiegand
readers with MC16 access controller. The expander offers 1.0A power output (AUX), 0.2A power output
(TML), RACS CLK/DTA communication bus and programmable inputs/outputs which can be used to control
door lock, communication with Wiegand readers and control of LEDs and buzzer of Wiegand readers. The
1.0A output is dedicated to supply door lock and door related devices (e.g. alarm signalling device). The
MCX402-BRD Operating Manual 08.10.2020
5/11
0.2A output is dedicated to supply readers. In the figure below a typical read-in/read-out door control
scenario with MCX402-BRD expander is presented. The door system is supplied from the expander and it
includes:
2 x PRT (RACS CLK/DTA) or 2 x Wiegand 26-66bit readers
12VDC door lock
12VDC alarm signalling device
Door contact
Exit button
Fig. 5 Typical scenario of operation for read-in/read-out door with PRT readers (A) and Wiegand readers (B)
Connection of expander to controller
The expander is not operated as standalone device but as an extension of MC16 access controller. It is
recommended to supply the MCX402-BRD from own transformer and equip it with backup battery. All
devices connected to the same RS485 bus should have GND terminals connected. Such connection can be
ensured with any wire. The maximal length of RS485 bus between MC16 controller and the expander
equals to 1200m. MCX402-BRD expander is usually installed near controlled door.
Fig. 6 Connection diagram for MC16 controller and expander
MCX402-BRD Operating Manual 08.10.2020
6/11
Device configuration
The expander is configured within low level configuration by means of RogerVDM software. Such
configuration must be done prior to connection to MC16 access controller particularly in regard of RS485
address and reader parameters. The address of expander can also be programmed manually with jumpers
on expander’s board. The address programmed with jumpers (hardware address) has higher priority than
the address programmed with RogerVDM (software address). The factory new expander has ID=100
software address.
Addressing with jumpers
Every time the address is modified, the expander must be restarted with RST button or switching power
supply off and on.
Fig. 7 Manual addressing with jumpers on expander’s board
Low level configuration with RogerVDM software
Fig. 8 Connection of expander to RUD-1 interface
Connect the expander to RUD-1 interface as indicated in Fig.8.
Run RogerVDM program and select MCX v1.x device, firmware version, RS485 communication
channel and communication port (COM) emulated by RUD-1 interface.
Click Connect and program will display main configuration window with parameters read from the
connected device.
MCX402-BRD Operating Manual 08.10.2020
7/11
Set device address (100-115) and other configuration parameters.
Click Send to device to upload modified configuration parameters to the connected device.
Optionally, save configuration parameters to file using Save to file button.
Disconnect programmed device from RUD-1 interface.
When low level configuration is finished then the expander can be connected to access controller in order to
make functional configuration with VISO management software.
Configuration parameters
In the table below the configuration parameters of MCX402-BRD expander are presented. All settings are
programmed with RogerVDM software within low level configuration of the expander.
Configuration parameters
Parameter
Function
Communication settings
RS485 Address
Parameter defines device address on RS485 bus. Range: 100-115.
Default value: 100
RS485 communication timeout [s]
Parameter defines delay after which device will signal lost
communication with controller. Range: 0-64s. When set to 0 then
signalling is disabled. Default value: 10 s.
General
Single key press**
When option is enabled then reader transmits the whole PIN to
controller. When option is disabled then reader transmits every
pressed key separately. Range: Yes, No. Default value: Yes.
Min. PIN length
Parameter defines minimal number of digits in PIN. Range: 0-8.
When set to 0 then PIN is disabled. Default value: 4.
Max. PIN length
Parameter defines maximal number of digits in PIN. Range 0-8.
When set to 0 then PIN is disabled. Default value: 8.
[*] clears PIN buffer
When option is enabled then [*] key pressing clears PIN buffer.
Range: Yes, No. Default value: Tak
Time between keys in PIN [s]
Parameter defines max. time between two consecutive key
pressings. Range: 1-64. Default value: 20.
PIN followed by [#] key
When option is enabled then PIN must be followed with [#] key.
Range: Yes, No. Default value: Yes.
AC return timeout [min.]
Parameter defines time after which return of AC supply is reported.
Range: 0-250. When set to 0 then signalling is disabled. Default
value: 2.
AC lost delay [min.]
Parameter defines time after which loss of AC supply is reported.
Range: 0-250. When set to 0 then signalling is disabled. Default
value: 10.
Battery test period [min.]
Parameter defines time between battery tests. Range: 0-250.
When set to 0 then testing is disabled. Default value: 10.
Input types
IN1-IN8
Parameter defines the type of input line. When Wiegand readers
are enabled then inputs IN1-IN4 are reserved for such readers.
Input comments
IN1-IN8
Parameter defines any text or comment which corresponds to the
object. It is later displayed in VISO program.
Output polarity
MCX402-BRD Operating Manual 08.10.2020
8/11
REL1,REL2
Parameter defines the polarity of output line. Output with normal
polarity represents high impedance in normal state and is shorted
to ground when triggered. Output with reversed polarity operates
with inverted logic. It is shorted to ground in normal state and
represents high impedance when triggered. Range: [0]: Normal
polarity, [1]: Reversed polarity. Default value: 0
IO1, IO2
as above
Output and power supply comments
REL1, REL2
Parameter defines any text or comment which corresponds to the
object. It is later displayed in VISO program.
IO1,IO2
as above
PWR
as above
Device comment
DEV
as above
Wiegand Terminal 1/2*
Terminal enabled
When option is enabled then Wiegand Terminal 1/2 is operated.
Range: Yes, No. Default value: Yes.
Keypad enabled
When option is enabled the keypad on Wiegand Terminal 1/2 is
operated. Range: Yes, No. Default value: Yes.
Card type
Parameter defines the data type of the card returned by terminal.
Default value: [16]: Number 40bits.
Card class
Parameter defines the class of the card returned by terminal.
Default value: [2]: EM.
KBD comment
Parameter defines any text or comment which corresponds to the
object. It is later displayed in VISO program.
CDI comment
as above
Card code length
Parameter defines type of Wiegand 26-66bit interface. Range: 0-
66. Default value: 26
Card code reverse order
When the option is enabled then expected card code returned by
terminals is in reverse order. Range: Yes, No. Default value: No.
PIN format
Parameter defines format of PIN returned by terminal. Range: [0]:
None, [1]: BIN, [2]: BCD, [3]: HEX. Default value: [0]: None.
PIN length
Parameter defines the length of PIN returned by terminal. Range:
0-64. Default value: 0.
PIN reverse order
When option is enabled then expected PIN returned by terminal is
in reverse order. Range: Yes, No. Default value: No.
Single key press
When option is enabled then reader transmits the whole PIN to
controller. When option is disabled then reader transmits every
pressed key separately. Range: Yes, No. Default value: No.
Terminal RACS CLK/DTA ID0/ID1**
Terminal enabled
When option is enabled then PRT terminal ID0/ID1 on RACS
CLK/DTA bus is operated. Range: Yes, No. Default value: Yes.
Keypad enabled
When option is enabled then keypad on Terminal ID0/ID1 is
operated. Range: Yes, No. Default value: Yes.
Card type
Parameter defines the data type of the card returned by terminal.
Default value: [16]: Number 40bits.
MCX402-BRD Operating Manual 08.10.2020
9/11
Parameter defines the class of the card returned by terminal.
Default value: [2]: EM.
KBD comment
Parameter defines any text or comment which corresponds to the
object. It is later displayed in VISO program.
CDI comment
as above
BUZZER comment
as above
LED SYSTEM comment
as above
LED OPEN comment
as above
LED ARMED comment
as above
* Wiegand settings are available when the factory default MCX402DR-WGx.hex firmware is uploaded into
expander
** PRT readers settings are available when MCX402DRx.hex firmware from www.roger.pl is uploaded into
expander
Memory reset
Memory reset procedure restores factory default settings including ID=100 software address.
Remove all connections from A, B, CLK and DTA terminals.
Put jumper on “64” contact and restart device with RST button on device board or by switching
supply off and on.
Remove jumper from “64” contacts when LED STAT (red), LED OPN and LED SYS are ON.
LED OPEN and LED SYSTEM will turn OFF and device shall restart automatically with factory
default settings.
Firmware update
Factory new expander is equipped with a firmware dedicated to Wiegand readers. If the expander is to be
operated with PRT readers then another firmware must be uploaded. Such firmware is available at
www.roger.pl. Firmware update is also used in case of migration from RACS 4 to RACS 5 when PR411 and
PR402 controllers are converted into MCX402 expanders. Firmware update requires RogerISP program.
Firmware update with RogerISP software
Connect device to RUD-1 interface according to Fig.8.
Put a jumper on FDM contacts.
Restart device with RST button on device board or by switching supply off and on.
Start RogerISP software.
Select serial port emulated by RUD-1 interface.
Select the option USB-RS485 Converter.
Select firmware file (*.hex).
Click Program and follow instructions on the screen.
Once the firmware is uploaded remove the FDM jumper.
Restart device.
Start Memory Reset procedure.
Installation
Enclosure with DIN rail is recommended for installation of MCX402-BRD expander. All electric connections
must be done without voltage on wires/terminals and with power supply disconnected. Optionally DIN rail
mounting clips can be removed and the expander can be installed on flat surface. It is recommended to
install the expander in the same enclosure as transformer/PSU. Prior to expander connection to the
controller specify RS485 address and configure other parameters if necessary. The expander is configured
within low level configuration by means of RogerVDM. Default address of factory new device is ID=100.
MCX402-BRD Operating Manual 08.10.2020
10/11
Fig. 9 MCX402-BRD board
MCX402-BRD terminals
Term.
Description
Term.
Description
BAT+
Battery positive pole
GND
Ground
BAT-
Battery negative pole
IN7
IN7 input line
P1
Power supply input
IN8
IN8 input line
P2
Power supply input
IO1
IO1 output line
COM1
REL1 relay common terminal
IO2
IO2 output line
NC1
REL1 relay output (NC)
IN1
IN1 input line
NO1
REL1 relay output (NO)
IN2
IN2 input line
CLK
RACS CLK/DTA interface, line CLK
GND
Ground
DTA
RACS CLK/DTA interface, line DTA
IN3
IN3 input line
GND
Ground
IN4
IN4 input line
A
RS485 communication bus, line A
TML
Power supply output 12VDC/0.2A
B
RS485 communication bus, line B
AUX
Power supply output 12VDC/1.0A
GND
Ground
NO2
REL2 relay output (NO)
IN5
IN5 input line
NC2
REL2 relay output (NC)
IN6
IN6 input line
COM2
REL2 relay common terminal
Specification
Supply voltage
Nominal 18VAC, min./max. range 17-22VAC
Nominal 12VDC, min./max. range 10-15VDC
Nominal 24VDC, min./max. range 22-26VDC
Backup battery
13.8V/7Ah, charging current app. 300mA
Average current
consumption
100 mA (excluding load points connected to AUX and/or TML outputs)
MCX402-BRD Operating Manual 08.10.2020
11/11
Inputs
Eight (IN1-IN8) NO/NC inputs, electrically biased to +12V via 15kΩ resistor,
triggering level app. 3.5V
Relay outputs
Two (REL1,REL2) relay outputs with single NO/NC contact, 30V/1.5A (REL1) and
230VAC/5A (REL2) rated
Transistor outputs
Two (IO1,IO2) open collector outputs, 15VDC/1A rated
Power supply outputs
Two power supply outputs: 12VDC/0.2A (TML) and 12VDC/1A (AUX) rated
Distances
Between controller and expander (RS485): max. 1200m
Between expander and Wiegand reader: max. 100 m
Between expander and PRT reader (RACS CLK/DTA): max. 150 m
Environmental class
Class I, indoor general conditions, temperature: +5°C to +40°C, relative humidity:
10 to 95% (no condensation)
Dimensions
80 x 115 x 28mm
Weight
approx. 100g
Certificates
CE
Ordering information
Product
Description
MCX402-BRD
I/O expander for door control with Wiegand or PRT readers
MCX402-1-KIT
1-door expander kit
MCX402-2-KIT
2-door expander kit
Product history
Version
Date
Description
MCX402-BRD v1.0
10/2017
The first commercial version of the product
This symbol placed on a product or packaging indicates that the product
should not be disposed of with other wastes as this may have a negative
impact on the environment and health. The user is obliged to deliver
equipment to the designated collection points of electric and electronic
waste. For detailed information on recycling, contact your local authorities,
waste disposal company or point of purchase. Separate collection and
recycling of this type of waste contributes to the protection of the natural
resources and is safe to health and the environment. Weight of the
equipment is specified in the document.
Contact:
Roger sp. z o.o. sp.k.
82-400 Sztum
Gościszewo 59
Tel.: +48 55 272 0132
Fax: +48 55 272 0133
Tech. support: +48 55 267 0126
E-mail: biuro@roger.pl
Web: www.roger.pl
/