n With ARM-based 32-bit SCM, highly integrated hardware, high
reliability level
n Multilingual interface (including English, Chinese or other cus‐
tomer specific languages) which can be chosen at the site,
making commissioning convenient for factory personnel
n Improved LCD wear-resistance and scratch resistance due to
hard screen acrylic
n Silicon panel and pushbuttons for better operation in high-tem‐
perature environment
n RS-485 communication port enabling remote control, remote
measuring, remote communication via ModBus protocol
n SMS (Short Message Service) function: When genset is
alarming, controller can send short messages via SMS auto‐
matically to max. 5 telephone numbers (external GSM modem
is needed). Besides this, generator status can be controlled
and checked.
n Equipped with CAN bus port to communicate with J1939
genset. Monitoring frequently-used data such as water temper‐
ature, oil pressure, speed, fuel consumption and so on of ECU
machine, and additionally also control start, stop, raising
speed, and speed droop via CAN bus port
n Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-
wire, and 2-phase 3-wire systems with voltage 120/240 V and
frequency 50/60 Hz
n easYgen-1800 only: Collects and shows 3-phase voltage, cur‐
rent, power parameter and frequency of generator or mains.
Mains Generator Line voltage (U
AB
, U
BC
, and U
CA
) Line voltage
(U
AB
, U
BC
, and U
CA
) Phase voltage (U
A
, U
B
, and U
C
) Phase
voltage (U
A
, U
B
, and U
C
)
n easYgen-800 only: Collects and shows 3-phase voltage, cur‐
rent, power parameter and frequency of generator. Generator
Line voltage (U
AB
, U
BC
, and U
CA
) Line voltage (U
AB
, U
BC
, and
U
CA
) Phase voltage (U
A
, U
B
, and U
C
) Phase voltage (U
A
, U
B
,
and U
C
)
n Phase sequence, frequency, Load current I
A
, I
B
, I
C
n Each phase: Total active power [kW], Total reactive power
[kvar], Total apparent power [kVA], Average power factor PF
n Accumulated Total generator power [kWh], [kvarh], [kVAh], and
Earth current
n easYgen-1800 only: For Mains, controller has over and under
voltage, over and under frequency, loss of phase and phase
sequence wrong detection functions
n For generator, controller has over and under voltage, over and
under frequency, loss of phase, phase sequence wrong, over
and reverse power, over current functions
n 3 fixed analog sensors (temperature, oil pressure and fuel
level)
n Flexible sensors can be set as temperature sensor, oil pres‐
sure sensor or level sensor
n Precision measure and display parameters about Engine,
Temp. (WT) °C/°F both be displayed Oil pressure (OP)
kPa/psi/bar all be displayed Fuel level (FL) %(unit) Speed
(SPD) r/min (unit) Battery Voltage (VB) V (unit) Charger
Voltage (VD) V (unit) Hour count (HC) can accumulate to max.
65535 hours. Start times can accumulate to max. 65535 times
n Protection: automatic start/stop of the genset, ATS (Auto
Transfer Switch) control with perfect failure indication and pro‐
tection function
n All output ports are relay-out
Key characteristics
System Overview
Features and Functions of bo...
37691AeasYgen-800 | Genset Control18